ADB SAFEGATE RELIANCE Navigator
™
Installation and Operation
Manual
Airport Lighting Control System
User Manual
96A0363, Rev. i, 2019/10/31
Страница 1: ...ADB SAFEGATE RELIANCE Navigator Installation and Operation Manual Airport Lighting Control System User Manual 96A0363 Rev i 2019 10 31 ...
Страница 2: ......
Страница 3: ...d are guaranteed to be merchantable and fit for the ordinary purposes for which such products are made ADB SAFEGATE L858 Airfield Guidance Signs are warranted against mechanical and physical defects in design or manufacture for a period of 2 years from date of installation per FAA AC 150 5345 44 applicable edition Note See your sales order contract for a complete warranty description All Products ...
Страница 4: ...ent parts or accessories Failing to make sure that auxiliary equipment complies with approval agency requirements local codes and all applicable safety standards if not in contradiction with the general rules Using materials or auxiliary equipment that are inappropriate or incompatible with your ADB SAFEGATE equipment Allowing unskilled personnel to perform any task on or with the equipment ADB SA...
Страница 5: ...ring Considerations 12 3 4 Connect the Computer 12 3 5 Wiring From CCRs 13 3 5 1 Wiring from Controllable Element Monitoring Points TB3 and TB4 13 3 5 2 Wiring for Controllable Element Points 14 3 5 3 Wiring Notes for Separate B1 B10 Control 15 3 5 4 Watchdog Wiring 15 3 5 5 Power Wiring TB1 15 4 0 Operation 17 4 1 Starting the Touchscreen Program 17 4 2 Overview of the Touchscreen 18 4 3 Choosing...
Страница 6: ...ADB SAFEGATE RELIANCE Navigator Installation and Operation Manual TABLE OF CONTENTS vi Copyright ADB Safegate All Rights Reserved ...
Страница 7: ...o observe this warning may result in personal injury death or equipment damage ARC Flash may cause blindness severe burns or death WARNING Wear personal protective equipment Failure to observe may result in serious injury WARNING Do not touch Failure to observe this warning may result in personal injury death or equipment damage CAUTION Failure to observe a caution may result in equipment damage Q...
Страница 8: ... specified by applicable safety regulations If safety devices must be removed for installation install them immediately after the work is completed and check them for proper functioning prior to returning power to the circuit Failure to follow this instruction can result in serious injury or equipment damage Additional Reference Materials Important Information IEC International Standards and Confo...
Страница 9: ...ety devices as specified by applicable safety regulations If safety devices must be removed for installation install them immediately after the work is completed and check them for proper functioning Route electrical wiring along a protected path Make sure they will not be damaged by moving equipment Never operate equipment with a known malfunction Do not attempt to operate or service electrical e...
Страница 10: ...he cabinet by touching a conductive earthed part of the cabinet Electronic modules or components must not be brought in contact with highly insulating materials such as plastic sheets synthetic fiber clothing They must be laid down on conductive surfaces The tip of the soldering iron must be grounded Electronic modules and components must be stored and transported in conductive packing Failure to ...
Страница 11: ... L 841 type providing basic control and monitoring of airfield ground lighting functions 2 2 1 Airport Lighting Control System Compliance with Standards FAA L 821 AC 150 5345 3 Current Edition ETL Certified ICAO Annex 14 Vol 1 para 5 3 and 8 3 and Aerodrome Design Manual part 5 para 3 4 and 3 7 Military UFC 3 535 01 par 15 3 System Overview The ADB SAFEGATE RELIANCE Navigator Airport Lighting Syst...
Страница 12: ... General Fault feedback point is used for example to tie an FAA L 827 L 829 Fault indication into the system Panel touchscreen has embedded PC with flash memory no hard drive fans or moving parts limiting the need for maintenance and providing a highly reliable control system PLC enclosure can be installed in either the tower if space is available or an electrical vault standard 9 feet 3 m or opti...
Страница 13: ...AC 50 60 Hz PLC Cabinet Input power Single phase 100 264 VAC 50 60 Hz Dimensions 12 Touchscreen Panel PC with Stand H W D 10 6 13 41 2 78 in 26 9 34 06 7 06 cm 15 Touchscreen Panel PC with Stand H W D 12 5 15 6 2 78 in 31 76 39 65 7 06 cm Stainless Steel Enclosure H W D 41 75 35 75 10 75 in 106 0 90 8 27 3 cm Figure 1 Typical Preset Lighting Page Shown with optional static graphic 96A0363 Rev i 20...
