7.

 Maintenance and Warranty 

7.1 Product maintenance 

7.1.1 Tools needed 

Table 7.1 Maintenance tools 

Number 

Tools 

Multimeter 

Phillips screwdriver 

 

Slotted screwdriver 

 

7.1.2 Spare parts list 

Table 7.2 Spare parts list 

No. 

Spare part PN 

Spare part name 

Spare part model 

Quantity 

31.051 

Internal Fan 

190 AC FAN 

31.052 

External Fan 

225 AC FAN 

41.019 

Main Control Board 

JYJL V20 

7.1.3 Routine Maintenance 

Table 7.3 Routine maintenance 

 

NUM. 

Check items 

Check methods 

Solution 

Power line 
attachment 
 

1.  Turn off the supply power 
2.  Tug on the power line with moderate force and check 

whether the line is loosening from its terminals 

3.  Tighten the 

screws on the power cord terminals 

with a screwdriver,

 watch whether the screw is 

tightening or stripped 

If a power line is loose or loosening, 
retorque the attachment terminals or 
replace the cable if damaged.

 

Voltage 
Stability 
 

Use the multimeter to measure the Air Conditioner input 
voltage, in order to gauge whether the voltage is within 
normal range. 

If the voltage is not within the normal 
range, please turn off the power 
supply immediately. Do not power-on 
the Air Conditioner until the supply 
voltage within normal range. 

Attachment 
bolt torque 

Check the torque on all attachment bolts to ensure that 
the unit is still secured to the enclosure properly. 

Retorque any bolts as required. 

Cooling 

Power on the switch and check whether the self-test is 
correct. If it is correct, then the monitor will display 
compressor current as self-test program. 

While self-testing, if there is 
abnormal noise or vibration, please 
cut power off immediately and notify 
a professional to inspect. 
If alarm triggers while self-testing, 
please process as table7.3 

Fan Dust 
Accumulation 

Check for dust build-up around the fan blades on both the 
internal and external fans. 

If significant dust has accumnulated, 
use compressed air to blow dust off 
of fan blades until clean. 

 

7.1.4 Alarm code and Processing method 

Table 7.4 Alarm information 

Содержание ACT-VCC-2000

Страница 1: ...ACT VCC 2000 AC Cabinet Air Conditioner User Manual Read this manual carefully before installation and use...

Страница 2: ...s 4 2 3 Working Principles 4 2 4 Product features 4 2 5 Technical Specifications 5 2 6 Air Circulation and Remote Mounting 5 2 7 Operation of the Unit 6 2 8 Condensate Handling 6 2 9 LED Display Param...

Страница 3: ...e cooling device intended for applications where the internal air of a sealed electrical enclosure must be cooled or maintained at a particular temperature This manual will provide an overview of the...

Страница 4: ...ressure vapor travels through a condenser where it dissipates heat to the environment The high pressure condensate then flows through an expansion valve which reduces the fluid s pressure and partiall...

Страница 5: ...de as short as possible to minimize the impact on the performance of the unit Any additional pressure drop incurred by the fans will reduce the performance of the unit Be prepared to oversize the cool...

Страница 6: ...its lowest speed o Active Cooling mode If the air temperature is greater than the setpoint temperature the unit will run on normal cooling mode to achieve the setpoint temperature o Heating mode Optio...

Страница 7: ...12 hours 0 72 hours P97 Return to factory setting Pressing the S key will return the product to default factory settings Heating functions are optional and not included on all units The above paramet...

Страница 8: ...10 AC Power undervoltage warning E11 Refrigerant circuit pressure is too high warning E12 Refrigerant circuit pressure is too low warning E13 Heater current overload warning E14 Heater current too low...

Страница 9: ...ing straps are unbroken and that the wooden box is undamaged not deformed or wet Use scissors or a knife to dismantle the packing belt then open the wooden box After opening the package please check t...

Страница 10: ...ed gasket Do not turn the unit on immediately after finishing the installation the unit must remain standing vertically for more than 30 minutes before being turned on to allow the compressor oil to d...

Страница 11: ...perly torqued to the relevant terminals All national wiring regulations and local electrical codes should be followed based upon instalation location Optional Heater 1000W Power supply 220 240 V Safet...

Страница 12: ...e IN Lighting Arrester CTRL NO COM NC T R T R INT Temp Sensor Cond Temp Sensor Inter Fan Exter Fan R S C Compressor 2 5 F 4 F 8 F J7 J8 J6 J32 J28 Evap Temp Sensor L Line J31 J30 J9 J27 RS48 5 JC J4 J...

Страница 13: ...wer supply voltage is normal and consistent with the requirements on the nameplate 6 2 Operating the Unit Apply power to the unit The product will first run a self test program and then the unit will...

Страница 14: ...arameter setting mode The display will show the Pxx code Use arrow keys to choose the desired item Press the S button to select The display will show the selected item s current parameter values use a...

Страница 15: ...ability Use the multimeter to measure the Air Conditioner input voltage in order to gauge whether the voltage is within normal range If the voltage is not within the normal range please turn off the p...

Страница 16: ...The compressor current is not within the normal range Turn off the power supply immediately Use a multimeter to measure the voltage do not power on the switch until the power supply is within the nor...

Страница 17: ...ve inspection test acceptance and use Seller s warranty shall run to Buyer its successors assigns and customers and users of products sold by Buyer Seller agrees to replace or correct defects of any G...

Страница 18: ...Rev A ACT VCC 2000 AC 18 IDEAL APPLICATIONS Questions or Comments ACT Quality Department quality 1 act com or call 717 295 6061 to reach the Sales staff for assistance on custom orders...

Отзывы: