RECOMMENDATIONS FOR THE BOILER MAINTENANCE
Essential recommendations for the electrical safety
•
Before opening the boiler for maintenance, turn off the boiler by pushing on the
ON/OFF master switch.
•
Isolate the external power supply of the appliance before performing any
operation, unless it is required to take measurements or perform system setup.
Essential recommendations for safety
•
Water flowing out of the drain valve may be extremely hot and could cause severe
scalding.
•
Do not use solvents to clean any of the burner components. The components could
be damaged, resulting in unreliable or unsafe operation.
•
Check the tightness of the flue pipe connections.
Essential recommendations for the correct operation of the appliance
•
It is recommended to have the boiler and the burner serviced at least once a year
or every 1,500 hours
by a qualified technician, preferably at the start of the heating
season. More frequent servicing may be required depending on boiler use. Please
consult your installer for advice.
•
The boiler and burner maintenance will be carried out by a qualified engineer, and
the defective parts may only be replaced by genuine factory parts.
•
Make sure to replace any gaskets or seals on the removed components before
reinstalling them.
•
To ensure maximum efficiency and reliability of the unit, it is recommended that
the end-user perform the periodic checks mentioned in the Safety section of this
manual.
•
Control the tightness of the hydraulic circuit connections.
N1 - N2 - N3 eco : A1005170 - 664Y7700 • B
en
20
EN
FR
NL
ES
IT
DE
PL
RU
MAINTENANCE
TOOLS REQUIRED FOR MAINTENANCE
BOILER SHUT DOWN FOR MAINTENANCE
1.
Switch the boiler off using the ON/OFF master switch and isolate the external power supply.
2.
Close the oil supply valve of the boiler.
PERIODIC BOILER MAINTENANCE TASKS
Tasks
Frequency
Periodic
inspec-
tion
1 year
2 years
End-user
Professional
1.
Make sure that the system water pressure is at least 1 bar
when cold. Top up the system if necessary, adding small
quantities of water at a time. In case of repeated fills, call
your installer.
X
X
2.
Check that there is no water on the floor under the boiler.
Call your installer if there is.
X
X
3.
Check that all oil, hydraulic and electrical connections are
correctly fastened and tight.
X
4.
Check the flue gas exhaust: correct fastening, correct in-
stallation, no leaks or clogging.
X
5.
Check that there is no discoloured or cracked area on the
burner chamber plate.
X
6.
Check the combustion parameters (CO and CO
2
), see the
burner manual.
X
7.
Check visually the heating body: no evidence of corrosion,
soot deposits or damages. Carry out all required cleaning
tasks, repairs and replacements that might be required.
X
8.
Check the burner nozzle and ignition electrode, refer to
the burner manual.
X
9.
Remove the front panel, open the front door and clean
the combustion chamber, see “Cleaning the Combustion
Chamber” on page 21.
X