BusWorks Model XT1533-000

 

 

4 CH Current  4 CH Digital I/O w/USB & Profinet 

 

 

 

 

 

Acromag, Inc. Tel: 248-295-0880  

            - 34 -                                   

http://www.acromag.com  

- 34 - 

http://www.acromag.com 

 

Diagnostics Table…

 

POSSIBLE CAUSE 

POSSIBLE FIX 

Out

puts Appear Noisy or Unstable…

 

Have you grounded your I/O 
return?  One I/O Return 
terminal should include a 
connection to earth ground.  

Connect one I/O Return terminal to earth 
ground if the I/O is not otherwise earth 
grounded. 

Software Status: 

“Data Transfer Error”, “Unknown Protocol” or “Timeout Error”…

 

USB connection was opened 
before unit had completed its 
power-on initialization and 
established its network 
connection. 

Wait ~30 seconds after powering-up unit 
before opening a USB connection via the 
configuration software.  Turn power off to the 
unit, close the USB configuration software, 
repower the unit, then reboot the USB 
configuration software after the unit has 
completed power-on initialization and 
established its network connection. 

Digital Outputs Not Working…

 

Missing digital excitation 
connection to power which 
powers the output driver. 

You must connect an excitation supply from 6-
32V to operate the digital outputs (not 
required for digital input-only operation). 

Digital Inputs Appear to Register Incorrect State…

 

There is contention between a 
field input signal and the 
tandem open-source output 
which may be ON, or the 
Invert Input Logic function is 
enabled. 

If you are monitoring a field-wired digital input, 

you must turn the channel’s corresponding 

output OFF.  Check the state of the Invert Input 
Logic function.  Note that the output will turn 
OFF if contention with a field input signal 
occurs and you will have to cycle excitation 
OFF/ON to restore output operation. 

Digital 

I/O Channels Change States when you connect USB…

 

Indicative of a ground fault 
between earth ground at the 
PC and earth ground applied at 
an I/O channel, when you have 
not isolated your USB signals. 

Only connect to the unit via isolated USB if 
your I/O signal is already earth grounded.  You 
could connect without USB isolation if the I/O 
signal is not already grounded (not 
recommended). 

Writing a digital output causes adjacent channels to 

change their state…

 

Digital outputs are written four 
channels at a time. 

Because all four outputs are addressed at a 
time, it is necessary to retrieve or store all 
current output states before writing specific 
outputs in order to implement a masking 
stra

tegy and prevent adjacent channel’s from 

potentially changing their states (i.e. if an 
adjacent channel is currently ON or OFF, you 
need to reinforce the ON/OFF state in your 
output write to keep it ON/OFF). 

`

 

Содержание XT1533-000

Страница 1: ...igital I O 4 DC Current Outputs and 4 Digital Inputs w 4 Tandem High Side Switch Outputs USER S MANUAL ACROMAG INCORPORATED Tel 248 295 0880 30765 South Wixom Road Fax 248 624 9234 Wixom MI 48393 2417...

Страница 2: ...ction 8 Output Connections 10 Digital Input Connections 13 EMI Filter Installation 14 Earth Ground Connections 15 CONFIGURATION SOFTWARE 15 Quick Overview 16 CONFIGURATION STEP BY STEP 18 Getting Conn...

Страница 3: ...ive effects of power wiring component sensor or software failure in the design of any type of control or monitoring system This is very important where property loss or human life is involved It is im...

Страница 4: ...tion offers a convenient daisy chain network connection saving switch ports Operation Diagnostic LED indicators aide trouble shooting Bus Power Ready for Clean Wiring along the DIN Rail and or for Red...

Страница 5: ...e the top groove of the module over the upper lip of the DIN rail Firmly push the unit downward towards the rail until it snaps into place To remove it from the DIN rail first separate the input termi...

Страница 6: ...and can be removed from their sockets by prying outward from the top with a flat head screwdriver blade Strip back wire insulation 0 25 inch on each lead and insert the wire ends into the cage clamp c...

