WTR2-640
Chapter 3: Installation
19 of 46
Connecting Cooling Water Piping
You must provide cooling water at 25 psi to 75 psi (172.4 kPa to 517.1 kPa/1.7 bars to 5.2 bars)
for proper operation. Untreated water can foul or corrode the heat transfer surfaces, slowing
water flow and causing fluid temperature control problems. The manufacturer sells a complete
line of water treatment equipment that can reduce downtime and maintenance costs.
Run properly-sized cooling water lines—never smaller than the outlets on the Upright unit. If
external piping is larger than Upright unit connections, reduce the size of the piping at the unit.
Connecting Vent Piping
You must leave the vent connection open to the atmosphere at all times. The vent connection is
located on top of the reservoir. On systems with piping above the reservoir level, you must run
vent piping to a minimum height of one foot (1’ / 31 cm) above the highest point in the system.
Run the piping down into an auxiliary vented overflow chamber, such as a vented, covered 55-
gallon (208-liter) drum. This practice ensures that overflow will not create a hazard to
personnel.
All external piping must be supported independently of the Upright unit.
The reservoir tank must be vented to prevent pressurization. A pressurized
reservoir could rupture, allowing hot fluid to escape and become a potential fire
and slip hazard.
Heat transfer fluids expand when heated. Expansion rates vary, depending on
fluid types and temperatures. For more information on expansion rates, refer to
specification information for the heat transfer fluid you select.
Generally, most heat transfer fluids expand at the rate of 2.5% for every
increase of 50°F/°C from temperatures above 60°F (16°C).
Figure 1: Upright Unit Piping Setup