SIGN
DESCRIPTION
A1
OUTSIDE TEMPERA
TURE SENSOR NTC4 (AF 120) for MCBA
A2
OUTSIDE TEMPERA
TURE SENSOR AF 200 for CONTROL UNIT
A3
CONTACT
SENSOR
NTC
6
to
be
mounted
on
the
outlet
of
the
mixed
heating
circuit
for
MCBA
(when
module
AM3-11
is installed)
A4
POCKET SENSOR KVT
Installed in the hot water tanks and in the balanced header. Co
nnected to the Control Unit.
A5
CONTACT
SENSOR
VF
202
to
be
mounted
on
the
outlet
of
the
mixed
heating
circuit
for
CONTROL
UNIT
(or
when
module ZMC-1 installed). Allows weather dependent regulation.
A6
SENSOR KLF 1000
A7
SENSOR SPF 1000
A8
CONTACT SENSOR RAM
B
AM 3-11 MODULE
Controls the second heating circuit - communicates directly wit
h the MCBA. Operates with room thermostat.
C
ZMC-1 MODULE
Controls
the
second
heating
circuit
- alarm
contact
- operates
only
in
cojunction
with
the
Room
Unit
RSC.
Needs
RMCI
installed directly in MCBA.
D
COMMUNICA
TION MODULE RMCI
Enables communications between the MCBA and the Room Unit RSC.
E
WEA
THER DEPENDENT REGULA
TOR CONTROL UNIT
Regulates
one
or
more
boiler
(cascade
of
max
8
boilers)
HeatMaster
TC
with
modulating
burners.
Allows
control
of
3
heating
circuits
(2
mixed,
1without
mixer)
and
hot
water
production.
Equipped
with
2
outputs
and
3
programmable
inputs, allowing solar system and solid fuel boiler regulation.
Installed in the wall mounting socket.
SIGN
DESCRIPTION
F
ROOM UNIT
Room
regulator,
controls
heating
and
hot
water
production,
installed
inside
of
the
building
on
the
wall.
Supplied
with
outside
temperature
sensor.
Allows
heating
curve
regulation,
room
and
hot
water
temperature.
Displays
all
tempera
-
tures. Connected to the terminals 10-11 of the boiler terminal
block.
G
ZONE UNIT
Shows
internal
temperature
and
allows
for
remote
control
of
1
heating
circuit.
Communicates
with
the
Control
Unit.
For
3
heating
circuits
- max
3
Zone
Units.
Allows
correction
of
the
heating
curve,
temperatures
and
shows
information
from installed sensors. Connected to the Control Unit terminals
24-25.
RFF
Operates
with
the
Control
Unit.
Can
be
mounted
on
every
heating
circuit.
Connected
to
Control
Unit
terminals
24-25.
H
ROOM THERMOSTA
T
Installed
inside
the
building
on
the
wall.
Controls
room
set
temperature.
Operates
with
MCBA.
Connected
to
the
boiler
terminals 1-2 instead of the bridge.
I
SOLAR CONTROLLER LAGO SD3
J
COLLECTOR 2 or 3 CIRCUITS DN 20 or 32
Installed
directly
under
the
boiler.
Allows
connection
of
2
heating
circuits.
Internal
regulation
of
the
by-pass
allows
it to become a balanced header.
K
HIGH TEMPERA
TURE KIT DN 20 or 32
Installed
to
the
collector
under
the
boiler.
Supplies
high
temperature
circuit
or
water
tank
primaries.
Includes:
1
circulation pump, 2 isolating valves, check valve, 2 thermomete
rs.
L
LOW TEMPERA
TURE KIT DN 20 or 32
Installed
to
the
collector
under
the
boiler.
Supplies
low
temperature
circuit
and
controls
its
temperature.
Includes:
1
circulation pump, 2 isolating valves, check valve, 2 thermomete
rs and the 3-way valve with the integrated by-pass.
M
SOLAR PUMP GROUP
N
DHW THERMOSTA
TIC MIXING VALVE
O
SOLAR PANEL
Hotel Orca Praia,
Portugal
2 HeatMaster TC, Solar
Collectors, solar tank
Forest Research
Institute
Sękocin Stary, Poland
1 HeatMaster 35 TC for
DHW only
Crieff Hydro,
UK
1 HeatMaster 35 TC
Villa House, Starowa
Góra, Poland
2 HeatMaster 35 TC,
SLME, Solar Collectors
for DHW and Heating
They chose ACV HeatMaster TC
Hotel Castle of Ordingen
Belgium
3x Heat Master 85 TC
DHW and Heating
Содержание HeatMaster 35 TC
Страница 1: ...HeatMaster TC TECHNICAL...
Страница 27: ...27 Electric diagram Solar pump DHW circulating pump...
Страница 31: ...31 Electric diagram Mixed HC pump close open...
Страница 33: ...33 Electric diagram Direct HC pump Mixed HC pump close open...
Страница 35: ...35 Electric diagram Direct HC pump Mixed HC pump 1 Mixed HC pump 2 open close open close...