16
American Dryer Corp.
113362 - 25
Optional Manual Bypass
Provisions are made in the dryer’s fire suppression system
for the installation of an optional manual bypass. Depending
on the model dryer, the connections for the manual bypass
are made at the “T” or “three way” fitting, located in the outlet
supply side of the water solenoid valve. The manual ball
cock shutoff valve must be located outside of the dryer at a
distance from the dryer where it is easily accessible. The
use and connections of this manual bypass are at the option
or discretion of the owner.
The water connection for the manual bypass is made to the
“T” or “three way” fitting, which has a 3/8” F.P.T. and a coupling
must be used to provide the minimum 1/2-inch (12.7 mm)
supply (feed) line.
If the rear area of the dryer or the water supply is located in
an area where it will be exposed to cold/freezing
temperatures, provisions must be made to protect these water
lines from freezing.
Electrical Requirements
No independent external power source or supply connection
is necessary. The 24-volt power to operate the fire
suppression system is accomplished internally from the
dryer controls.
!
WARNING
Electrical power must be provided to the dryer at all
times. If the main electrical power supply to the dryer
is disconnected, the fire suppression system is
inoperative!!