Страница 7: ...RESULT NOTE IT IS RECOMMENDED THAT SUPPLIES CAPABLE OF DELIVERING MORE THAN 2 5A TO THE UNIT BE FUSED WITH A HIGH SURGE TOLERANT FUSE TB6 OF TX6 20 19 18 17 ANY I O TB5 OF TX5 TB4 OF TX4 I O DC POWER...

Страница 8: ...then installed in the field which may be in a hazardous area Do not attempt to connect a PC or laptop to this unit while installed in a hazardous area as USB energy levels could ignite explosive gase...

Страница 9: ...urrent Output 4 CH Digital I O w USB Profinet Acromag Inc Tel 248 295 0880 9 http www acromag com 9 http www acromag com Connect Unit to Power Before USB This unit does not use USB power but requires...

Страница 10: ...e regulator will result Refer to the following figures to wire the current outputs digital outputs and excitation of these models PERSONAL COMPUTER RUNNING WINDOWS OS 1 METER CABLE USB A MALE TO HOST...

Страница 11: ...ent outputs require external analog excitation to operate Outputs do include digital and hardware current limiting There are two analog excitation inputs one for 12V 10 15V another for 24V 20 28V and...

Страница 12: ...he output driver is also powered from the excitation supply IMPORTANT Add Protection with Inductive Loads Outputs do include internal reverse bias shunt diodes to help protect the output switch from d...

Страница 13: ...rn via 10K pull down resistors installed on the board and will never float Observe proper polarity when making I O connections Refer to the following figures to wire the digital inputs of this model I...

Страница 14: ...s outputs and Power order Acromag 4001 135 Laird 28A0592 0A2 or similar for USB cable Acromag 4001 140 and Laird 28A0807592 0A2 or similar for Ethernet cable Acromag 4001 139 Locate ferrites by clampi...

Страница 15: ...of this module CONFIGURATION SOFTWARE While this is an Ethernet network I O module its I O can only be configured and calibrated via its Configuration Software over a USB connection to a Windows based...

Страница 16: ...up Device Select First Connect to the Unit Here Select from connected modules and Open or Close communication with them Display the Model Serial Number and Manufacturer of the connected module and rep...

Страница 17: ...ic for the tandem digital input channel useful for i2o operation Choose Legacy Support Yes if you want the output to scale 0 100 to 0 20000 versus 0 100 to 0 30000 Optional invert Input Logic of input...

Страница 18: ...ired 4 Connect Power You need to connect power from 12 32V to power this module Current required will vary with voltage level refer to Specifications Your supply must be capable of providing at least...

Страница 19: ...USB hub you can use the Device scroll field to select another unit using the serial information suffix of the Device Model number to discern one unit from another Once you have selected a device click...

Страница 20: ...efines one host from all other computers hosts on the Internet The IP address is made up of four octets 8 bits each octet having a value between 0 255 00H FFH It is expressed here in decimal form with...

Страница 21: ...fault the module is setup to use Static IP Addressing and a default Static IP Address of 192 168 1 100 You can optionally choose to have the IP address assigned dynamically via DHCP but this will addi...

Страница 22: ...tively then click Send Config to write the channel configuration to the unit or more simply make changes to many channels and then click Send Config one time to write all the channel configurations to...

Страница 23: ...gital outputs Analog Output Test There are 8 or 4 analog output fields that allow you to enter or read output values in volts XT154x or mA XT153x Read Analog Output Click this button to read the curre...

Страница 24: ...this button to Start Stop periodic polling of the digital input channels The channel states are indicated via 1 0 and LED color and updated about once per second Be sure to first stop polling before...

Страница 25: ...conds of slide or arrow inactivity Simply set the output to precisely 1mA using a meter to measure the output a live zero is used instead of 0mA to improve the accuracy of calibration click the zero b...

Страница 26: ...messages like No Error Transfer Error and Timeout Error after clicking OK during calibration If you encounter a Transfer or Timeout Error you may have to repeat the calibration process HELP You can pr...

Страница 27: ...t this address on the Device Communication Setup page of the USB Configuration Software for the unit the default is 192 168 1 100 This will access the home page of the unit similar to the first screen...

Страница 28: ...f a 32 bit microcontroller Each output source is pulled down to return via a 10K resistor and is fed back to the controller through a 100K series resistor which drives non inverting input buffers with...

Страница 29: ...plication layer protocol TCP IP especially selected for industrial automation applications In this way Profinet offers scalable performance with protocols providing three different data channels TCP I...

Страница 30: ...etwork a Profinet IO Controller must be programmed with a special Profinet Configuration tool such as Step7 from Siemens Profinet IO devices like this module are also configured using a Profinet confi...

Страница 31: ...me reason OUTPUT Consumed DO Channel 3 2 1 0 Unsigned 16 bit Bits 3 0 Bits 15 4 Not Used OUTPUT Consumed AO Channel 0 Unsigned 16 bit Normalized count from 0 30000 or 0 20000 w Legacy support represen...

Страница 32: ...is bad The RUN LED will continue to blink as the unit initially hunts for a network link Connect a network cable to the unit to allow it to complete its initialization and stop the blinking Note this...

Страница 33: ...hen select and re open the module for communication or simply exit the Configuration software and reboot it Cannot Communicate with Module via USB A missing USB Isolator could cause a ground loop betw...

Страница 34: ...ppear to Register Incorrect State There is contention between a field input signal and the tandem open source output which may be ON or the Invert Input Logic function is enabled If you are monitoring...

Страница 35: ...ally by connecting 24V to it by mistake Connecting 24V power to the 12V analog excitation terminals will destroy its TVS and switching regulator In this case connect 24V excitation 20 28V to the 24V t...

Страница 36: ...rface Package Configuration Kit Order XT SIP USB Signal Isolator USB A B Cable 4001 112 USB A mini B Cable 4001 113 Configuration Software CDROM 5041 094 This kit contains all the essential elements f...

Страница 37: ...onnections to Power Two end stops 1027 222 used to secure the terminal block and module for hazardous location installations Low EMI Double Shielded Patch Cable Ethernet Patch Cable 3 feet long Model...

Страница 38: ...sitive current is pulled from the analog excitation supply sourced from the output channel and pushed through the load to Return RTN The unit must be wired and configured for the intended output see C...

Страница 39: ...count or the normalized count For normalization to 30000 the effective resolution is dominated by the 16 bit raw DAC resolution at 1 part in 29533 But for normalization to 20000 the effective resolut...

Страница 40: ...wn to help protect the output channel from damage due to overload cycle excitation OFF ON to restore output operation after a shutdown Output Thermal Shutdown Individual outputs will shutdown and latc...

Страница 41: ...gnal it shuts OFF and you must cycle output excitation OFF ON to restore output operation Digital Inputs This model has four tandem digital input and output channels No additional excitation is requir...

Страница 42: ...001 of output span effect per volt DC change USB Interface Unit includes a USB socket for temporary connection to a PC or laptop for the purpose of channel setup reconfiguration and trouble shooting U...

Страница 43: ...e metal shield circuit of the network connectors is isolated and capacitively coupled to the input power minus terminal via an isolation capacitor Network to Network Isolation Network ports are additi...

Страница 44: ...double shielded Ethernet cable is also helpful in curbing emissions These limits represent the minimum requirements of the applicable standard but this product has typically been tested to comply with...

Страница 45: ...ed that is set at a level not exceeding 140 of the peak rated voltage value at the supply terminals to the equipment Reliability Prediction Reliability Prediction MTBF Mean Time Between Failure MTBF i...

Страница 46: ...l Reference section of this manual for detailed information on available software control of this model REVISION HISTORY The following table shows the revision history for this document Release Date V...

Отзывы: