16
2.2 Installation Guideline (Refrigerant Piping)
Refrigerant piping length limitations
Pipe Parts
Pipe
Length
Total length
Actual length
A5VR030DRM
≤80m
L1+L2+...
+Li+a+b+…+i
A5VR040~A5VR080DRM
≤120m
Longest pipe length
Actual length
A5VR030DRM
≤50m
L1+L2+... +Li+i
A5VR040~A5VR080DRM
≤75m
Equivalent
length
A5VR030DRM
≤60m
A5VR040~A5VR080DRM
≤85m
Equivalent length from first bifurcation/refnet to furthest piping section
≤20m
L2+... +Li+i
Height
difference
Maximum height difference between indoor units and outdoor units
≤20m
-
Maximum height difference between the indoor units
≤15m
-
Bifurcation/Refnet
Height difference between
indoor units and outdoor units
Height difference between
the indoor units