18.04. EVA170S / EFA170S
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
50
75
100
125
150
175
200
225
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM W
% PWM
W
770
66
288
70
333
74
371
79
422
84
474
88
512
93
561
98
610
775
67
294
71
335
75
374
80
428
85
476
89
518
94
571
99
618
800
71
315
75
358
80
404
85
457
89
502
93
550
99
610
825
74
340
79
383
84
436
88
482
93
535
97
584
850
78
364
83
413
88
463
92
513
97
568
875
82
390
87
445
92
494
96
549
MOTOR / BLOWER LIMIT
900
87
431
92
483
97
547
NOTES:
W
= Indoor Fan Power, Watts
PWM
= Pulse Width Modulation Setting, % PWM
Default PWM Setting = 90% PWM (Medium Speed)
AIRFLOW (l/s)
275
250
225
200
175
150
125
100
75
50
25
0
EXTERNAL
ST
ATIC PRESSURE (Pa)
700
725
750
775
800
825
850
875
900
0
25
50
75
100
125
150
175
200
225
250
275
700
725
750
775
800
825
850
875
900
APPLICATION RANGE
MOTOR / BLOWER LIMIT
99% PWM
95% PWM
90% PWM
85% PWM
80% PWM
70% PWM
65% PWM
60% PWM
75% PWM