WTR2-640
Chapter 4: Operation
22 of 46
Chapter 4:
Operation
4-1 Start-up
1. Push the PUMP START button to start the pump.
2. When the unit has built at least five (5) psi (34.5 kPa) of pressure, wait two (2)
minutes, then select a set point of 100°F (38ºC) and switch the unit into AUTO
mode. As the oil warms up, viscosity decreases and pressure falls.
3. Four to six inches (4” to 6” / 10 cm to 15 cm) of fluid should be visible in the
sight glass.
5.
Select a process set point on the controller.
4-2 Controller Description & Operation
The Microprocessor Controller
The controller is an easy-to-operate microprocessor-based PID control device. When
the process reaches the set point, the PID control cycles the cooling valve and/or
immersion heater to maintain the proper leaving water temperature.
The controller has been fully factory tested. Set the desired process temperature set
point and the control does the rest.
Built-in range of operation on the controller is 0°F to 550°F (-18°C to 288°C).
Controller Display
Figure 4: Microprocessor controller