31
11. Startup Procedures
11.9 Setting the Appliance Parameters
Press the “
” button at the display panel for approximately 2
1.
to 3 seconds until main display begins to flash.
Press the “
” button repeatedly to scroll through the list of
2.
parameters. The operating display will show the parameter
number and the main display will show the parameter setting.
To modify a parameter, press the “ ” or “ ” buttons.
3.
Press the “
” button to advance to the next parameter to be
4.
changed.
After all parameters have been changed, press the
reset
5.
button to close the parameter menu and store the changes. The
main display will go blank and a P will be displayed in the
operating display to indicate the parameter changes have been
stored.
If the
reset button is not pressed within 30 sec-
onds, the parameter menu is automatically closed and
the changes are stored.
If the
ON/OFF button is pressed prior to the
reset button, the parameter menu is closed and the
changes are NOT stored.
NOTICE
Adjustments
Description
Parameters
(Flashing)
Factory Settings
LED
(Flashing)
Installation type
0
186ºF [86ºC]
140ºF [60ºC]
0=Combi (Heat and DHW)
2=DHW only
3=Heating only
CH pump continuous
0
0=Intermittent, pump on during heat and post purge
1=Pump continously, active except during DHW call or
if outside temperature is above parameter 7 with the
outdoor sensor installed - Warm Weather Shut Down.
1=H SMART/COMFORT I.F.W.H.
CH Minimum Boiler Temperature
86ºF [30ºC]
Adjustment range 60°F to 140°F
[16ºC to 60ºC]
CH Reset Curve Coldest Day
0ºF [-18ºC]
Adjustment range -22°F to 50°F
[-30ºC to 10ºC]
CH Reset Curve Warmest Day
64 ºF [18ºC]
Adjustment range 60°F to 78°F
[16ºC to 26ºC]
CH post pump
1
Adjustment range 0 to 15 minutes
Not applicable
0
Adjustment range 0 to 15 minutes
CH Anti cycle time
The CH anti cycle time starts when the burner shuts down during a CH call due to boiler water reaching the boiler set point temperature plus a
6ºF [3ºC] differential. The CH circulator will continue to operate while the burner is blocked.
0
Minimum off time during CH operation
Adjustable from 0 to 15 minutes
1
2
5
6
7
8
o
P
Main Display
Operating
Display
CH Maximum Boiler Temperature
Not applicable
Adjustment range 86ºF to 194ºF [30ºC to 90ºC]
Adjustment range 104ºF to 149ºF [40ºC to 65ºC]
1
1
For installations with an optional ACV- Triangle Tube SMART/COMFORT Indirect Fired Water Heater (I.F.W.H.) piped off the CHALLENGER, similar
to Figures 7 and 8 on page 14, parameter 1 should be set to 1. The I.F.W.H. aquastat should be wired to CHALLENGER’s X4-5 and X4-6 terminals,
see Figure 12, page 19. The I.F.W.H. circulator should be wired using the CHALLENGER’s 120 V terminals 4 (line), 5 (neutral) and 6 (ground).
During a DHW call for heat on terminals X4-5 and X4-6, only the DHW circulator will operate and the boiler’s target supply water temperature will
change to 186°F [86°C].
2
The DHW post pump function only applies when parameter 1 is set to 1 Heating & SMART/COMFORT I.F.W.H. and only occurs if no CH
call for heat is present.
3
2
DHW post pump
1
Adjustment range 0 to 15 minutes
9
3
DHW Flow Device Selection
0 for all Solo Boilers
P.
0