Standard System Features
•
Commissioning can be performed by the airport's technical staff (“out-of-the-box”), simplifying system delivery and setup
on site. ADB SAFEGATE support available if needed.
•
The lighting control system is built around an integrated Touchscreen/Panel PC, requiring only minimal installation space
in the ATC tower. It incorporates a Human Machine Interface (HMI) with control functionalities for approach, runway,
taxiway and apron visual aids.
•
High-contrast, anti-glare resistive 12-inch LCD Touchscreen. Standard Touchscreen can be either pedestal or flush mount.
•
Intuitive user interface provides buttons that lead air traffic controllers through lighting control tasks
•
The ADB SAFEGATE Navigator can be remotely controlled using an L-854 Radio Control, photocell or phone dial-in device
•
A static airfield touchscreen graphic (.png file) can be added
•
Provides visual alarm indications for all monitored points
•
Soft-start CCR control provides programmable delays between intensity step switching
•
Based on Windows
™
Embedded Standard 2009
•
Entire system uses only off-the-shelf components
•
Highly reliable and effective PLC-based control and monitoring of CCRs and auxiliary circuits
•
If the controllable item is a CCR, each CCR can have up to 3 dedicated feedback contact points (Primary Power; Remote/
Local status; CCR Output Current Sensing) or may have a single General Fault feedback point. A General Fault feedback
point is used, for example, to tie an FAA L-827/L-829 Fault indication into the system.
•
Panel touchscreen has embedded PC with flash memory – no hard drive, fans or moving parts – limiting the need for
maintenance and providing a highly reliable control system
•
PLC enclosure can be installed in either the tower (if space is available) or an electrical vault (standard 9 feet/3 m, or
optionally, up to 4,000 feet/1,219 m away) using EIA-485 communication
•
Fail-safe – Fail-safe provides preset relays to meet airport operational requirements. Fail-safe is manually wired to select a
dedicated CCR step. Fail-safe can be manually overridden for maintenance troubleshooting purposes.
Hardware Options
•
Second Touchscreen for tower or vault
•
15-inch Touchscreen display
•
Audible alarm speakers
•
Communication methods: Fiber optic or wireless radio communication link
•
CCR Monitoring Kit: Primary Power; Remote/Local and CCR ON Current Sensor
•
UPS with UL1449 surge protection
•
Remote dial-in capability (modem and software) for remote service and maintenance. A dedicated telephone line
(customer supplied) is connected to a modem that is added to the panel PC.
•
L-854 radio remote control (see data sheet 3002)
•
Phone dial-in device for password-protected lighting control
•
Photocell (day vs. night input)
Operating Conditions
Operating Temperature:
0 °C (+32 °F) to +45 °C (+113 °F)
Extended Operating Temperature
1
:
-18 °C (0 °F) to +45 °C (+113 °F)
Relative Humidity:
10-95% at 40 °C (non-condensing)
Notes
ADB SAFEGATE RELIANCE Navigator
™
Installation and Operation Manual
ADB Safegate Navigator
6
Copyright
©
ADB Safegate, All Rights Reserved