7
Electrical Data - R410A
MODEL
A5MAC210D A5MAC230D
FAN MOTOR
RATED RUNNING CURRENT H/L
A
2.5/1.7
MOTOR OUTPUT
W
900
POLES (H/L)
6/10
FAN SPEED
H/L
RPM
780/477
COMPRESSOR
RATED RUNNING CURRENT
A
19.22
20.8
LOCKED ROTOR AMP (LRA)
A
115
124
IP/INSULATION GRADE
UNIT OPERATING CURRENT
A
35.5
36.9
UNIT MAX RUNNING CURRENT
A
44.5
47
A5MAC340DR
A5MAC450D
3.96/2.64
1300
6
920 / 750
20.8
124
IPX4/F
54.3
76.1
78.1
103.2
NOTES:
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) MAX RUNNING CURRENT IS TESTED UNDER BELOW CONDITION: COOLING OUTDOOR DRY-BULB TEMPERATURE 43°C;
HEATING DRY-BULB TEMPERATURE 21°C, WET-BULB TEMPERATURE 15.5°C.
3) THE RATED RUNING CURRENT AND POLES ARE TESTED IN THE HIGH SPEED AND LOW SPEED.
Safety Devices
MODEL
A5MAC210D A5MAC210D A5MAC350DR
A5MAC450D
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE
PSW,H20PS
OPEN
MPa
4.15 ± 0.1
CLOSE
MPa
3.11 ± 0.1
LOW PRESSURE
SWITCH
TYPE
N/A
OPEN
MPa
N/A
CLOSE
MPa
N/A
PHASE SEQUENCER
YES
DISCHARGE TEMPERATURE
SETTING
°C/°F
130/266
NOTE: ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
Содержание A5MAC 210D
Страница 1: ...Technical Manual AIR COOLED MODULAR CHILLER A5MAC 210D A5MAC 230D A5MAC 340D A5MAC 450D...
Страница 14: ...14 Wiring Diagrams MODEL A5MAC210 230D...
Страница 15: ...16 1 4 5 3 2 7 8 6 1 4 5 3 2 7 8 6 A5MAC340DR...
Страница 16: ...17 1 4 5 3 2 7 8 6 1 4 5 3 2 7 8 6 A5MAC450D...
Страница 36: ...38 Wired Controller Instruction Dimensions Controller Installation...