in a Neutral current above 100 A. The trip device in the N-pole of the MCB could react.
Formula: worst case I
neutral
= 55000W / 3 / 230V x 1,25 = 100A
rms
.
12.6 Main transformer, cables, switchgear, busbar systems
The main transformer, the switchgear and the supply cables to the dimmer cabinet carry
these non-sinusoidal currents.
This is valid for all phase-control dimmers (thyristor, triac, and some transistor dimmers),
independent of brand and manufacturer.
A 'classic' recommendation is
- Inform the (future) supplier of the power transformer about the presence of
thyristor- controlled dimmers. He will select a suitable, type taking into account the
extra losses due to the harmonics and the increased rms current in the N
- over-size the kVA rating of the main transformer; e.g. by 50% above the expected
max. load.
12.7 Voltage distortion and 'short-circuit voltage' of the main transformer
Another aspect is that the harmonic currents cause distortion of the sine wave voltage.
And with a distorted voltage wave-form, the dimmer electronics have a harder time to find
the 'zero crossing'; unstable 'zero crossing' means that the light levels may flicker in some
instances.
In more technical terms: the combination of the source impedance of the supply system
(transformer, switchboard, busbars, and supply cables) with the harmonic currents will
distort the voltage at the input terminals of the dimmers.
Main transformer – recommendation
The transformer plays an important role. Its output voltage will show less distortion of the
sine wave if the transformer's series impedance is low, i.e. if the transformer has a low
'short- circuit voltage'. We recommend that the main supply transformer should have a
'short-circuit voltage' of max. 4%. Again, this recommendation is valid for all phase-control
dimmers (thyristor, triac, and phase-control transistor dimmers), of all brands and
manufacturers.
Содержание EURODIM Twin Tech
Страница 1: ...M 3213 1106 01 213 Installation Manual V 1 2 EURODIM Twin Tech ...
Страница 2: ......
Страница 13: ...EURODIM TWIN TECH User Manual page 11 Issue 2 1 www adbstagelight com 3 DESCRIPTION ...
Страница 50: ...EURODIM TWIN TECH User Manual page 48 Issue 2 1 www adbstagelight com 3 8 8 142 990 596 216 ...
Страница 52: ...EURODIM TWIN TECH User Manual page 50 Issue 2 1 www adbstagelight com 11 2 3500 01 660 Power Modules 9 16 ...
Страница 53: ...EURODIM TWIN TECH User Manual page 51 Issue 2 1 www adbstagelight com 11 3 3500 01 670 Power Modules 17 24 ...
Страница 54: ...EURODIM TWIN TECH User Manual page 52 Issue 2 1 www adbstagelight com 11 4 3500 01 680 Power Modules 25 32 ...
Страница 55: ...EURODIM TWIN TECH User Manual page 53 Issue 2 1 www adbstagelight com 11 5 10 kW Module Connection ...
Страница 63: ...EURODIM TWIN TECH User Manual page 61 Issue 2 1 www adbstagelight com 14 CONFIGURATION TABLES ...
Страница 65: ...EURODIM TWIN TECH User Manual page 63 Issue 2 1 www adbstagelight com ...
Страница 67: ...EURODIM TWIN TECH User Manual page 65 Issue 2 1 www adbstagelight com Notes ...
Страница 68: ......
Страница 70: ......
Страница 71: ...M 3213 E 09p Subject to modifications www adbstagelight com info adblighting com ...