RECOMMENDATIONS FOR THE PREVENTION OF CORROSION AND 

SCALING IN HEATING SYSTEMS

 

How oxygen and carbonates can affect the heating system

Oxygen and dissolved gasses in the water of the primary circuit contribute to the oxi-

dation and the corrosion of the system components that are made of ordinary steel 

(radiators, ...). The resulting sludge is then deposited in the appliance exchanger.

The combination of carbonates and carbon dioxide in the water results in the formation of scale 

on the hot surfaces of the installation, including those of the appliance exchanger.

 

These deposits in the heat exchanger reduce the water fl ow rate and thermally insulate the ex-

change surfaces, which is likely to damage them.

Sources of oxygen and carbonates in the heating circuit

The primary circuit is a closed circuit; the water it contains is therefore isolated from the mains 

water. When maintaining the system or fi lling up the circuit, water renewal results in the addition 

of oxygen and carbonates in the primary circuit. The larger the water volume in the system, the 

larger the addition.

 

Hydraulic components without an oxygen barrier (PE pipes and connections) admit oxygen into 

the system.

Prevention Principles

1.  Clean the existing system before installing a new appliance

Before the system is fi lled, it must be cleaned in accordance with standard EN14336. 

Chemical cleaning agents can be used.

-  If the circuit is in bad condition, or the cleaning operation was not efficient, or the volume of 

water in the installation is substantial (e.g. cascade system), it is recommended to separate 

the appliance from the heating circuit using a plate-to-plate exchanger or equivalent. In 

that case, it is recommended to install a hydrocyclone or magnetic filter on the installation 

side.

2.  Limit the fill frequency

Limit fill operations. In order to check the quantity of water that has been added into the 

system, a water meter can be installed on the filling line of the primary circuit.

-  Automatic filling systems are not recommended unless the fill frequency is monitored and 

the scale and corrosion inhibitor remain at the correct levels.

-  If your installation requires frequent water refilling, make sure your system is free of water 

leaks.

-  Inhibitors may be used in accordance with standard EN 14868.

3.  Limit the presence of oxygen and sludge in the water

A deaerator (on the appliance flow line) combined with a dirt separator (upstream of the 

appliance) must be installed according to the manufacturer's instructions.

-  ACV recommends using additives that keep the oxygen in solution in the water, such as 

Fernox (www.fernox.com) and Sentinel (www.sentinel-solutions.net) products.

-  The additives must be used in accordance with the instructions issued by the manufacturer 

of the water treatment product.

4.  Limit the carbonate concentration in the water

-  The fill water must be softened if its hardness is higher than 20° fH (11,2° dH).

-  Check regularly the water hardness and enter the values in the service log.

-  Water hardness table :

 

Water hardness

°fH

°dH

mmolCa(HCO3)2 / l

Very soft

0 - 7

0 - 3.9

0 - 0.7

Soft

7  - 15

3.9 - 8.4

0.7 - 1.5

Fairly hard

15 - 25

8.4 - 14

1.5 - 2.5

Hard

25 - 42

14 - 23.5

2.5 - 4.2

Very hard

> 42

> 23.5

> 4.2

5.  Control the water parameters

-  In addition to the oxygen and the water hardness, other parameters of the water must be 

checked.

-  Treat the water if the measured values are outside the range.

 

Acidity

6,6 < pH < 8,5

Conductivity

< 400 μS/cm (at 25°C)

Chlorides

< 125 mg/l

Iron

< 0,5 mg/l

Copper

< 0,1 mg/l

N1 - N2 - N3 eco : A1005170 - 664Y7700 • B

en

10

EN

FR

NL

ES

IT

DE

PL

RU

TECHNICAL CHARACTERISTICS

Содержание N1 ECO

Страница 1: ...A1005170 664Y7700 B EN FR NL ES IT DE PL RU INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS for the Installer and the User eco N1 N2 N3...

Страница 2: ...NSTALLATION 14 Safety Instructions for the Installation 14 Package contents 14 Tools Required for the Installation 14 Burner installation 15 Oil Connection 15 Electrical Connection 16 Recommendations...

Страница 3: ...replaced by genuine factory parts General remarks The availability of certain models as well as their accessories may vary according to markets The manufacturer reserves the right to change the techn...

Страница 4: ...electrical safety electrical hazard Essential recommendation for the correct operation of the appliance or the system General remark Safety valve connected to the sewage system Connection to the sewag...

Страница 5: ...n 5 USER S GUIDE The part number Code and serial number N of the appliance are indicated on its rating plate and must be provided to ACV in case of warranty claim Failure to do so will make the claim...

Страница 6: ...x position WHAT TO CHECK ON A REGULAR BASIS Essential recommendations for the correct operation of the appliance ACV recommends to check the system at least every 6 months as follows Check that the sy...

Страница 7: ...at the rear of the boiler and preset at 45 C delays the heating pump activation This prevents the risks of corrosion of the combustion chamber Production of domestic hot water The N eco boilers can be...

Страница 8: ...ation with very low emissions Refer to the burner technical manual for installation operation and maintenance instructions and for the technical characteristics Key 1 Motor 2 Oil pump with filter 3 Ph...

Страница 9: ...t PCI max kW 25 6 31 3 45 1 Output at 100 80 60 C kW 24 7 30 3 43 4 Efficiency at 100 80 60 C 96 5 96 7 96 2 Efficiency at 30 load EN677 98 5 97 9 97 2 NOx Class 5 Weighted mg kWh 110 110 110 CO Max o...

Страница 10: ...it is recommended to install a hydrocyclone or magnetic filter on the installation side 2 Limit the fill frequency Limit fill operations In order to check the quantity of water that has been added int...

Страница 11: ...up the boiler and check regularly the water level Fill with water as necessary It is mandatory to ventilate the boiler room The high or low air vent opening dimensions depend on the boiler power and...

Страница 12: ...nt opening dimensions depend on the boiler power and the boiler room size Refer to the local regulations in force B23 E A B F C D FLUE PIPE CONNECTION TYPES It is mandatory to use ACV flue systems to...

Страница 13: ...6 8 9 L1 T2 T1 N PE M Br B Bk G G Br Bk G Bk B Y Gr B R G B Y Gr G V W B Y Gr Y Gr Br Y Gr B Bk G L1 T1 T2 S3 B4 N 10 T1 T2 S3 B4 Boiler N1 N2 N3 eco boiler wiring diagram 1 ON OFF master switch 2 Mi...

Страница 14: ...and knowledge unless supervised or unless they have been given instruction concerning the use of the appliance by a person responsible for their safety Essential recommendations for the correct opera...

Страница 15: ...rsonal injury or death Essential recommendations for the correct operation of the appliance Bleed the oil duct and check thoroughly if all the boiler tubes both internal and external are tight Control...

Страница 16: ...B en 16 EN FR NL ES IT DE PL RU INSTALLATION ELECTRICAL CONNECTION T2 S3 T1 N L1 B4 T2 S3 T1 N L1 B4 2 M N PE 230 V 50HZ L1 t 1 3 1 Room thermostat 2 System heating pump 3 Bridge to be removed before...

Страница 17: ...ircuit which is adapted to the boiler power size and the type of system General remark The circuit illustrations are basic principle diagrams only HEATING CONNECTION Typical connection high temperatur...

Страница 18: ...first put the DHW circuit under pressure before pressurizing the heating primary circuit Refer to the hot water preparation tank manual for more information Set up conditions External power supply is...

Страница 19: ...ctions detailed in the technical manual of your burner 2 Adjust CO2 according to the values provided in the basic adjustment table below and by setting the oil pressure as well as the air flap as desc...

Страница 20: ...nd user perform the periodic checks mentioned in the Safety section of this manual Control the tightness of the hydraulic circuit connections N1 N2 N3 eco A1005170 664Y7700 B en 20 EN FR NL ES IT DE P...

Страница 21: ...ter N1 N2 N3 eco A1005170 664Y7700 B EN FR NL ES IT DE PL RU en 21 MAINTENANCE CLEANING THE COMBUSTION CHAMBER Set up conditions Boiler shut down External power supply isolated Oil supply closed Front...

Страница 22: ...N1 N2 N3 eco A1005170 664Y7700 B en 22 EN FR NL ES IT DE PL RU SERVICE LOG Service date CO2 Flue gas T Efficiency Remarks Name Signature SERVICE LOG...

Страница 23: ...heat output at 30 of rated heat output P1 kW 9 04 10 80 16 10 at rated output and high temp regime P4 kW 24 65 30 3 43 42 Useful efficiency at 30 of rated heat output 1 98 47 97 93 97 66 at rated outp...

Страница 24: ...application Low Temperature Low Temperature Low Temperature declared load profile for water heating Seasonal space heating energy efficiency class B B B Water heating efficiency class rated heat outp...

Отзывы: