11
Seal the bottom of foundation to prevent the exhausted air from crossing the unit,
Only install two units in the way.
2.2.4 Double-layer Installation
• An obstacle exists at the air exhaust side (see Figure 19)
Seal opening A to prevent the exhausted air from crossing the unit. The drainage construction space
required for the upper outdoor unit is about 100 mm. Water generated from the outdoor unit at the upper
layer cannot be directly drained to the outdoor unit at the lower layer. The overlaid units cannot exceed 2.
• An obstacle exists at the air intake side (see Figure 20)
Seal opening A to prevent the exhausted air from crossing the unit. The drainage pipe construction space
required for the upper outdoor unit is about 100 mm. The overlaid units cannot exceed 2.
Figure 17
Figure 18
Seal the bottom of foundation to prevent the exhausted air from crossing the unit.
b. Group units installation (more than two units)(see Figure 18)
The relation of H, A, L is as follows:
L
A
L ≤ H
0 < L ≤ 1/2H
250
1/2H < L ≤ H
300
H < L
The setting of foundation is L ≤ H