background image

17

USER GUIDE

codes

00

02

03-07

11

12

13-17

18

19

25

28

31

32

33

36

37

38

44

Error description

No flame detected

No ignition after 5 attempts

Internal error

Eprom error

Low water pressure or 24V fuse failure

Internal error

Primary temperature 1 > 110 °C

Primary temperature 2 > 110 °C

Primary temperature 1 gradient too high

No fan signal

Short circuit in temperature 1 sensor

Short circuit in temperature 2 sensor

Hot water temperature sensor

Temperature 1 sensor: circuit open

Temperature 2 sensor: circuit open

Hot water temperature sensor: circuit open

Internal error

Fault repair

- check wiring / - change electrode / - change MCBA

- check ignition electrode and its positioning

- if the problem persists after 2 resets, change the MCBA

- if the problem persists after 2 resets, change the MCBA

- top up the primary circuit 

(see Using The Boiler - Heating System Pressure)

.

- call engineer to check fuse

- if the problem persists after 2 resets, change the MCBA

- check that sensor NTC1 is propely housed in its pocket

- if so, change sensor NTC1

- check that sensor NTC2 is propely housed in its pocket

- if so, change sensor NTC2

- check that the shunt pump is operating, and if so vent the boiler

- if the fan is turning:

• check the PWM connection

• if the problem persists after 2 resets, change the fan

• if the problem persists after 2 resets, change the MCBA

- if the fan is not turning:

• check the 230 Volt power to the fan

- change sensor NTC1

- change sensor NTC2

- change sensor NTC3

- check the connection of sensor NTC1 to the terminal strip

- if the problem persists, change sensor NTC1

- check the connection of sensor NTC2 to the terminal strip

- if the problem persists, change sensor NTC2

- check the connection of sensor NTC3 to the terminal strip

- if the problem persists, change sensor NTC3

- if the problem persists after 2 resets, change the MCBA

Safety shutdown

If an operating error develops, the system locks and the display
flashes: the first digit shows the sequence the burner was in when
the error occurred, the last two digits show the error code 

(see table

below)

; the first digit and the next two flash alternately.

To reset the system:
• Press the “RESET” button on the MCBA display.
• If an error occurs again, call an approved heating engineer.

Table of error codes and corrective action

Содержание HM 71

Страница 1: ...er tube is coated with metal fibre NIT which in addition to its remarkable heat exchange capabilities gives greater durability The main components are a venturi and one model 71 or two model 101 gas v...

Страница 2: ...w m3 h 2 46 8 60 3 80 13 17 Gas G31 37 50 mbar I 3P Flow m3 h 0 82 2 86 0 94 4 50 Pressure drop combustion chamber mbar 0 6 1 4 Flue gas temperature net C 172 165 Mass flow rate of combustion products...

Страница 3: ...rn OFF the on off switch on the boiler control panel and isolate external electrical supply 2 Turn off the gas supply to the boiler 3 Remove the flue to gain access to the top of the boiler 4 Remove t...

Страница 4: ...our installer will have informed you of this value at the time of installation see Commissioning Section Filling the hot water and heating circuits If the pressure falls below 1 bar the boiler water p...

Страница 5: ...behind a flap on the front of the boiler see picture on page 16 Standby Mode Standby Mode is the normal operation display setting The first digit shows the boiler sequence This sequence relates to cu...

Страница 6: ...ck that sensor NTC2 is propely housed in its pocket if so change sensor NTC2 check that the shunt pump is operating and if so vent the boiler if the fan is turning check the PWM connection if the prob...

Страница 7: ...Efficiency Gas pressure SERVICE RECORD Date serviced CO2 min load CO2 max load Gas LPG Remarks Name and signature Flue gas T Efficiency Gas pressure Date serviced CO2 min load CO2 max load Gas LPG Re...

Страница 8: ...84 E MAIL sales triangletube com ARGENTINA TECNOPRACTICA ALFEREZ BOUCHARD 4857 1605 CARAPACHAY BUENOS AIRES TEL 54 11 47 65 33 35 FAX 54 11 47 65 43 07 E MAIL jchas tecnopractica com BRAZIL SIMETAL IN...

Отзывы: