GENERAL RECOMMENDATIONS FOR CHIMNEY CONNECTION

Essential recommendations for safety

• 

 Do  not install the boiler into a common flue piping with any other gas or oil 

appliances. This will cause flue gas spillage or appliance malfunction.

• 

Verify installed combustion air and flue piping are sealed gas tight and meet all 

provided instructions and applicable codes and standards.

• 

Failure to properly support the flue system can cause the flue system to fail, 

resulting in substantial property damage, serious injury, or death.

• 

A byproduct of any gas/oil fired appliance is carbon monoxide. Failure to install 

carbon monoxide detectors with alarms can result in serious injury, or death. Refer 

to applicable local regulations.

Essential recommendations for the correct operation of the appliance
• 

A condensation outlet connected to the sewer must be fitted close to the boiler to 

prevent the condensation products from the flue pipe from running into the boiler.

• 

Install a condensate neutralisation system if required by national and/or local 

regulations and have it cleaned regularly.

• 

Only use flue system components from the same manufacturer to connect this 

appliance and ensure that the pipe and connection diameters all match.

• 

Make sure to secure the flue piping to a solid structure.

• 

Exclusively use provided brackets to support the flue system.

• 

Install the horizontal flue pipes with a slight slope of 5 cm per meter (3°), so that the 

acid condensation water  flows to a condensate recovery container and does not 

damage the heating body.

≤0,5 m

≤2,0 m

≤1,0 m

≤1,0 m

4

1

3

1

≤0,25 m

≤2,0 m

≤0,25 m

4

2

≤0,25 m

≤0,25 m

≤2,0 m

4

2

Slope = 3°

1.  Each elbow and straight element will be secured at the sleeve.
2.  In case the straight element before or after the first elbow is shorter than 25 cm, 

secure the straight element after the elbow using a bracket.

3.  In case a straight (horizontal or sloped) element is longer than 1 m, support the element in 

its center using a clamp, making sure to allow free movement of the pipe.

4.  Secure with a clamp every 2 meters in vertical piping/1 meter in horizontal/sloped 

piping, making sure to distribute the clamps evenly on the length of piping.

• 

If the appliance is provided with a condensate drain assembly, make sure to install 

the complete assembly on the boiler.  If the assembly is incomplete, replace the entire 

assembly.

• 

Make sure that the condensate drain assembly is filled with water before starting 

up the boiler and check regularly the water level. Fill with water as necessary.

• 

It is mandatory to ventilate the boiler room. The high or low air vent opening 

dimensions depend on the boiler power and the boiler room size. Refer to the local 

regulations in force.

• 

If the combustion air inlet is located in an area likely to cause or contain 

contamination, or if products which could contaminate the air cannot be removed, 

the combustion air must be repiped and terminated at another location. 

• 

Pool, laundry, common household, and hobby products often contain fluorine 

or chlorine compounds, which can form strong acids and corrode the internal 

components and flue system.

• 

In the case of parallel flue systems, make sure to maintain sufficient distance 

(at least 40 mm) between the boiler flue piping and combustible materials, and 

between the flue pipe and air inlet pipe if the latter is made of plastic material.

• 

Do not use screws to fasten together any flue pipe elements or any PP air inlet 

elements.

• 

Do not bond piping elements together using glue (e.g. silicone) or foam (e.g. PUR). 

General remark

• 

For safety reasons and to make assembly easier, it is recommended to prefer the 

use of concentric flue pipes when possible.

• 

It is recommended to isolate the flue piping in damp rooms to prevent condensation 

water from forming on the piping and drip.

• 

When cutting the pipes to dimension, make sure to cut squarely and deburr the 

edges to prevent seals from being incorrect or damaged.

• 

To make piping assembly easier, exclusively use a mixture of water and soap (1%) 

on the extremity of the pipe to be fit in.

• 

When fitting metal flue pipes, make sure to always fit the pipe into the sleeve to 

the end stop.

• 

When fitting plastic flue pipes, make sure to allow material expansion by leaving 

about 10 mm between the pipe end and the sleeve end stop.

• 

Make sure to install the piping without any strain.

• 

Make sure to install an inspection opening in the flue system.

• 

When connecting the flue pipes, make sure not to exceed the maximum length 

recommended for the product, otherwise the system power might decrease.

• 

ACV-approved components will be used for the chimney connection. Failure to do 

so will make any warranty claim void.

• 

For C63 connection type (not allowed in Belgium), make sure to use the correct 

piping material according to the resistance to temperature, pressure, chemical 

composition of flue, condensation and soot. A code (as explained in EN 1443), 

marked on the pipe, allows to determine if the material complies with the flue 

system requirements.

N1 - N2 - N3 eco : A1005170 - 664Y7700 • B

EN

FR

NL

ES

IT

DE

PL

RU

en

11

TECHNICAL CHARACTERISTICS

Содержание N1 ECO

Страница 1: ...A1005170 664Y7700 B EN FR NL ES IT DE PL RU INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS for the Installer and the User eco N1 N2 N3...