Страница 14: ...mmunications 43A4380 04 NAVIGATOR System Externals Wireless Communications 105A0863 12 1 All in one touchscreen computer 105A0870 L157 15 All in one touchscreen computer 44A7675 01 PLC Enclosure Assembly Drawing 44A7675 02 PLC Enclosure Assembly Drawing 43A4582 01 Vault Enclosure Assembly Internal Wiring Diagram Drawing 43A4582 02 Vault Enclosure Assembly Internal Wiring Diagram Drawing 43A4582 03...
Страница 15: ...e Internal Wiring Diagram 44A7677 K2 4G 2 Wireless Radio Communication Enclosure 144A2440 XX 2 4 GHz Yagi antenna and grounding assembly 94A0454 DC DC Current Sensing Relay Refer to the ADB Safegate Web site at www adbsafegate com for a copy of these drawings and additional information located in the Product Center 2 2 4 Components The RELIANCE NAVIGATOR comes with the following standard component...
Страница 16: ...in components 2 2 5 Inspect Delivered Items Inspect the carton and contents for any signs of damage Notify ADB if any parts are missing or damaged ADB SAFEGATE RELIANCE Navigator Installation and Operation Manual ADB Safegate Navigator 10 Copyright ADB Safegate All Rights Reserved ...
Страница 17: ...t the console area to fit Place the touchscreen down in the console making sure that the bezel catches on the outside of the cutout for a flush fit The power cord will be attached underneath the screen when it is mounted and should be plugged into critical power in the ATCT Refer to 105A0863 for specific touchscreen computer port connections These will vary depending on the options purchased so pl...
Страница 18: ...nications extension cable is being used it is important to bring that cable into the PLC enclosure via a separate conduit penetration to minimize possible interference problems The following sections provide general guidelines only For all wiring refer to Installation Drawings see Associated Drawings and Documents 3 4 Connect the Computer The airport is to supply the CAT5 cable from the PC to the ...
Страница 19: ...s a CCR from TB4 labelled EXTERNAL DEVICE 24 VDC SOURCE Each point on TB4 is fused so that the cabinet power supply is protected from an outside fault The PLC input modules are designed and pre wired to actuate upon return of this alarm condition voltage Hence it is required that the source voltage be isolated from the controllable element power supply by an appropriate isolated contact such as re...
Страница 20: ...losure relays will need to be added for the system to read these inputs correctly If the PCR or photocell is a contact closure the relay can be sourced 24V DC from the power block to the right of the remote control inputs If the PCR or photocell does not contain dry contact closures the relays mentioned previously will need to be used Do not use a 120V AC control signal directly into TB3 3 5 2 Wir...
Страница 21: ...ol elements 8 9 11 and 12 cannot be wired with a separate B10 control line Regulators that do not require a separate B10 control line should be used in these positions 3 5 4 Watchdog Wiring The watchdog is wired from the factory and does not need any field connections in order to function The 3 position switch on the front of the PLC assembly is used to control failsafe and watchdog functions The ...
Страница 22: ...ADB SAFEGATE RELIANCE Navigator Installation and Operation Manual Installation 16 Copyright ADB Safegate All Rights Reserved ...
Страница 23: ...n Navigator application has been started several programs will begin to start in the background These programs are Circuit State Engine CSE Vault PLC Manager For each of these programs a dialog box will appear which can be ignored when starting up the touchscreen application These programs are required for the ADB SAFEGATE RELIANCE NAVIGATOR system to function properly but have no functional use t...
Страница 24: ...splays either airport name or current status of presets if configured Overview of the Touchscreen Alarm Ackbutton Button color turns red on alarm touch to acknowledge alarm Using the Alarm Ack Button Clean Screenbutton Touch to deactivate all buttons while screen is being cleaned Using the Clean Screen Button Exit to Main Menubutton Touch to exit the Touchscreen program Exiting Programs Optional a...
Страница 25: ...ts were selected in the Primary Configuration touch the Preset button to display the presets in the lower portion of the window 4 4 Using the Control Buttons The Control buttons allow you to turn any controllable item on or off CCR Beacon Generator etc The primary Control button displays the item name and its current status The display differs according to the button style selected during Primary ...
