Acromag 65*T-0600 Скачать руководство пользователя страница 1

 

 

Series 654T  

Single/Dual Channel Two-Wire Transmitters 

Voltage Input

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

USER’S MANUAL 

 
 
 
 
 

 

 

 

 

 

 

 

 

ACROMAG INCORPORATED 

30765 South Wixom Road 

Wixom, MI 48393-2417 U.S.A. 

Tel: (248) 624-1541 

Fax: (248) 624-9234 

 
 
 

Copyright 2000, Acromag, Inc., Printed in the USA. 

Data and specifications are subject to change without notice. 

 
 
 

8500627H 

Safety Summary - Symbols on equipment: 

 

Содержание 65*T-0600

Страница 1: ...USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road Wixom MI 48393 2417 U S A Tel 248 624 1541 Fax 248 624 9234 Copyright 2000 Acromag Inc Printed in the USA Data and specifications are subject to change without notice 8500627H Safety Summary Symbols on equipment ...

Страница 2: ...ptions or features Table 1 Models Covered in This Manual Series Input Type Options Output Enclosure Approvals1 Factory Configuration2 654T 0600 C Notes Table 1 1 Approvals cULus Listed Hazardous Locations Class I Division 2 Groups A B C D See specifications 2 Include the C suffix to specify factory configuration option Otherwise no suffix is required for standard configuration DESCRIPTION Series 6...

Страница 3: ...able shipping cartons and packing material be saved for future use in the event the product must be shipped This module is physically protected with packing material and electrically protected with an anti static bag during shipment However it is recommended that the module be visually inspected for evidence of mishandling prior to applying power This circuit utilizes static sensitive components a...

Страница 4: ... of power supply ripple You can reduce this ripple by connecting an external 1uF capacitor across the load if desired For sensitive applications with high speed acquisition rates high frequency noise may be reduced by placing a 0 1uF capacitor directly across the load Inductive Loads If the two wire current loop includes a highly inductive load such as an I P transducer this may reduce output stab...

Страница 5: ...ted and has its full range endpoints scaled to the 4 to 20mA output by default However you may use the front panel toggle switches to scale virtually any part of the nominal input range to the 4 20mA output range For example use the 2 to 10V portion of the 0 10V input range to drive the 4 to 20mA output range this configuration will be used as an example in the following procedure Transmitter Zero...

Страница 6: ...sion and digitally filters the signals The digitized signal is then transmitted serially to a microcontroller The microcontroller completes the transfer function according to the input range and scaling configuration and sends a corresponding output signal to an optocoupler and filter circuit A corresponding analog output voltage is generated and used to drive the amplifier that modulates the loop...

Страница 7: ...lution is controlled by the output stage which resolves to 1 part in 6546 for the nominal 4 to 20mA output span Response Time 980ms typical for an analog output to reach 98 of the final value for a step change in input Input Filter Bandwidth 3dB at 3Hz typical Input bias current 25nA typical Noise Rejection Normal Mode Better than 40dB 60Hz typical with 100 input unbalance Noise Rejection Common M...

Страница 8: ...1 Radiated Emissions Meets or exceeds European Norm EN50081 1 for Class B equipment IMPORTANT Power input and output I O wiring must be in accordance with Class I Division 2 wiring methods Article 501 4 b of the National Electrical Code NFPA 70 for installations in the U S or as specified in section 18 1J2 of the Canadian Electrical Code for installations within Canada and in accordance with the a...

Страница 9: ...2 OUT CHANNEL 2 SOURCE IN Acromag CHAN 1 TB2 or TB3 TB2 CHANNEL 1 TB3 WARNING MODEL 654T 0600 GROUND LOOPS AND MEASUREMENT ERROR CHAN 2 MODEL 654T 0600 SHOWN I O Connections CH1 DIPSWITCHES Model 654T 0600 CH2 DIPSWITCHES FOR COMPLIANCE TO APPLICABLE SAFETY AND PERFORMANCE STANDARDS SEE I O CONNECTIONS AT LEFT AVOID MAKING ADDITIONAL GROUND CONNECTIONS WHICH COULD GENERATE NOTE 1 THIS GROUND CONNE...

Страница 10: ...N 0 10V 0 5V 0 2 5V 1 ON Closed 0 OFF Open 0 0 1 0 0 1 1 0 0 0 2 3 6 4 5 1 ON 2 3 4 5 6 7 8 9 10 11 12 12 11 10 9 8 7 1 0 0 1 1 1 1 1 1 0 0 1 1 0 1 1 0 DIP SWITCH SETTINGS SWITCHES 4 11 ARE NOTUSED RECONFIGURATION LOCK UNLOCK DEFAULTCONFIGURATION All Switches OFF 0V to 10V DC Lock ON ConfigurationUNLOCKED ConfigurationLOCKED 4501 798A Z Z FS L FS C DN UP SET DN UP 4 60 116 8 3 75 95 3 3 90 99 1 CH...

Страница 11: ...___________________________________________________________ 11 REVISION HISTORY The following table details the revision history for this document Release Date Version EGR DOC Description of Revision 3 AUG 2017 H CAP JAA Remove CE Mark due to non RoHS compliant part Refer to ECN 17G016 ...