Страница 2: ...NSTALLATION 14 Safety Instructions for the Installation 14 Package contents 14 Tools Required for the Installation 14 Burner installation 15 Oil Connection 15 Electrical Connection 16 Recommendations...

Страница 3: ...replaced by genuine factory parts General remarks The availability of certain models as well as their accessories may vary according to markets The manufacturer reserves the right to change the techn...

Страница 4: ...electrical safety electrical hazard Essential recommendation for the correct operation of the appliance or the system General remark Safety valve connected to the sewage system Connection to the sewag...

Страница 5: ...n 5 USER S GUIDE The part number Code and serial number N of the appliance are indicated on its rating plate and must be provided to ACV in case of warranty claim Failure to do so will make the claim...

Страница 6: ...x position WHAT TO CHECK ON A REGULAR BASIS Essential recommendations for the correct operation of the appliance ACV recommends to check the system at least every 6 months as follows Check that the sy...

Страница 7: ...at the rear of the boiler and preset at 45 C delays the heating pump activation This prevents the risks of corrosion of the combustion chamber Production of domestic hot water The N eco boilers can be...

Страница 8: ...ation with very low emissions Refer to the burner technical manual for installation operation and maintenance instructions and for the technical characteristics Key 1 Motor 2 Oil pump with filter 3 Ph...

Страница 9: ...t PCI max kW 25 6 31 3 45 1 Output at 100 80 60 C kW 24 7 30 3 43 4 Efficiency at 100 80 60 C 96 5 96 7 96 2 Efficiency at 30 load EN677 98 5 97 9 97 2 NOx Class 5 Weighted mg kWh 110 110 110 CO Max o...

Страница 10: ...it is recommended to install a hydrocyclone or magnetic filter on the installation side 2 Limit the fill frequency Limit fill operations In order to check the quantity of water that has been added int...

Страница 11: ...up the boiler and check regularly the water level Fill with water as necessary It is mandatory to ventilate the boiler room The high or low air vent opening dimensions depend on the boiler power and...

Страница 12: ...nt opening dimensions depend on the boiler power and the boiler room size Refer to the local regulations in force B23 E A B F C D FLUE PIPE CONNECTION TYPES It is mandatory to use ACV flue systems to...

Страница 13: ...6 8 9 L1 T2 T1 N PE M Br B Bk G G Br Bk G Bk B Y Gr B R G B Y Gr G V W B Y Gr Y Gr Br Y Gr B Bk G L1 T1 T2 S3 B4 N 10 T1 T2 S3 B4 Boiler N1 N2 N3 eco boiler wiring diagram 1 ON OFF master switch 2 Mi...

Страница 14: ...and knowledge unless supervised or unless they have been given instruction concerning the use of the appliance by a person responsible for their safety Essential recommendations for the correct opera...

Страница 15: ...rsonal injury or death Essential recommendations for the correct operation of the appliance Bleed the oil duct and check thoroughly if all the boiler tubes both internal and external are tight Control...

Страница 16: ...B en 16 EN FR NL ES IT DE PL RU INSTALLATION ELECTRICAL CONNECTION T2 S3 T1 N L1 B4 T2 S3 T1 N L1 B4 2 M N PE 230 V 50HZ L1 t 1 3 1 Room thermostat 2 System heating pump 3 Bridge to be removed before...

Страница 17: ...ircuit which is adapted to the boiler power size and the type of system General remark The circuit illustrations are basic principle diagrams only HEATING CONNECTION Typical connection high temperatur...

Страница 18: ...first put the DHW circuit under pressure before pressurizing the heating primary circuit Refer to the hot water preparation tank manual for more information Set up conditions External power supply is...

Страница 19: ...ctions detailed in the technical manual of your burner 2 Adjust CO2 according to the values provided in the basic adjustment table below and by setting the oil pressure as well as the air flap as desc...

Страница 20: ...nd user perform the periodic checks mentioned in the Safety section of this manual Control the tightness of the hydraulic circuit connections N1 N2 N3 eco A1005170 664Y7700 B en 20 EN FR NL ES IT DE P...

Страница 21: ...ter N1 N2 N3 eco A1005170 664Y7700 B EN FR NL ES IT DE PL RU en 21 MAINTENANCE CLEANING THE COMBUSTION CHAMBER Set up conditions Boiler shut down External power supply isolated Oil supply closed Front...

Страница 22: ...N1 N2 N3 eco A1005170 664Y7700 B en 22 EN FR NL ES IT DE PL RU SERVICE LOG Service date CO2 Flue gas T Efficiency Remarks Name Signature SERVICE LOG...

Страница 23: ...heat output at 30 of rated heat output P1 kW 9 04 10 80 16 10 at rated output and high temp regime P4 kW 24 65 30 3 43 42 Useful efficiency at 30 of rated heat output 1 98 47 97 93 97 66 at rated outp...

Страница 24: ...application Low Temperature Low Temperature Low Temperature declared load profile for water heating Seasonal space heating energy efficiency class B B B Water heating efficiency class rated heat outp...

Отзывы: