SERIES IOS-440 I/O SERVER MODULE                                32-CHANNEL ISOLATED DIGITAL INPUT MODULE 
_________________________________________________________________________________________

 

- 3 - 

Acromag, Inc.  Tel:248-295-0310  Fax:248-624-9234  Email:[email protected]  http://www.acromag.com 

 

enclosure walls where it is dissipated by the external cooling 
fins.  

 

I/O SERVER MODULE  INTERFACE FEATURES 

 

High density -

 Four units mounted on the IOS carrier board 

provide up to 128 isolated input points in a single system 
slot.   

 

Local ID

 - Each IOS module has its own 8-bit ID PROM 

which is accessed via data transfers in the "ID Read" space. 

 

8-bit I/O

 - Port register Read/Write is performed through 8-

bit data transfer cycles. 

 

I/O SERVER MODULE SOFTWARE LIBRARY 

 

IOS MODULE Win32 DRIVER SOFTWARE 

 

Acromag provides a software product (sold separately) to 

facilitate the development of Windows Embedded Standard 
applications interfacing with I/O Server Modules installed on 
Acromag Industrial I/O Server systems.  This software (Model 
IOSSW-DEV-WIN) consists of a low-level driver and Windows 
32 Dynamic Link Libraries (DLLS) that are compatible with a 
number of programming environments including Visual C++, 
Visual Basic.NET, Borland C++ Builder and others.  The DLL 
functions provide a high-level interface to the IOS carrier and 
modules eliminating the need to perform low-level reads/writes 
of registers, and the writing of interrupt handlers. 

 

IOS MODULE LINUX SOFTWARE 

 

Acromag provides a software product (sold separately) 

consisting of Linux  software.  This software (Model IOSSW-
API-LNX) is composed of Linux libraries designed to support 
applications accessing I/O Server Modules installed on 
Acromag Industrial I/O Server systems.  The software is 
implemented as a library of 

“C” functions which link with 

existing user code. 

 
 
2.0   PREPARATION FOR USE 

 

UNPACKING AND INSPECTION 

 

Upon receipt of this product, inspect the shipping carton for 

evidence of mishandling during transit.  If the shipping carton is 
badly damaged or water stained, request that the carrier's agent 
be present when the carton is opened.  If the carrier's agent is 
absent when the carton is opened and the contents of the carton 
are damaged, keep the carton and packing material for the 
agent's inspection. 

 
For repairs to a product damaged in shipment, refer to the 

Acromag Service Policy to obtain return instructions.  It is 
suggested that salvageable shipping cartons and packing 
material be saved for future use in the event the product must be 
shipped.  
 

This board is physically protected with 
packing material and electrically 
protected with an anti-static bag during 
shipment.  However, it is recommended 
that the board be visually inspected for 
evidence of mishandling prior to 
applying power. 
 

 
The board utilizes static-sensitive components and should only 
be handled at a static-safe workstation. 

BOARD CONFIGURATION 

 

Power should be removed from the board when installing IOS 

modules, cables, termination panels, and field wiring.  Refer to 
your IOS module documentation for configuration and assembly 
instructions.  Model IOS-440 digital input boards have no 
hardware jumpers or switches to configure. 

 
 
CONNECTORS 

 

IOS Field I/O Connector (P2) 

 

P2 provides the field I/O interface connections for mating IOS 

modules to the carrier board.  P2 is a 50-pin female receptacle 
header (AMP 173279-3 or equivalent) that mates to the male 
connector of the carrier board (AMP 173280-3 or equivalent).  
This provides excellent connection integrity and utilizes gold 
plating in the mating area.  The field and logic side connectors 
are keyed to avoid incorrect assembly. 

 

P2 pin assignments are unique to each IOS model (see Table 
2.1) and normally correspond to the pin numbers of the field I/O 
interface connector on the carrier board (you should verify this for 
your carrier board). 
 

Table 2.1:  IOS-440 Field I/O Pin Connections (P2) 

Pin Description 

Number 

Pin Description 

Number 

 

IN00 

 

IN16 

21 

 

IN01 

 

IN17 

22 

IN02 

IN18 

23 

IN03 

IN19 

24 

NC 

NC 

25 

IN04 

IN20 

26 

 

IN05 

 

IN21 

27 

IN06 

IN22 

28 

 

IN07 

 

IN23 

29 

 

ACOM 

10 

 

CCOM 

30 

 

IN08 

11 

 

IN24 

31 

 

IN09 

12 

 

IN25 

32 

IN10 

13 

IN26 

33 

IN11 

14 

IN27 

34 

NC 

15 

NC 

35 

IN12 

16 

IN28 

36 

 

IN13 

17 

 

IN29 

37 

IN14 

18 

IN30 

38 

 

IN15 

19 

 

IN31 

39 

 

BCOM 

20 

 

DCOM 

40 

 

No Connection 

41 

 

No Connection 

42 

 

No Connection 

43 

 

No Connection 

44 

 

No Connection 

45 

 

No Connection 

46 

 

No Connection 

47 

 

No Connection 

48 

 

No Connection 

49 

 

No Connection 

50 

 
Input channels of this module are divided into four ports of 

eight channels each.  Channels of a port share a common signal 

 

 

Содержание IOS-440

Страница 1: ...ANUAL ACROMAG INCORPORATED Tel 248 295 0310 30765 South Wixom Road Fax 248 624 9234 P O BOX 437 Wixom MI 48393 7037 U S A solutions acromag com Copyright 2009 Acromag Inc Printed in the USA Data and specifications are subject to change without notice 8500 839 B11C007 retired ...

Страница 2: ...C The inputs normally function as independent input level detectors without interrupts However each input line includes built in event sense circuitry with programmable polarity debounce and interrupt support Inputs also include hysteresis for increased noise immunity The IOS 440 utilizes state of the art Surface Mounted Technology SMT to achieve its wide functionality and is an ideal choice for a...

Страница 3: ...ed keep the carton and packing material for the agent s inspection For repairs to a product damaged in shipment refer to the Acromag Service Policy to obtain return instructions It is suggested that salvageable shipping cartons and packing material be saved for future use in the event the product must be shipped This board is physically protected with packing material and electrically protected wi...

Страница 4: ...ual inputs also include selectable hardware debounce in Enhanced Mode For event sensing the Enhanced Mode allows a specific input level transition High to Low Low to High or Change of State to be detected and optionally generate an interrupt Memory is organized and addressed in separate banks of eight registers or ports eight ports to a bank The Standard Mode of operation addresses the first group...

Страница 5: ... Register IN08 IN15 02 05 Not Driven1 READ4 Port 2 Register IN16 IN23 04 07 Not Driven1 READ4 Port 3 Register IN24 IN31 06 09 Not Driven1 READ2 Port 4 NOT USED 08 0B Not Driven1 READ2 Port 5 NOT USED 0A 0D Not Driven1 READ2 Port 6 NOT USED 0C 0F Not Driven1 READ Port 7 READ MASK REGISTER Also Current Bank Status 0E 0F Not Driven1 WRITE Port 7 WRITE MASK REGISTER Also Bank Select Register 0E Table ...

Страница 6: ... return the status of the mask in bits 0 3 Standard Mode Write Mask Register Port 7 BIT WRITE TO REGISTER READ FROM REGISTER 0 Port 0 Write Mask Port 0 Write Mask 1 Port 1 Write Mask Port 1 Write Mask 2 Port 2 Write Mask Port 2 Write Mask 3 Port 3 Write Mask Port 3 Write Mask 4 7 NOT USED NOT USED Bits 4 7 of this register are not used On power up reset all bits are set to 0 To switch to Enhanced ...

Страница 7: ... the carrier board see Interrupt Enable Register Event Interrupt Status Register for Ports 0 3 BIT READ EVENT STATUS REGISTER 0 Port 0 Interrupt Status IN00 IN07 1 Port 1 Interrupt Status IN08 IN15 2 Port 2 Interrupt Status IN16 IN23 3 Port 3 Interrupt Status IN24 IN31 4 6 NOT USED 7 Interrupt Status Flag Event Polarity Control Register For Ports 0 3 Enhanced Mode Bank 1 Port 6 Write Only A write ...

Страница 8: ...OS clock for debounce The IOS 440 always uses the 8MHz clock for debounce and this register is only provided to facilitate backwards compatibility with the IOS 440 This register is cleared following a reset Bank Select Write Status Read Register 2 Enhanced Mode Bank 2 Port 7 Read and Write Bits 0 5 of this register are not used Bits 6 7 of this register are used to indicate read or select write th...

Страница 9: ... input lines 0 31 Additionally ports are grouped eight to a bank There are four banks of ports used for controlling this module Standard Mode plus Enhanced Mode Banks 0 1 and 2 plus 2 additional registers for enabling the interrupt request line generating a software reset and storing the interrupt vector Each port input line is bipolar and accepts both positive and negative input voltages in two r...

Страница 10: ... channel has been reset by writing a 1 to the corresponding event sense bit in the Event Sense Status Register after writing 0 to clear the event sense flip flop Interrupts may be reflected internally and reported by polling the module or optionally reported to the carrier by enabling control of the Interrupt Request line Intreq0 Control of this line is initiated via Bit 0 of the Interrupt Enable ...

Страница 11: ...or while writing a 0 clears the event sensed without enabling further event sensing 9 Write 00H to the port 7 address to select register bank 0 where the port 0 input channels may be write masked Note that the port 7 address bank selection only operates from bits 6 7 of this register Likewise this register has a dual function depending on whether a read or write is executed As such the polarity se...

Страница 12: ...en a board is first produced and when any repair is made it is tested placed in a burn in room at elevated temperature and retested before shipment Please refer to Acromag s Service Policy Bulletin or contact Acromag for complete details on how to obtain parts and repair PRELIMINARY SERVICE PROCEDURE Before beginning repair be sure that all of the procedures in Section 2 Preparation For Use have b...

Страница 13: ...with no digital upsets Conducted RF Immunity CRFI Complies with EN61000 4 6 3V rms 150KHz to 80MHz and European Norm EN50082 1 with no digital upsets Electromagnetic Interference Immunity EMI No digital upset under the influence of EMI from switching solenoids commutator motors and drill motors Electrostatic Discharge Immunity ESD Complies with EN61000 4 2 Level 3 8KV enclosure port air discharge ...

Страница 14: ...ebounce times are programmable and derived from the 8MHz system clock in combination with the debounce duration register value Debounce times are applied at the FPGA input and do not include opto coupler delay time Debounce values of 4us 64us 1ms and 8ms may be configured Each debounce time has an error of up to 375ns Interrupts Each channel has configurable interrupts They may be configured for h...

Страница 15: ...LE 32 CHANNEL ISOLATED DIGITAL INPUT MODULE _________________________________________________________________________________________ 15 Acromag Inc Tel 248 295 0310 Fax 248 624 9234 Email solutions acromag com http www acromag com ...