4.5 Relay Board
Figure 5: Relay Board
. The Radio Control Equipment provides for relay outputs for control of external lighting. Either of the two relay
sets can be configured for either cumulative (incremental) or, individual output. See
for a description of
the logic used. All relay contacts are dry, and can switch 48Vdc or 120Vac through either set of relays for CCR control.
Table 6: Cumulative (Incremental) Operation
Radio Clicks Detected
Active Control Output
3
5
7
3-Radio Clicks
5-Radio Clicks
7-Radio Clicks
Table 7: Individual Operation
Radio Clicks Detected
Active Control Output
3
5
7
3-Radio Clicks
5-Radio Clicks
7-Radio Clicks
The output voltage required from the relays (u48V DC or 120V AC) is provided to the relays through ACom (Terminal
Strip #4) for relays A3, A5, A7 or BCom (Terminal Strip #11) for relays B3, B5, B7. See
.
L-854 Radio Control Equipment
Theory of Operation
16
Copyright
©
ADB Safegate, All Rights Reserved
Содержание L-854
Страница 1: ...L 854 Radio Control Equipment RCE Type I Style A User Manual 96A0390 Rev K 2019 02 01 ...
Страница 2: ......
Страница 6: ...L 854 Radio Control Equipment TABLE OF CONTENTS vi Copyright ADB Safegate All Rights Reserved ...
Страница 18: ...L 854 Radio Control Equipment Options 12 Copyright ADB Safegate All Rights Reserved ...
Страница 24: ...L 854 Radio Control Equipment Theory of Operation 18 Copyright ADB Safegate All Rights Reserved ...
Страница 32: ...L 854 Radio Control Equipment Operation 26 Copyright ADB Safegate All Rights Reserved ...
Страница 34: ...L 854 Radio Control Equipment Maintenance 28 Copyright ADB Safegate All Rights Reserved ...
Страница 48: ......