Installation & Commissioning Guide - ESP Platinum ID Split Ducted Units 

Doc. Part No. 0525-052  

Rev. 5  200928

Page 8 of  20

LIFTING THE UNIT

Always observe WH&S regulations for safe and secure lifting 

practices in order to prevent physical injury.  

Suggested lifting procedures are outlined in the next page as 

reference guide to safely lift and transport the unit, however, 

these does not over rule the industry WH&S practices.   

LOCATION

This unit is intended for indoor installation only. 

It is highly 

recommended that this indoor unit and accessories, 

particularly zone barrels, be mounted in the roof cavity.

Mount the unit in a stable and rigid support wherein the 

weight is properly distributed, such as roof joist and rafters. 

Take into consideration the minimum service access 

clearances  provided in the unit drawings. 

Locate the indoor unit away from the areas where noise is 

a critical factor. Use rubber mounting pad (not supplied) in 

order to minimize the transfer of noise and vibration into 

building structures. 

A hanging bracket assembly and rubber grommet (optional 

on other units) are also provided to secure the indoor unit 

into the roof rafters. This installation configuration is most 

suitable for installation that require the unit to be rigidly 

secured up from the roof joist.   

   

CONDENSATE and SAFETY TRAY DRAINAGE

An integrated safety drain tray is provided as a standard 

inclusion to your indoor unit in order to reduce the potential of 

condensate damage to the roof. Drain Kit (optional on some 

units) is provided for the condensate drain to be externally 

trapped from the indoor unit. Suggested condensate 

and safety tray drainage instructions are provided at the 

proceeding page for your reference. 

SUPPLY AIR and RETURN AIR DUCT

The indoor unit is supplied with duct flange as standard in 

order to facilitate the system’s duct connection into the unit. 

Supply and return air duct works must be adequately sized to 

meet the system’s air flow and static pressure requirements. 

Refer to the unit drawing for supply air and return air duct 

dimensions, specific to your requirement.

NOTE: Fit a flexible duct connection in between the unit 

and the duct system, where noise and vibration is a critical 

consideration.

RETURN AIR FILTER 

Air filters must be provided in the return air side of the unit 

in order to maintain the efficiency and prolong the operation 

of the unit. These are also paramount in order to  satisfy 

requirement for a clean and hygienic room condition. Air 

filters must be placed in an easily accessible location for 

service and maintenance.

NOTES:

    1. Air filters are not supplied with the unit as individual air 

        filtration requirements are varied.

    2. Ensure that filters are cleaned / replaced regularly.

SUPPLY AIR and RETURN AIR DUCT (OPTIONAL)

Supply Air plenums and Duct Plates (twin-spigot) are 

available in order to facilitate your duct system connection to 

the indoor unit. The supply air plenums come in 1-way, 2-way 

and 3-way options, which offer a wider solutions to your 

different air distribution requirements.

SPLIT FAN COIL SYSTEM (OPTIONAL ERQ4-19AS)

The Actron Air innovative 2-piece fan coil system provides 

a solution to your difficult and tight roof space installation 

requirement. This versatile system has a separate fan and 

coil sections. Each of the compact and lightweight section 

is simply installed in two separate locations and joined by 

flexible duct system. Air ducts are attached to each section  

of the split fan coil by both of the supply air plenum and the 

twin spigot duct plate.

FAN COIL w/ VERTICAL DISCHARGE (OPTIONAL)

An upright Fan Coil with vertical supply air discharge is 

also available wherein installation applications require the 

placement of the unit down in a closet, basement or garage. 

Please refer to the Technical Catalogue of your indoor unit 

for dimensions, installation details and specifications.

FIELD PIPE CONNECTIONS

Specifications and installation requirements for field 

pipe connections are contained in the Installation and 

Commissioning Guide of the outdoor unit that matches 

your indoor unit. Please refer to this guide and thoroughly 

understand the procedures for safe and correct indoor and 

outdoor connection. 

ELECTRICAL FIELD CONNECTION

The power supply and control communication data to the 

indoor unit are supplied via the outdoor unit. Please refer 

to the wiring diagram supplied with the outdoor unit for 

specifications. 

All electrical work must be performed by a licensed 

electrician and must conform with the wiring diagram and all 

relevant electrical authorities.   

INSTALLATION INSTRUCTIONS

The installation instructions provided below are intended as a guide only and does not supersede the relevant council, 

The installation instructions provided below are intended as a guide only and does not supersede the relevant council, 

state and federal codes, regulations and building code standards. Compliance and consultation with the authorities 

state and federal codes, regulations and building code standards. Compliance and consultation with the authorities 

having jurisdiction with the installation of this equipment is the responsibility of the installer. Actron Air will not be held 

having jurisdiction with the installation of this equipment is the responsibility of the installer. Actron Air will not be held 

liable for any damages or costs as a result of the installer’s failure to comply. Please refer to the matching outdoor unit 

liable for any damages or costs as a result of the installer’s failure to comply. Please refer to the matching outdoor unit 

Installation and Commissioning Guide for further information and details. 

