Chapter 2: Installation
December 20, 2004
2-12
LTPH-UM-1261-01
Optional Fan Alarm Procedure
Figure 2-3. Alarms Wire-wrap Field (TB2)
Note:
The FAN terminals wire-wrap field provides access to the Normally Open (NO), Form A fan relay
contact located on the HMU-319 management unit. A temperature monitor activates this fan relay when the
shelf temperature exceeds 45°C (±1°C) and deactivates the relay when the temperature drops below 35°C
(±1°C). If the temperature exceeds 77°C (±1°C) a critical alarm is also generated. The critical alarm resets
when the temperature drops below 40°C (±1°C).
Step
Action
1
Connect the optional fan inputs to the Alarms wire-wrap field pins 25 and 26 (see
Figure 2-3
).