1
4
7
10
5
8
9
2
3
6
High efficiency oil & gas boilers
41
Technical Data
High efficiency oil & gas boilers
40
Easy Maintenance
Easy access to the combustion chamber
means that cleaning of the boiler and
flueways is straightforward.
1.
Ceramic fibre insulation
moulded in one piece overlaid
on mineral wool mattress
2.
Combustion chamber
3.
Glass wool insulation
4.
Combustion chamber door
5.
Control panel
6.
Flue tubes with bimetallic
spiral turbulators
7.
Primary water flow connection
8.
Primary water return
connection
9.
Safety valve connection
10. Open vent connection
Compact A
Compact A 100
Compact A 150
Compact A 200
*
Fuel
Oil (35 sec) or Natural gas/LPG
Burner options
Pressure Jet oil - forced draught nat gas/LPG
Maximum input
kW
109
161
260
Minimum input
kW
82
134
137
Maximum output
kW
100
140
235
Minimum output
kW
74
115
185
Mass rate of combustion products - gas
kg/h
189
254
451
Mass rate of combustion products - oil
kg/h
199
288
466
Total capacity
L
102
122
150
Primary connections (flange)
Ø
DN50
DN50
DN65
Safety valve connection (female BSP)
Ø
1
1/
4
"
1
1/
4
"
1
1/
4
"
Open vent connection (female BSP)
Ø
1
1/
4
"
1
1/
4
"
1
1/
4
"
Primary pressure drop
mbar
2 - 5
5 - 11
11 - 31
Flue circuit pressure drop
mbar
0.22 - 0.48
0.68 - 0.96
1.83 - 2.5
Flue connection
mm
200
200
200
Weight empty (excluding burner)
kg
315
380
470
Weight Full (excluding burner)
kg
417
502
620
Natural gas flow rates
m
3
/h
11.4
15.9
26.7
Oil flow rate
Ltrs/hr
9.08
13.35
15.58
Maximum operating temperature
°C
90
90
90
*Larger sizes available upon request.
Maximum operating pressure Primary: 5 bar
Dimensions
(excluding burner)
Compact A 100
Compact A 150
Compact A 200
Length
mm
1295
1495
1795
Height
mm
1000
1000
1000
Width
mm
796
796
796
High efficiency steel boiler with
pressurised combustion
chamber – match with natural
gas, LPG or oil burner.
Product Features
• Floor standing reverse flame heating boiler
• Robust and reliable steel construction
• Choice of pressure jet oil or forced draught gas burners available
• 3 models of 74, 115 and 235 kW output (larger sizes on request)
• 125mm glass wool insulation
• Combustion chamber door equipped with facility for left or right
hand opening
• Control panel including thermostats, thermometer, indicators,
power socket and on/off switch
• Delivered to site as a bare shell
- Allows easy off-loading and positioning
- Insulation and casing are packed
separately, for assembly after installation
to avoid damage
Characteristics
Control Panel
The control panel includes:
- On/Off switch
- Thermometer
- High/Low thermostats
- High/Low indicator lamps
- High limit thermostat
- Door open warning lamp