BURNER FEATURES

71/101 Gas burner features

(*) propane

Gas category

Type

HM 71

HM 101

Input

Kw

22.0 - 69.9

25.0 - 107 / 22.0 - 110 (*)

Output

Kw

18.4 - 63.0

23.0 - 96.3 / 20.2 - 99.0 (*)

Combustion efficiency - natural gas

%

92.0

92.1

Natural gas CO

2

%

9.0

9.5

Gas G20 - 20 mbar - I 2E(S)B - I 2 Er - I 2H 

Flow

m

3

/h

2.12 - 7.40

2.64 - 11.32

Gas G25 - 20/25 mbar - I 2L - I 2ELL

Flow

m

3

/h

2.46 - 8.60

3.80 - 13.17

Gas G31 - 37/50 mbar - I 3P

Flow

m

3

/h

0.82 - 2.86

0.94 - 4.50

Pressure drop combustion chamber

mbar

0.6

1.4

Flue gas temperature (net)

°C

172

165

Mass flow rate of combustion products 

(grammes per second)

9.2 - 32.1

11.5 - 49.2

BE

FR

AT

DK

ES

UK

IT

PT

IE

SE

NL

LU

DE

I 2Er

X

I 2E(S)B

X

I 2H

X

X

X

X

X

X

X

X

I 3P

X

X

X

X

X

X

I 2L

X

I 2ELL

X

X

BG 2000-M/71

BG 2000-M/101

Burner tube

Air collector

Ignition electrode

Fan

Gas valve

Gas inlet

Burner tube

Air collector

Ignition electrode

Fan

Gas valve

Gas inlet

Gas collector

Содержание HM 71

Страница 1: ...er tube is coated with metal fibre NIT which in addition to its remarkable heat exchange capabilities gives greater durability The main components are a venturi and one model 71 or two model 101 gas v...

Страница 2: ...w m3 h 2 46 8 60 3 80 13 17 Gas G31 37 50 mbar I 3P Flow m3 h 0 82 2 86 0 94 4 50 Pressure drop combustion chamber mbar 0 6 1 4 Flue gas temperature net C 172 165 Mass flow rate of combustion products...

Страница 3: ...rn OFF the on off switch on the boiler control panel and isolate external electrical supply 2 Turn off the gas supply to the boiler 3 Remove the flue to gain access to the top of the boiler 4 Remove t...

Страница 4: ...our installer will have informed you of this value at the time of installation see Commissioning Section Filling the hot water and heating circuits If the pressure falls below 1 bar the boiler water p...

Страница 5: ...behind a flap on the front of the boiler see picture on page 16 Standby Mode Standby Mode is the normal operation display setting The first digit shows the boiler sequence This sequence relates to cu...

Страница 6: ...ck that sensor NTC2 is propely housed in its pocket if so change sensor NTC2 check that the shunt pump is operating and if so vent the boiler if the fan is turning check the PWM connection if the prob...

Страница 7: ...Efficiency Gas pressure SERVICE RECORD Date serviced CO2 min load CO2 max load Gas LPG Remarks Name and signature Flue gas T Efficiency Gas pressure Date serviced CO2 min load CO2 max load Gas LPG Re...

Страница 8: ...84 E MAIL sales triangletube com ARGENTINA TECNOPRACTICA ALFEREZ BOUCHARD 4857 1605 CARAPACHAY BUENOS AIRES TEL 54 11 47 65 33 35 FAX 54 11 47 65 43 07 E MAIL jchas tecnopractica com BRAZIL SIMETAL IN...

Отзывы: