Plate Heat Exchanger Kits

1 INTRODUCTION

This technical data contains information for dimensioning & assembly of a 

cascade system kit for the Evo S. 

GENERAL DESCRIPTION OF FRAME & HEADER KITS

A requirement to spread the total required heat output over several boilers can 

be accommodated by the use of the Evo S multiple boiler frame & header kit 

options. 

The flue configurations for the range of appliances using these system kits are 

C13, C33 & B23 (See appliance manual).

 

Note

. In the case of the 150         kW 

boiler, this must be flued in accordance to the Clean Air Act. 

All headers and pipe work should be insulated in accordance with  the Non 

Domestic Building Services Compliance Guide. To ensure compliance with the 

maximum heat loss criteria, insulation thickness should be calculated according 

to BS EN ISO 12241 using standardised assumptions.

2.1  FRAME AND HEADER KIT DESIGN OPTIONS

Note: 

All boilers need to be sized in accordance to the total required 

heat load and the modulation capabilities of the appliances.

2  GENERAL DESCRIPTION OF CASCADE SYSTEMS

continued . . . . .

Max Boilers in Cascade @ stated 

Header Size

PHEX Options

Boiler Type

Boiler Header 

Size

No

Max Output 

(kW)

Evo S 40

DN50

4

160

60 kW, 150 kW, 300 kW

Evo S 60

DN50

4

240

Evo S 70

DN50

4

280

Evo S 80

DN80

6

480

150 kW, 300 kW, 450 kW, 600 kW

Evo S 100

DN80

6

600

Evo S 120

DN80

5

600

Evo S 150

DN100

6

900

300 kW, 450 kW, 600 kW, 750 kW, 900 kW

Note:

 The total system output must not exceed the Plate Heat 

Exchanger Kit Rating. 
One Plate Heat Exchanger Kit required per cascade. 

Table 1 - Cascade Options

Table 2 - Available Boilers

kW

Product No.

Evo S 40

100008264200

Evo S 60

100008264300

Evo S 70

100008265900

Evo S 80

100008264400

Evo S 100

100008264500

Evo S 120

100008264600

Evo S 150

100008264700

PHE Kits (kW)

Outlet Connection Size

60

DN25 FLANGE

150
300

DN50 FLANGE

450
600
750

DN80 FLANGE

900

Table 3 - PHEX Kit Outlet Connection Size

Содержание EVO S 100

Страница 1: ...onform to the safety and performance specification that we require Do not use reconditioned or copy parts that have not been clearly authorised by ACV For the very latest copy of literature for specif...

Страница 2: ...sory 9 5 Installation Drawings for Multiple Boiler Systems 10 Boiler Water Header Size Maximum No Boilers in Cascade Maximum Output in Cascade kW Evo S 40 DN50 4 160 Evo S 60 DN50 4 240 Evo S 70 DN50...

Страница 3: ...RAME AND HEADER KIT DESIGN OPTIONS Note All boilers need to be sized in accordance to the total required heat load and the modulation capabilities of the appliances 2 GENERAL DESCRIPTION OF CASCADE SY...

Страница 4: ...ed by the appliance must be maintained at all times The optional LPB bus accessory control can be installed 1 per boiler to enable cascade control 2 5 GAS SUPPLY All Evo S boilers are compatible with...

Страница 5: ...ately 3 2 MAIN WATER HEADERS Each header kit provides water flow and return headers sized either DN50 DN80 or DN100 dependent on total maximum combined heating output required 3 3 GAS HEADER The Gas h...

Страница 6: ...o DATE ALLDIMENSIONS IN MM DO NOTSCALE IF IN DOUBT ASK DRAWING VOID IFAMENDED MANUALLY MATERIAL DRAWN BY CHECKED BY ECN No FINISH DATE SCALE NTS FIRST ANGLE PROJECTION THIS DOCUMENTIS COPYRIGHTPROTECT...

Страница 7: ...nents or wiring Pressure gauge Not supplied A pressure gauge must be fitted to the system visible from the filling point Expansion vessel Not supplied 1 A diaphragm type expansion vessel complying wit...

Страница 8: ...to the frame before the hoses are connected to the boiler MOUNTING FRAME MUST BE SECURED TO THE FLOOR WITH BOLTS These Installations refer to perpendicular wall and floor If walls are not perpendicul...

Страница 9: ...Plate Heat Exchanger can be located either LHS or RHS of the headers REV BY ECN No DATE ALLDIMENSIONS DO NOTSCALE IF IN DO DRAWING VOID IFAMENDE MATERIAL DRAWN BY CHECKED BY ECN No FINISH DATE SCALE...

