![ActronAir Classic 2 CCA130S Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/actronair/classic-2-cca130s/classic-2-cca130s_installation-and-commissioning-manual_2844097028.webp)
Installation and Commissioning Guide - Classic 2 Split Ducted Outdoor Unit
Doc. No.0525-073 Ver. 8 210414
Installation and Commissioning Guide
Classic 2 Outdoor Units
28
Circuit Breaker Size and Cable Size Requirement
Model
Circuit Breaker Size
Cable Size
*
(mm2)
Amps
MAIN
O.D. to I.D.
CRA100S / EVA100S
25.0
4.0
1.0
CRA130S / EVA130S / EFA130S
CCA130S / EVA130S / EFA130S
32.0
6.0
1.0
CRA150S / EVA150S / EFA150S
CCA150S / EVA150S / EFA150S
32.0
6.0
1.0
CRA170S / EVA170S / EFA170S
CCA170S / EVA170S / EFA170S
40.0
10.0
1.0
CRA130T / EVA130S / EFA130S
16.0
2.5
1.0
CRA150T / EVA150S / EFA150S
20.0
2.5
1.0
CRA170T/ EVA170S / EFA170S
CCA170T / EVA170S / EFA170S
20.0
2.5
1.0
CRA200T / EVA200S /
EFA200S
CCA200T / EVA200S / EFA200S
20.0
2.5
1.0
CRA230T / EVA230S / EFA230S
CCA230T / EVA230S / EFA230S
25.0
4.0
1.0
*
Suggested Minimum Cable Size should be used as a guide only, refer to the latest edition of the
AS/NZS 3000 “Australian / New Zealand Wiring Rules” for more details.
14. Maximum Cable Lengths
14.01. Wall Controller Options
Maximum of three (3) wall controllers in below combinations is allowed on unit. See below table.
Combinations
Wall Controllers
WC 1
WC 2
WC 3
1st Option
NEO
2nd Option
NEO
NEO
3rd Option
NEO
NEO
LR7-1 / LC7-2
4th Option
NEO
LR7-1 / LC7-2
5th Option
NEO
LR7-1 / LC7-2
LR7-1 / LC7-2
6th Option
LR7-1 / LC7-2
7th Option
LR7-1 / LC7-2
LR7-1 / LC7-2
8th Option
LR7-1 / LC7-2
LR7-1 / LC7-2
LR7-1 / LC7-2
NOTES
• NEO - Available in White (NTW-1000) and Black (NTB-1000) colours.
• LR7-1 and LC7-2 - Available in White and Grey colours.
• In the instance of a combination of NEO and LR7-1 / LC7-2 being connected together, the NEO will always need to be
addressed as C1.