Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Indoor Unit
Doc. No. 0525 - 068
Ver. 3 201104
Installation and Commissioning Guide
Variable Capacity Commercial
11.02. Wiring Configuration : Recommended
4
INDOOR UNIT
DATA CONTROL
CABLE
3
LM-RS
-2
(OPTIONAL)
AERSS
(OPTIONAL)
2a
NEO
WALL CONTROLLER
1
(OPTIONAL)
2b
NEO
WALL CONTROLLER
2
(OPTIONAL)
LC7-2
WALL CONTROLLER
3
(OPTIONAL)
2c
1
OUTDOOR UNIT
NOTES
• Diagram shown above is a general representation only. Refer to individual unit wiring diagram for complete wiring
connection details.
• Long runs beside Mains cables or TV antenna cables should be avoided where possible.
• Daisy connection is not allowed for NEO wall controller.
Item
Description
Maximum Cable Length
1 to 4
Outdoor PCB to Indoor PCB
100 m
4 to 2a, 4 to 2b
Indoor PCB to Wall Controller
90 m
4 to 2C
Indoor PCB to Wall Controller 3
100 m
4 to 3
Indoor PCB to Remote Sensor
100 m
Description
Cable Type
LC7-2 and NEO Field Control Wiring
Cat5E UTP (AWG 24) Data Cable
Indoor to Remote Sensor
Cat5E UTP (AWG 24) Data Cable
Indoor to Outdoor Data Cable
2 Core Shielded Twisted Pair 7/0.30 (0.5mm
2
) Shielded Data Cable