Страница 26: ...ows up once the step command button is pressed To turn an item on or off If necessary touch a Lighting Page button Touch a Control button for example TWY A Touch the appropriate Step button for that item for example touch STEP 2 to turn the item on to the second step or touch OFF turn the item off The CONFIRM and REJECT buttons pop up to the right of the Step buttons Touch the CONFIRM button to pe...
Страница 27: ...is selected on the page Figure 11 Control Buttons To turn an item on or off If necessary touch a Lighting Page button Touch the appropriate Step button for an item for example touch STEP 2 to turn the item on to the second step or touch OFFturn the item off If desired touch Step buttons for other items before confirming or rejecting the changes Touch the CONFIRM button to perform the selected oper...
Страница 28: ... and NIGHT another might be Dusk Visibility up to eight configured states for example Less than 1 mile 1 2 miles More than 5 miles Runway Direction usually two directions To change a preset condition simply touch the appropriate button and confirm your choice For example When it begins getting dark outside touch the NIGHT preset button Touch the CONFIRM button to change the preset condition or tou...
Страница 29: ...selected during Primary Configuration Table 4 Alarm Conditions Monitoring point If selected during configuration Primary Power The touchscreen displays an alarm when the NAVIGATOR detects that the primary power to the CCR beacon or other item is OFF Remote Local The touchscreen displays an alarm when the item is switched to Local control or OFF preventing remote control of the item such as during ...
Страница 30: ...the file Vault log and the acknowledgement is recorded in the file TchScrn log Both log files are in the log folder in the program directory C ALCSJ 4 6 2 Acknowledging an Alarm To acknowledge an alarm when the ALARM ACK button is flashing red and the audible alarm is sounding Touch the ALARM ACK button to acknowledge the alarm The button remains red until the alarm condition is cleared and the au...
Страница 31: ...ilable When you are ready touch the CLEAN SCREEN button at the top of the window typically on the PRESET PAGE if used Figure 15 Clean Screen Button After the Clean Screen button is touched the screen display changes to the following 96A0363 Rev i 2019 10 31 25 Copyright ADB Safegate All Rights Reserved ...
Страница 32: ... from the Vault application The password for these operations is sba without the quotes case sensitive Figure 17 Example Password Screen Exiting from the Navigator will also require the use of the system password 4 9 Exiting Programs The Touchscreen application must be running for operators to control the configured items At times however you will need to exit the program to perform setup computer...
Страница 33: ... has a dialog box with an Exit button as shown at right Each program must be closed separately To close each of these three programs Click on the associated Exit button This opens the Please Enter Password window Enter the system password and click OK The Touchscreen application closes and the display returns to the Windows desktop Lights will go to a hardware failsafe unless the PLC panel switch ...
Страница 34: ...ADB SAFEGATE RELIANCE Navigator Installation and Operation Manual Operation 28 Copyright ADB Safegate All Rights Reserved ...
Страница 35: ...econd PC8 Notes All fiber optic cables should be terminated with ST style connectors Fiber optic cable and connectors not provided by ADB SAFEGATE 1 PLC cabinet must be within 9ft of Touchscreen PC 2 Fiber optic cable supplied by others multi mode wavelength 1300 nanometers single mode 1310 nanometers 3 For use with 120 VAC 60 Hz operation only 4 Use this option if all CCRs present do not require ...
Страница 36: ...ADB SAFEGATE RELIANCE Navigator Installation and Operation Manual Parts 30 Copyright ADB Safegate All Rights Reserved ...
Страница 37: ...all When you have an airfield lighting or system control system problem it is our goal to support airfield maintenance staff as quickly as possible To support this effort we ask that you have the following information ready before calling The airport code If not with an airport then company name prefer customer id number Contact phone number and email address Product with part number preferable or...
Страница 38: ...onents and sub contractor operations ADB SAFEGATE offers a recycling program for our products to all customers worldwide whether or not the products were sold within the EU ADB SAFEGATE products and or specific electrical and electronic component parts which are fully removed separated from any customer equipment and returned will be accepted for our recycling program All items returned must be cl...
Страница 39: ...act Tel 46 0 40 699 17 00 Fax 46 0 40 699 17 30 Email marketing adbsafegate com Internet www adbsafegate com ADB SAFEGATE Airfield Technologies Ltd China ADB SAFEGATE China Unit 603 D Block CAMIC International Convention Center No 3 Hua Jia Di East road ChaoYang district Beijing 100102 P R China Contact Tel 86 10 8476 0106 Fax 86 10 8476 0090 Email china safegate com Internet www adbsafegate com A...
Страница 40: ......