Страница 10: ...r Kits 5 INSTALLATION DRAWINGS FOR MULTIPLE BOILER SYSTEMS 5 1 GENERAL Note The total system output must not exceed the Plate Heat Exchanger Kit Rating refer to Table 1 for the range of Plate Heat Exc...

Страница 11: ...ATE HEAT EXCHANGER AND GAS CONNECTIONS CAN BE ON EITHER THE LHS OR RHS OF THE ASSEMBLY TO SUIT THE INSTALLATION 2 FRAME UIN 232857 ONE SUPPLIED PER BOILER 3 OPTIONAL 60kW PLATE HEAT EXCHANGER UIN 2328...

Страница 12: ...GER AND GAS CONNECTIONS CAN BE ON EITHER THE LHS OR RHS OF THE ASSEMBLY TO SUIT THE INSTALLATION 2 FRAME UIN 232857 ONE SUPPLIED PER BOILER 3 OPTIONAL 300kW PLATE HEAT EXCHANGER UIN 232891 ONE PER CAS...

Страница 13: ...LY TO SUIT THE INSTALLATION 2 OPTIONAL 300 kW PLATE HEAT EXCHANGER XB150037 ONE PER CASCADE 3 ALL DIMENSIONS IN mm 4 COMPATIBLE BOILERS 40 kW 60 kW 70 kW 704 TOP OF BOILER 1506 TOP OF FRAME 1535 554 6...

Страница 14: ...5 TOP OF BOILER 1506 894 300 554 643 680 120 639 SYSTEM RETURN DN50 PN6 FLANGE SYSTEM FLOW DN50 PN6 FLANGE 120 450 480 480 20 20 500 250 1500 NOTES 1 PLATE HEAT EXCHANGER AND GAS CONNECTIONS CAN BE EI...

Страница 15: ...20 639 2000 2678 480 480 480 480 20 20 20 500 500 500 250 123 NOTES 1 PLATE HEAT EXCHANGER AND GAS CONNECTIONS CAN BE ON EITHER THE LHS OR RHS OF THE ASSEMBLY TO SUIT THE INSTALLATION 2 FRAME UIN 2328...

Страница 16: ...894 554 643 680 120 300 450 TOP OF BOILER 1506 TOP OF FRAME 1535 500 500 500 500 250 123 480 20 480 20 480 20 480 20 480 2500 3178 120 639 SYSTEM FLOW DN50 PN6 FLANGE SYSTEM RETURN DN50 PN6 FLANGE NO...

Страница 17: ...ER 1506 TOP OF FRAME 1535 2500 3246 NOTES 1 PLATE HEAT EXCHANGER AND GAS CONNECTIONS CAN BE ON EITHER THE LHS OR RHS OF THE ASSEMBLY TO SUIT THE INSTALLATION 2 FRAME UIN 232858 ONE SUPPLIED PER BOILER...

Страница 18: ...1801 TOP OF FRAME 1830 704 894 1500 2190 120 639 500 500 250 123 480 480 480 20 20 NOTES 1 PLATE HEAT EXCHANGER AND GAS CONNECTIONS CAN BE ON EITHER THE LHS OR RHS OF THE ASSEMBLY TO SUIT THE INSTALL...

Страница 19: ...F THE ASSEMBLY TO SUIT THE INSTALLATION 2 FRAME UIN 235596 ONE SUPPLIED PER BOILER 3 OPTIONAL 600kW PLATE HEAT EXCHANGER UIN 232902 ONE PER CASCADE 4 ALL DIMENSIONS IN mm 5 COMPATIBLE BOILERS 150kW SY...

Страница 20: ...IONS CAN BE ON EITHER THE LHS OR RHS OF THE ASSEMBLY TO SUIT THE INSTALLATION 2 FRAME UIN 235596 ONE SUPPLIED PER BOILER 3 OPTIONAL 900kW PLATE HEAT EXCHANGER UIN 232904 ONE PER CASCADE 4 ALL DIMENSIO...

Страница 21: ...21 Plate Heat Exchanger Kits NOTES...

Страница 22: ...22 Plate Heat Exchanger Kits NOTES...

Страница 23: ...23 Plate Heat Exchanger Kits NOTES...

Страница 24: ...continuing improvement in the design and performance of its products The right is therefore reserved to vary specification without notice ACV U K Limited St David s Business Park Dalgety Bay Fife Sco...

Отзывы: