ActronAir
is constantly seeking ways to improve the design of its products. Therefore, specifications are subject to change without notice.
Copyright © 2017 Actron Engineering Pty. Ltd.
Page 5 of 20
INDOOR UNIT DIMENSIONS / CLEARANCES
ERQ4-19AS
UNIT MODEL NUMBER
UNIT
WEIGHT
(kg)
ERQ4-19AS
76
MINIMUM SERVICE ACCESS CLEARANCES
STACKING OF UNITS
ONE IN FRONT OF THE OTHER
(DISTANCE BET.
C
&
A
)
SIDE BY SIDE
(DISTANCE BET.
B
&
A
)
DUCT WORK
800 mm
OVERALL NOMINAL DIMENSION (H x W x D)
= 435 x 1420 x 680
SUPPLY DUCT (H x W) = 300 x 715
RETURN DUCT = 360 x 1140
DRAIN CONNECTION = 20mm ID
SUPPLY
AIR
715
311
311
1420 O/A
1140
79
118
630
20
20
435
O/A
INDOOR COIL
1375
90
130
SUPPLY AIR
590
40
50
680 O/A
360
50
25
110
300
25
RETURN
AIR
EC
INDOOR
FAN
EC
INDOOR
FAN
11
1315
(MTG C-C DIST)
11
TOP VIEW
FRONT VIEW
SIDE VIEW
HEIGHT CLEARANCE = 410
DUCT WORK
DUCT WORK
800 mm
SERVICE
CLEARANCE
800 mm
SERVICE
CLEARANCE
(ELECTRICAL)
EC
ID FAN
EC
ID FAN
INDOOR COIL
A
B
C
D
NOTES :
1.
Do not scale drawing. All dimensions are in mm unless specified. Refer to
corresponding unit dimensional drawing for mounting hole details.
2.
Service Access Areas and Spaces for Airflow Clearances given are suggested
minimum based on the condition that the spaces around the units are free from any
obstructions and a walkway passage of 1000mm between the units or between the
unit and the outside perimeter is available.
3.
Minimum Service Access Areas and Spaces for Airflow Clearances are
responsibilities of the installer, ActronAir will not be held liable for any extra charges
incurred due to lack of access and space for airflow.
THIRD ANGLE