Installation and Commissioning Guide for further information and details. 

Содержание ERQ2-14AS

Страница 1: ...en consent from Actron Air Please Read This Guide Congratulations on your purchase of an Actron Air air conditioning unit This unit has been designed and manufactured with the highest quality standard in mind Please read this guide thoroughly and keep it near the unit for future reference INDOOR UNITS ESP PLATINUM Single Fan Coil Split Fan Coil ERQ2 14AS FRQ4 19AS ERQ3 17AS ARV4 19AS ERQ4 19AS Spl...

Страница 2: ...re that unit installation complies with relevant council regulations and building code standards council regulations and building code standards 4 4 All electrical wiring must be in accordance with All electrical wiring must be in accordance with current electrical authority regulations and all wiring current electrical authority regulations and all wiring connections to be as per electrical diagr...

Страница 3: ...are subject to change without notice Copyright 2017 Actron Engineering Pty Ltd Page 3 of 20 COMPONENTS OVERVIEW INDOOR UNIT COMPONENTS OVERVIEW EC Motor Fans Coil 8Z VAQ Module Lid Control Panel Control Panel SRD175C SRD175E UMMARY SRD175C SRD175E L SCROLL RESSOR ED UNIT Unit Control Board EMC Filter ...

Страница 4: ...3 Minimum Service Access Areas and Spaces for Airflow Clearances are responsibilities of the installer ActronAir will not be held liable for any extra charges incurred due to lack of access and space for airflow THIRD ANGLE PROJECTION STACKING OF UNITS ONE IN FRONT OF THE OTHER DISTANCE BET C A SIDE BY SIDE DISTANCE BET B A DUCT WORK 800 mm HEIGHT CLEARANCE 340 DUCT WORK DUCT WORK 800 mm SERVICE C...

Страница 5: ...TURN AIR EC INDOOR FAN EC INDOOR FAN 11 1315 MTG C C DIST 11 TOP VIEW FRONT VIEW SIDE VIEW HEIGHT CLEARANCE 410 DUCT WORK DUCT WORK 800 mm SERVICE CLEARANCE 800 mm SERVICE CLEARANCE ELECTRICAL EC ID FAN EC ID FAN INDOOR COIL A B C D NOTES 1 Do not scale drawing All dimensions are in mm unless specified Refer to corresponding unit dimensional drawing for mounting hole details 2 Service Access Areas...

Страница 6: ...S ONE IN FRONT OF THE OTHER DISTANCE BET C A SIDE BY SIDE DISTANCE BET B A 800 mm DUCT WORK 800 mm SERVICE CLEARANCE TOP VIEW DUCT WORK TO FAN SECTION 0m Min 6m Max COIL SECTION DUCT WORK 800 mm SERVICE CLEARANCE HEIGHT CLEARANCE 410mm A B C D NOTES 1 Do not scale drawing All dimensions are in mm unless specified Refer to corresponding unit dimensional drawing for mounting hole details 2 Service A...

Страница 7: ...FRONT OF THE OTHER DISTANCE BET C A SIDE BY SIDE DISTANCE BET B A 800 mm DUCT WORK UNIT MODEL NUMBER UNIT WEIGHT kg FRQ4 19AS 46 A B C D NOTES 1 Do not scale drawing All dimensions are in mm unless specified Refer to corresponding unit dimensional drawing for mounting hole details 2 Service Access Areas and Spaces for Airflow Clearances given are suggested minimum based on the condition that the s...

Страница 8: ...AIR DUCT OPTIONAL Supply Air plenums and Duct Plates twin spigot are available in order to facilitate your duct system connection to the indoor unit The supply air plenums come in 1 way 2 way and 3 way options which offer a wider solutions to your different air distribution requirements SPLIT FAN COIL SYSTEM OPTIONAL ERQ4 19AS The Actron Air innovative 2 piece fan coil system provides a solution t...

Страница 9: ...prevent the unit from being damaged during lifting 4 Test lift the unit to determine exact unit balance and stability before hoisting it to the installation location A CRANE LIFTING METHOD NOTE Crane lifting method is recommended for high rise lifting Fig 1 Connect the loop ends of slings unto shackle Fig 2 WH S regulations must be observed and will take precedence during lifting process WARNING M...

Страница 10: ...URN AIR INDOOR COIL CONDENSATE DRAIN MUST BE RUN SEPERATLY FROM THE SAFETY TRAY DRAIN SAFETY TRAY DRAIN CONNECTION CONDENSATE DRAIN CONNECTION SUPPLY AIR INTERNAL CONDENSATE TRAY THE TOP OF THE P TRAP MUST BE 50MM BELOW THE TOP OF THE CONDENSATE DRAIN CONNECTION THE TOP OF THE P TRAP MUST BE 50MM BELOW THE TOP OF THE CONDENSATE DRAIN CONNECTION INSTALL A T PIECE AS AN AIR VENT FOR LONG DRAIN RUNS ...

Страница 11: ...TH M SERIES CONTROLS ONLY 24 VOLT 8 ZONE KIT 8Z 24V AMZ 24V ZONE CARD 20VA 240 TO 24 VOLT TRANSFORMER INSTALLATION INSTRUCTIONS MOUNTING SCREWS LENGTH OF ALL BARRELS MEASURE 290 mm DIMENSIONS ALL INTEGRATED ZONE BARRELS COME INDIVIDUALLY BOXED FOR SAFE TRANSPORT INCLUSIONS 8Z 24V 8 ZONE KIT 8Z 24V ZONE MODULE INSTALLATION INSTRUCTIONS Duct Duct Zone Barrel Damper Motor on Top of the Zone Barrel TY...

Страница 12: ...8 ZONE 7 ZONE 6 ZONE 5 ZONE 4 ZONE 3 ZONE 2 ZONE 1 TO ZONE 2 8 240V MAINS ZONE MOTOR ZONE CONTROL 1 REMOTE SENSOR 1 LOG RJ45 SOCKETS FOR ACTRON AIR CAT5E SPEC CABLES ONLY REFER TO QUE CONTROL SYSTEM INSTALLATION COMMISSIONING MANUAL FOR ALL AVAILABLE CONFIGURATIONS FIELD WIRING RF RF OPTIONAL WIRED CONNECTION POWER ONLY CUT OFF SCREEN WIRE TO OUTDOOR UNIT 8Z VAQ DATA CABLE GREEN CAT5E CABLE THIS I...

Страница 13: ...nd cable boots Yellow FIELD WIRING BY INSTALLER 2 CORE 7 0 30 0 5mm2 Twisted Pair Shielded Data Cable with Screen Foil clamped to a Metal P Clip OUTDOOR UNIT TO OUTDOOR PCB MODEL MEPS CERT I FI ED A U S TRALIAN M A D E A U STRALIAN OW N E D R 410A LIVE ELECTRICAL WITHIN ENCLOSURE ISOLATE ELECTRICAL SUPPLY BEFORE REMOVING PANELS AUTHORISED TECHNICIANS ONLY 1 DIAGRAM SHOWING SCREEN FOIL CLAMPING Met...

Страница 14: ...LY BOXED FOR SAFE TRANSPORT INCLUSIONS 8Z 24V 8 ZONE KIT 8Z 24V ZONE MODULE INSTALLATION INSTRUCTIONS MOUNTING SCREWS ITEM PART NUMBER 7 METER CABLE 4070 004 ZONE MOTOR ONLY TRANSFORMER ONLY ZM 24V 2045 046 20 METER CABLE 4070 007 2 WAY RJ45 JOINER 2045 121 3 WAY RJ45 JOINER 4070 008 ZONE OPTION 2 1 5V AAA 1 5V AAA 1 5V AAA 1 5V AAA TYPE 10 250 mm PART NUMBER ZB 10 250 INTEGRATED ZONE BARREL PART ...

Страница 15: ... Yrs 3 Yrs 4 Yrs 5 Yrs Casing Panels and Frames Visual check for damage rust and dust accumulation For highly corrosive environment wash panels quarterly with water and neutral detergent solution Wax panels Repair re paint where required Insulation Visual check for insulation conditions Repair replace insulation material Fan Visual check for run out of balance and dust attached Clean off dust as n...

Страница 16: ...Y QUANTITY 1 EC ID Fan 2520 333 1 1 2 EC ID Fan 2520 334 1 3 Indoor Coil Assembly 1040 156 1 4 Indoor Coil Assembly 1040 254 1 5 Indoor Coil Assembly 1040 177 1 6 Coil Piston 4540 088 1 7 Coil Piston 4540 098 1 8 Coil Piston 4540 128 1 9 ID Control Board AFS QUEIB1 1 2020 154 1 1 1 10 Zone Module 8Z VAQ 1 1 1 11 Filter Board 4080 013 1 1 1 12 Yellow Cat5e Cable 10m 4070 028 1 per controller 1 per ...

Страница 17: ...THIS PAGE WAS INTENTIONALLY LEFT BLANK ...

Страница 18: ...THIS PAGE WAS INTENTIONALLY LEFT BLANK ...

Страница 19: ...THIS PAGE WAS INTENTIONALLY LEFT BLANK ...

Страница 20: ...Ltd ABN 34 002 767 240 HEAD OFFICE SYDNEY AUSTRALIA Printed in Australia Part No 0525 052 Rev No 5 0 200928 1800 119 229 actronair com au Copyright 2017 Actron Engineering Pty Ltd Refrigerant Trading Authorisation No AU06394 ...

Отзывы: