4.

 Unpacking and Acceptance 

 

Make sure the package is upright as shown in Figure 4.1 before you open the package, 

Figure 4.1 packaging 

 

 

 

 

 

 

 

 

 

 

Please check that the packing straps are unbroken and that the wooden box is undamaged, not deformed or 

wet. 

 

Use scissors or a knife to dismantle the packing belt, then open the wooden box. 

 

After opening the package, please check the contents against the packing list. 

 

5.

 Installation 

5.1 Physical Installation   

Please follow the below diagram, figure, and instructions for installation: 

Figure 5.1 Installation diagram 

 

 

Содержание ACT-VCC-2000

Страница 1: ...ACT VCC 2000 AC Cabinet Air Conditioner User Manual Read this manual carefully before installation and use...

Страница 2: ...s 4 2 3 Working Principles 4 2 4 Product features 4 2 5 Technical Specifications 5 2 6 Air Circulation and Remote Mounting 5 2 7 Operation of the Unit 6 2 8 Condensate Handling 6 2 9 LED Display Param...

Страница 3: ...e cooling device intended for applications where the internal air of a sealed electrical enclosure must be cooled or maintained at a particular temperature This manual will provide an overview of the...

Страница 4: ...ressure vapor travels through a condenser where it dissipates heat to the environment The high pressure condensate then flows through an expansion valve which reduces the fluid s pressure and partiall...

Страница 5: ...de as short as possible to minimize the impact on the performance of the unit Any additional pressure drop incurred by the fans will reduce the performance of the unit Be prepared to oversize the cool...

Страница 6: ...its lowest speed o Active Cooling mode If the air temperature is greater than the setpoint temperature the unit will run on normal cooling mode to achieve the setpoint temperature o Heating mode Optio...

Страница 7: ...12 hours 0 72 hours P97 Return to factory setting Pressing the S key will return the product to default factory settings Heating functions are optional and not included on all units The above paramet...

Страница 8: ...10 AC Power undervoltage warning E11 Refrigerant circuit pressure is too high warning E12 Refrigerant circuit pressure is too low warning E13 Heater current overload warning E14 Heater current too low...

Страница 9: ...ing straps are unbroken and that the wooden box is undamaged not deformed or wet Use scissors or a knife to dismantle the packing belt then open the wooden box After opening the package please check t...

Страница 10: ...ed gasket Do not turn the unit on immediately after finishing the installation the unit must remain standing vertically for more than 30 minutes before being turned on to allow the compressor oil to d...

Страница 11: ...perly torqued to the relevant terminals All national wiring regulations and local electrical codes should be followed based upon instalation location Optional Heater 1000W Power supply 220 240 V Safet...

Страница 12: ...e IN Lighting Arrester CTRL NO COM NC T R T R INT Temp Sensor Cond Temp Sensor Inter Fan Exter Fan R S C Compressor 2 5 F 4 F 8 F J7 J8 J6 J32 J28 Evap Temp Sensor L Line J31 J30 J9 J27 RS48 5 JC J4 J...

Страница 13: ...wer supply voltage is normal and consistent with the requirements on the nameplate 6 2 Operating the Unit Apply power to the unit The product will first run a self test program and then the unit will...

Страница 14: ...arameter setting mode The display will show the Pxx code Use arrow keys to choose the desired item Press the S button to select The display will show the selected item s current parameter values use a...

Страница 15: ...ability Use the multimeter to measure the Air Conditioner input voltage in order to gauge whether the voltage is within normal range If the voltage is not within the normal range please turn off the p...

Страница 16: ...The compressor current is not within the normal range Turn off the power supply immediately Use a multimeter to measure the voltage do not power on the switch until the power supply is within the nor...