MAINTENANCE
We recommend that the float steam traps are serviced as necessary. Steam traps should be checked
periodically (at least yearly), to verify that they are operating correctly and to clean the internal parts and screen
(if any).
When reassembling make sure that all gasket faces are clean and always use a new gasket. Tighten cover
bolts uniformly in a diagonal sequence.
For further information refer to the relevant FLT16 brochure or consult our Sales Office.
TROUBLESHOOTING
-
If the malfunctions cannot be solved with the help of the following chart, please consult the manufacturer.
-
Some of these faults may only occur in some models.
TROUBLE SHOOTING CHART
FAULT
POSSIBLE REASON
SOLUTION
Continuous steam discharge
Damaged seat.
Incorrect installation.
Substitute seat.
check the installation position
(see IMI 1.344 E 08.03).
The condensate isn’t discharged
Or not enough discharged
Obstructed strainer.
Inadequate pressure differential.
Excessive back pressure.
Damaged float.
Proceed to an accurate clean and
identify the possible reason of
contamination.
Check the steam trap D.P. and
substitute.
Replace the steam trap by a
superior DN or use ADCAMAT.
Replace.
Temporary condensate
accumulation
Steam blocking.
Downsizing.
Use a steam trap with SLR.
Check maximum flow rate (during
start-up)
Slow initial start up
Damaged air eliminator.
The air flow is too high for the trap.
Downsizing.
Replace.
Install an additional air eliminator.
Check maximum flow rate (during
start-up)