CHOOSING A PREVENTION METHOD 

The fill and make-up water must be softened where necessary to within 

the recommended range. Additives can be added to keep the limestone 

in solution in the water. ACV recommends Fernox (www.fernox.com) 

and Sentinel (www.sentinel-solutions.net) additives.

Please note that these additives must be used in accordance with the 

instructions issued by the manufacturer of the water treatment product.

The water hardness must be checked regularly and the values entered 

in the service log.

OTHER PARAMETERS

In addition to the oxygen and the water hardness, other parameters of 

the water in the heating systems must be checked: 

Acidity

6.6 < pH < 8.5

Conductivity

< 400 μS/cm (at 25°C)

Chlorides

< 125 mg/l

Iron

< 0.5 mg/l

Copper

< 0.1 mg/l

These parameters must be measured and the water must be treated 

if these values are outside the range. ACV recommends Fernox (www.

fernox.com) and Sentinel (www.sentinel-solutions.net) additives.

Please note that these additives must be used in accordance with the 

instructions issued by the manufacturer of the water treatment product.

CLEANING THE SYSTEM

Before the system is filled, it must be cleaned in accordance with 

standard EN14868. Chemical cleaning agents can be used. ACV 

recommends Fernox (www.fernox.com) and Sentinel (www.sentinel-

solutions.net) additives.

Please note that these additives must be used in accordance with the 

instructions issued by the manufacturer of the water treatment product.

   If any of the recommendations cannot be followed, the 

boiler must be hydraulically separated from the system 

by a plate type heat exchanger.

GENERAL

The fill water contains elements likely to damage the exchanger of a 

boiler if the concentration is outside the appropriate range.

The risk increases with the size of the system because the quantity of 

water in the circuit increases depending on the installed capacity. To 

cover these risks in a cascade installation, ACV demands the installation 

of a plate type heat exchanger between the boilers and the heating 

circuit.

PREVENTION PRINCIPLES

OXYGEN

Depending on the volume of water in the heating circuit, a certain 

amount of oxygen is introduced when the installation is filled. During 

operation, a little oxygen is added if the water is topped up and/or 

through the walls of the hydraulic components without an oxygen 

barrier (PE pipes & connections).

Oxygen corrodes the steel and generates sludge. ACV HeatMaster heat 

exchangers are made of stainless steel and are therefore insensitive 

to corrosion. However, the sludge produced by the corrosion of the 

components in the system made of ordinary steel (radiators, etc.) will 

be deposited on the hot surfaces, including those inside the exchanger.

These deposits in the heat exchanger reduce the water flow rate and 

thermally insulate the exchange surfaces, which is likely to damage 

them.

ENSURING PROTECTION AGAINST OXYGEN

-  Mechanical process: a deaerator combined with a desludger installed 

according to the manufacturer’s instructions effectively reduces the 

effects of oxygen on the installation;

-  Chemical process: additives keep the oxygen in solution in the water. 

ACV recommends Fernox (www.fernox.com) and Sentinel (www.

sentinel-solutions.net) additives.

  Please note that these additives must be used according to the 

instructions issued by the manufacturer of the water treatment 

product.

WATER HARDNESS

Depending also on the volume of water in the system, the water 

hardness and the fill frequency, a certain amount of limestone gets 

into the circuit. The resulting fur is deposited on the hot surfaces, 

including those inside the heat exchanger, reducing the passage of 

water and thermally insulating the active surfaces of the exchanger. This 

phenomenon can damage the heat exchanger.

  In order to maintain the performance levels of your 

HeatMaster® in professional installations, we recommend 

softening the water if the hardness is above 20°fH.

Water hardness

°fH

°dH

mmolCa(HCO3)

2

/l

Very soft

0 - 7

0 - 3.9

0 - 0.7

Soft

7 - 15

3.9 - 8.4

0.7 - 1.5

Fairly hard

15 - 25

8.4 - 14

1.5 - 2.5

Hard

25 - 42

14 - 23.5

2.5 - 4.2

Very hard

> 42

> 23.5

> 4.2

WATER QUALITY

EN • 4

664Y5300 • A

E

N

FR

R

U

P

L

DE

IT

ES

N

L

Содержание HeatMaster 25 TC

Страница 1: ...Installation operating and servicing instructions HeatMaster 25 35 70 85 TC 664Y5300 A EN FR RU PL DE IT ES NL...

Страница 2: ...rcuit controlled by an ACV 22 room thermostat 15 Installation of a high temperature heating circuit controlled by an ACV 22 room thermostat 16 Installation of two heating circuits controlled by Room U...

Страница 3: ...anual Essential instruction for the correct operation of the installation Essential instruction for the safety of persons and the environment Electrocution hazard use a qualified technician Burn hazar...

Страница 4: ...pe heat exchanger between the boilers and the heating circuit PREVENTION PRINCIPLES OXYGEN Depending on the volume of water in the heating circuit a certain amount of oxygen is introduced when the ins...

Страница 5: ...thane foam insulation 16 Boiler charging pump 17 Primary circuit separating disc 18 Safety valve 3 bar 19 Drain down valve HeatMaster 70 85 TC 1 Concentric flue connection 100 150 mm that can be trans...

Страница 6: ...ur times the first digit is 4 and the last two digits indicate the current temperature setting for the central heating To change this temperature press the or keys until the temperature indicated by t...

Страница 7: ...3 7 Gas flow rate G25 m3 h 3 1 4 3 Gas flow rate G31 kg h 1 95 2 37 CO2 max power CO2 8 99 10 5 9 4 10 5 CO2 min power CO2 6 67 10 1 9 0 10 1 Hydraulic parameters Max operating temperature C 90 90 90...

Страница 8: ...low rate G20 m3 h 7 40 8 99 9 73 Gas flow rate G25 m3 h 8 60 10 46 11 32 Gas flow rate G31 kg h 5 43 6 61 CO2 max power CO2 9 1 10 9 9 3 10 9 CO2 min power CO2 8 6 9 0 8 6 9 0 Hydraulic parameters Max...

Страница 9: ...pply HeatMaster 70 85 TC only 23 Gas pressure switch HeatMaster 70 85 TC only The ionisation current is measured between the terminal 19 and the earth ELECTRICAL CONNECTION Br B B V W Y Gr B Br G R V...

Страница 10: ...5 240 HYDRAULIC CONNECTIONS HeatMaster 25 35 TC HeatMaster 70 85 TC Heating connection F 1 1 1 2 DHW connection M 1 1 Gas supply M 3 4 3 4 bar 2 1 O 3 4 A B C D E G H F O N L K J I M 1736 3 x 65 730 1...

Страница 11: ...subjected to similar wind conditions C43 x Connection by two ducts to a collective duct system serving more than one appliance this system of collective ducts features two ducts connected to a termina...

Страница 12: ...BG CH CY CZ DE DK EE ES FI FR GB GR HR HU IE IS IT LT LU LV MK MT NL NO PL PT RO SE SI SK TR Appliance categories I2H I2L I2E I2E S I2Er I2ELL I2HS I3B P I3P Gas type and pressure G20 20 mbar G25 25...

Страница 13: ...sion vessel 6 DHW temperature control valve 7 Hot water tap 5 6 7 1 2 3 4 bar 2 1 O 3 4 CONVERSION TO NATURAL GAS OR PROPANE As indicated on the data plate the boiler is factory preset to operate with...

Страница 14: ...carried out on the appliance Please ensure that all the caps are removed before filling the appliance There is a connection and valve for filling and or draining the appliance at the bottom of the un...

Страница 15: ...s 10800107 HM 70 85 TC High temperature kit DN 32 Includes a circulator two isolation valves the check valve and two thermometers Initial adjusted Description 00 Heating mode OFF 01 Heating mode ON Te...

Страница 16: ...servomotor 537D3040 Contact sensor 12k Measures the flow temperature of the circuit controlled 10800106 HM 70 85 TC Low temperature kit DN 32 Includes a circulator two isolation valves the check valv...

Страница 17: ...perature of the heating circuit Minimum temperature of the heating circuit 20 Circulator controlled by the room thermostat DHW priority active 21 Continuous circulator night reduction active DHW prior...

Страница 18: ...rface RMCIEBV3 Enables communication between the MCBA and the Room Unit RSC 10800104 HM 70 85 TC 2 circuit manifold DN 32 With built in wall mounts 10800045 X2 2 k VF202 contact sensor For outlet on c...

Страница 19: ...the DHW temperature ZMC 2 230 Volt A B VF 0 VE 0 VF202 1 2 3 4 5 6 7 8 9 10 11 12 13 2 1 BUS A BUS B BUS A BUS B BUS B BUS A BUS B BUS A ZMC 2 230 Volt A B VF 0 VE 0 VF202 L 1 L 2 3 N N PE VA N N N M...

Страница 20: ...and air gas supply parameters are factory preset and cannot be changed Check if the parameters are set to meet the user s requirements The boiler s settings can only be checked by a trained ACV insta...

Страница 21: ...ay also be necessary to pour water into the cylinder in order to clean out any foreign bodies located in the flue ducts After doing this it is essential that the condensate trap is cleaned Check the b...

Страница 22: ...s between 9 and the temperature last two digits and b with the error code Once the cause of the blocking has been resolved the burner starts up automatically after a maximum of 150 seconds Status Boil...

Страница 23: ...ber of hours of DHW operation x 10000 STEP Outside temperature T4 in C STEP NA STEP Number of hours of DHW operation x 100 STEP Flue gas temperature T5 in C STEP Internal MCBA temperature STEP Number...

Страница 24: ...dicate that the code has been accepted STORE Press the MODE key until the desired mode appears MCBA parameters for the specialist SETTING THE PARAMETERS only accessible using the code Factory setting...

Страница 25: ...peed in central heating mode rpm Natural gas Propane Max fan speed in domestic hot water mode rpm x 100 Natural gas Propane Max fan speed in DHW mode rpm Natural gas Propane Min fan speed rpm x 100 Na...

Страница 26: ...y active 50 Controlled circuit outdoor sensor and AM3 11 module circulator controlled by the room thermostat DHW priority inactive DHW production type This parameter cannot be modified in any way on a...

Страница 27: ...the most recent error as well as the status of the boiler and the values at the time of this error MODE Display STEP Display Description of the parameters Error code at last lockout Boiler status at t...

Страница 28: ...lt fuse of the MCBA 3 Link 12 13 missing Internal error If the problem persists after two RESET attempts replace the MCBA Water in the 24 Volt circuit Check the 24 Volt circuit and dry if necessary se...

Страница 29: ...me the MCBA Internal error If the problem persists after two RESET attempts replace the MCBA Flue gas temperature too high NTC5 1 Check the connection of the NTC5 sensor 2 Check the wiring of the NTC5...

Страница 30: ......

Страница 31: ......

Страница 32: ......

Отзывы: