Series 654T Transmitter User's Manual Voltage Input
___________________________________________________________________________________________
- 8 -
APPROVALS (-xxx0)
0
: cULus Listed
Hazardous Locations: Class I; Division 2; Groups A, B, C, D.
ENCLOSURE/PHYSICAL SPECIFICATIONS
Unit is packaged in a general purpose plastic enclosure that is
DIN rail mountable for flexible, high density (approximately 1”
wide per unit) mounting. See Enclosure Dimensions Drawing
4501-780 for details.
Dimensions
: Width = 1.05 inches, Height = 4.68 inches, Depth
= 4.35 inches (see Drawing 4501-780).
DIN Rail Mounting (-xx0x):
DIN rail mount, Type EN50022; “T”
rail (35mm).
Connectors:
Removable plug-in type terminal blocks; Current/
Voltage Ratings: 15A/300V; Wire Range: AWG #14-24 solid
or stranded; Separate terminal blocks are provided for each
I/O channel.
Case Material:
Self-extinguishing NYLON type 6.6 polyamide
thermoplastic, UL94 V-2, color beige; general purpose NEMA
Type 1 enclosure.
Printed Circuit Boards:
Military grade FR-4 epoxy glass.
Shipping Weight:
1 pound (0.45 Kg) packed.
ENVIRONMENTAL SPECIFICATIONS
Operating Temperature:
-25
C to +75
C (-13
F to +167
F),
Temperature Code: T4.
Storage Temperature:
-40
C to +85
C (-40
F to +185
F).
Relative Humidity:
5 to 95%, non-condensing.
Isolation:
Inputs, outputs, and channels are isolated from each
other for common-mode voltages up to 250VAC, or 354V DC
off DC power ground, on a continuous basis (will withstand
1500VAC dielectric strength test for one minute without
breakdown). This complies with test requirements outlined in
ANSI/ISA-82.01-1988 for the voltage rating specified.
Installation Category:
Designed to operate in an Installation
Category for use in pollution degree 2..
Radiated Field Immunity (RFI):
Designed to comply with
IEC1000-4-3 Level 3 (10V/M, 80 to 1000MHz AM & 900MHz
keyed) and European Norm EN50082-1.
Electromagnetic Interference Immunity (EMI):
No output shift
will occur beyond
0.25% of span, under the influence of EMI
from switching solenoids, commutator motors, & drill motors.
Electrical Fast Transient Immunity (EFT):
Complies with
IEC1000-4-4 Level 3 (2KV) and European Norm EN50082-1.
Electrostatic Discharge (ESD) Immunity:
Complies with
IEC1000-4-2, Level 3 (8KV/4KV air/direct discharge) to the
enclosure port and European Norm EN50082-1.
Surge Immunity:
Complies with IEC1000-4-5 Level 3 (2.0KV)
and European Norm EN50082-1.
Radiated Emissions:
Meets or exceeds European Norm
EN50081-1 for Class B equipment.
IMPORTANT:
Power, input, and output (I/O) wiring must be in
accordance with Class I, Division 2 wiring methods Article 501-
4(b) of the National Electrical Code, NFPA 70 for installations in
the U.S., or as specified in section 18-1J2 of the Canadian
Electrical Code for installations within Canada and in accordance
with the authority having jurisdiction.
This equipment is suitable for use in Class I, Division 2,
Groups A, B, C, and D, or non-hazardous locations only.
WARNING
– EXPLOSION HAZARD
– Substitution of
components may impair suitability for Class I, Division 2.
WARNING
– EXPLOSION HAZARD
– Do not disconnect
equipment unless power has been switched off or the area is
known to be non-hazardous.
CAUTION
–
To reduce the risk of fire or electric shock, do not
interconnect the outputs of different class 2 circuits.
CONFIGURATION CONTROLS
Configuration of this transmitter is accomplished via external
DIP switches and toggle switches provided for each channel and
described below:
Toggle Switches (Each Channel, See Drawing 4501-798):
The following SPDT toggle switches are used to configure the
transmitter’s zero and full-scale end points (input to output
scaling) and are located on the front panel. Adjustment via
these switches may be locked out via DIP switch 12 (see
below).
Z (Zero) Up/Down -
Used to adjust the
Zero
endpoint during
field configuration. With a zero input signal applied,
depress this toggle to the UP direction to raise the output
zero level, or DN to lower the output zero level.
FS (Full-Scale) Up/Down -
Used to adjust the
Full-Scale
endpoint during field configuration. With the full-scale
input signal applied, depress this toggle to the UP
direction to raise the full-scale output level, or DN
direction to lower the full-scale output level.
DIP Switches (See Drawing 4501-798 For Location):
Options Configuration
- Used to select the input range and
lock or unlock reconfiguration. Refer to Drawing 4501-
798 and INSTALLATION section to set switches. Note
that switches 4-11 are non-functional for this model.
Input - Range (S1-3):
The transmitter can be configured
to accept any one of eight voltage ranges. Input ranges
are already factory calibrated.
Unlock Reconfiguration (S12):
This switch is normally
enabled (locked) and must be set ON to unlock zero/full-
scale reconfiguration capability of the front panel toggle
switches. It is provided as an extra level of security to
help prevent inadvertent reconfiguration or tampering in
the field.