11. Startup Procedures
11.8.3
High Fire Test Mode
Press both the “
” and “+” buttons simultaneously once until the
operating display shows “h” or twice until the operating display shows
“H” for high fire.
11.8.4
Low Fire Test Mode
Press both the “
” and “ ” buttons simultaneously until
operating display shows “L”.
11.8.5
Test Mode Operation
While in the test mode:
High temperature limit will function
1.
Appliance CH circulator will function
2.
The test mode will time out after approximately 10 minutes
3.
Press both the “+” and “-” buttons simultaneously to deactivate
high/low fire test mode.
11.8.6
Flame Current
While in high fire or low fire test modes, the flame current (µA) can be
checked at the control by pressing and holding the “
” DHW
button.
11.8.7
Control Software Version
To view the control software version cycle the incoming power to the
CHALLENGER off then on.
The
LED will be lit for CH (central heating call)
The
LED will be lit for DHW (domestic hot water call) with optional Triangle Tube SMART/COMFORT I.F.W.H.
“X” represents temperature or pressure readings. When temperature is displayed it will be followed by “ºF” or “ºC” in the main display
and the appropriate LED will be lit. When pressure is displayed it will be followed by a “P” in the main display. Pressure can only be
read when the operating display is blank or shows a “A”.
* If factory installed CH Low Water Cut Off (LWCO) is below 7 psig [0.5 bar] the main display will flash a soft lockout of LOP (burner
and CH primary pump is blocked) followed by the pressure reading. Once CH system pressure is increased above 7 psig [0.5 bar]
normal boiler operation will be restored. Check LWCO wiring if LOP flashes to 90 _P (PSI) or 6.0 _P (bar).
** If the outdoor sensor is not installed the main display will display ODS when the boiler is in standby without a CH or DHW call for
heat or any errors. The lack of the outdoor sensor will not prevent the unit from operating on a CH or DHW call for heat, but is
recommended to increase system efficiency
Function
Main Display
Operating Display
OFF
XXP
XXP
XXX
7
Press
No demand for heat
Control self-test
Fan pre purge or post purge cycle
Space Heating (CH) post pump cycle
XXX
XXX
6
A
1
Ignition sequence
XXX
2
Burner ON for space heating (CH)
XXX
LOP*
3
Burner ON for domestic hot water (DHW)
4
Burner ON for DHW pre-heating
Raise CH pressure above 7 psig [0.5 bar]
ODS**
Outdoor sensor not installed
POLE
Incoming line and neutral are reversed
Burner ON for freeze protection
8
9
Burner OFF due to reaching temperature
setpoint
button to turn appliance ON, LED light above
button will be lit when appliance is ON.
NOTICE
11.8.8
Control Display Table