42
Special precautions when dealing with refrigerant R407C unit
1) WHAT IS NEW REFRIGERANT R407C?
R407C is a zeotropic refrigerant mixture which has zero ozone depletion potential and thus conformed
to the Montreal Protocol regulation. It requires Polyol ester oil (POE) oil for its compressor's lubricant. Its
refrigerant capacity and performance are about the same as the refrigerant R22.
2) COMPONENTS
Mixture weight composition R32(23%), R125(25%), R134a(52%)
3) CHARACTERISTIC
•
R407C liquid and vapor components have different compositions when the fluid evaporates or
condenses. Hence, when leak occurs and only vapor leaks out, the composition of the refrigerant
mixture left in the system will change and subsequently affect the system performance. If just additional
refrigerant is added to leaked system, system performance will drop. It is recommended that the system
should be evacuated thoroughly before recharging with R407C.
•
When refrigerant R407C is used, the composition will differ depending on whether it is in gaseous or
liquid phase. Hence when charging R407C, ensure that only liquid is being withdrawn from the cylinder
or can. This is to make certain that only original composition of R407C is being charged into the system.
•
POE oil is used as lubricant for R407C compressor, which is different from the mineral oil used for R22
compressor. Extra precaution must be taken not to expose the R407C system too long to moist air.
4) CHECK LIST BEFORE INSTALLATION/SERVICING
•
Tubing
Refrigerant R407C is more easily affected by dust of moisture compared with R22, make sure to
temporarily cover the ends of the tubing prior to installation
•
Compressor oil
No additional charge of compressor oil is permitted.
•
Refrigerant
No other refrigerant other that R407C
•
Tools
Tools specifically for R407C only (must not be used for R22 or other refrigerant)
i)
Manifold gauge and charging hose
ii)
Gas leak detector
iii)
Refrigerant cylinder/charging cylinder
iv)
Vacuum pump c/w adapter
v)
Flare tools
vi)
Refrigerant recovery machine
5) HANDLING AND INSTALLATION GUIDELINES
Like R22 system, the handling and installation of R407C system are closely similar. All precautionary
measures; such as ensuring no moisture, no dirt or chips in the system, clean brazing using nitrogen, and
thorough leak check and vacuuming are equally important requirements. However, due to zeotropic nature of
R407C and its hydroscopic POE oil, additional precautions must be taken to ensure optimum and
trouble-free system operation.
a) Filter-dryer must be installed along the liquid line for all R407C air conditioners. This is to minimise the
contamination of moisture and dirt in the refrigerant system. Filter-dryer must be of molecular sieve
type. For a heat-pump system, install a two-way flow filter dryer along the liquid line.
b) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to
moist air. Residual POE oil in the piping and components can absorb moisture from the air.
8. SPECIAL PRECAUTIONS FOR R407C
Содержание A4LC 20B
Страница 15: ...14 OUTDOOR UNIT ALC 30 40 50C CR A4LC 30 40 50 C CR...
Страница 16: ...15 INDOOR UNIT COOLING ONLY MODEL ACK 20 25A C3A BOARD 7 WIRING DIAGRAMS OUTDOOR UNIT MODEL ALC A4LC 20 25B...
Страница 17: ...16 INDOOR UNIT COOLING ONLY MODEL ACK 30A C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 30C...
Страница 18: ...17 INDOOR UNIT COOLING ONLY MODEL ACK 40 50A C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 40 50C...
Страница 19: ...18 INDOOR UNIT HEAT PUMP MODEL ACK 20 25AR C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 20 25BR...
Страница 20: ...19 INDOOR UNIT HEAT PUMP MODEL ACK 30AR C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 30CR...
Страница 21: ...20 INDOOR UNIT HEAT PUMP MODEL ACK 40 50AR C3A BOARD OUTDOOR UNIT MODEL ALC A4LC 40 50CR...
Страница 22: ...21 INDOOR UNIT COOLING ONLY MODEL ACK 20 25A UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 20 25B...
Страница 23: ...22 INDOOR UNIT COOLING ONLY MODEL ACK 30A UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 30C...
Страница 24: ...23 INDOOR UNIT COOLING ONLY MODEL ACK 30A UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 30B...
Страница 25: ...24 INDOOR UNIT COOLING ONLY MODEL ACK 40 50A UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 40 50C...
Страница 26: ...25 INDOOR UNIT HEAT PUMP MODEL ACK 20 25AR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 20 25BR...
Страница 27: ...26 INDOOR UNIT HEAT PUMP MODEL ACK 30AR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 30CR...
Страница 28: ...27 INDOOR UNIT HEAT PUMP MODEL ACK 40 50AR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC A4LC 40 50CR...
Страница 29: ...28 INDOOR UNIT COOLING ONLY MODEL ACK 15B UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC15B...
Страница 30: ...29 INDOOR UNIT COOLING ONLY MODEL ACK 20 25B UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC20 25B...
Страница 31: ...30 INDOOR UNIT COOLING ONLY MODEL ACK 30B UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC30C...
Страница 32: ...31 INDOOR UNIT COOLING ONLY MODEL ACK 30B UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 30B...
Страница 33: ...32 INDOOR UNIT HEAT PUMP MODEL ACK 15BR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 15BR...
Страница 34: ...33 INDOOR UNIT HEAT PUMP MODEL ACK 20 25BR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 20 25BR...
Страница 35: ...34 INDOOR UNIT HEAT PUMP MODEL ACK 30BR UNIVERSAL BOARD OUTDOOR UNIT MODEL ALC 30CR...
Страница 38: ...37 MODEL ALC 20 25BR HEAT PUMP 3 PHASE 50HZ 380 415V MODEL ALC 30CR HEAT PUMP 3 PHASE 50HZ 380 415V...
Страница 41: ...40 LOW AMBIENT UNIT OPTIONAL OUTDOOR UNIT MODEL ALC 10B 15B 50HZ OUTDOOR UNIT MODEL ALC 20B 25B 50HZ...