INSTRUCTIONS:  Model 4683-TTM-xF

 

AC-Powered RS-485 Network Repeaters 

⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯

 

 

 

⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯

 

Acromag Incorporated, 30765 South Wixom Road   

   P.O. Box 437   

   Wixom, MI   

   48393-7037, USA 

Phone: (248) 295-0880   

 Fax: (248) 624-9234   

 E-mail: [email protected]   

 On-Line: http://www.acromag.com 

 
Copyright 1990, Acromag, Inc.  Printed in the USA.                                                                                                    8500-758-C08H015

 

 

MODEL DESCRIPTION 

 

Model Power 

4683-TTM-1F 

115V AC ±10% 

4683-TTM-2F 

230V AC ±10% 

4683-TTM-3F 

   24VAC ±10% 

 

These devices are “rugged” RS-485 network repeaters used for 
isolating network signals and extending communication 
distances.  Model 4683-TTM-xF units are similar to the 
Acromag Model 4SCR-TTM-x models, but add field-selectable, 
End-Of-Line (EOL) network terminations on board for both the 
A and B sides, are UL/cUL approved, and work at higher baud 
rates. 

 

Operation is transparent to all other network devices and no 
handshaking is required.  Up to 32 RS-485 devices can be 
driven.  These repeaters are enclosed in a rugged aluminum 
enclosure and come ready to mount on any base plate, or can 
be installed into a NEMA enclosure for harsh environments. 
 
Installation is as simple as mounting, setting the baud rate, 
connecting and terminating the network, and connecting power. 
 

FEATURES 

 

    Designed for use with Johnson Controls N2 or BACnet 

MS/TP bus. 

 

    No handshaking & No extra control lines required. 

 

    Full I/O signal isolation. 

 

    Supports baud rates of 600, 1200, 2400, 4800, 9600, 

19.2K, 38.4K, and 76.8K, switch-selectable. 

 

    Field-selectable, End-of-Line (EOL) network terminators on 

both the A (input) and B (output) sides. 

 

    Transient protection installed to help protect connected 

devices from destructive noise spikes and line transients. 

 

    Status LED’s indicate transmission direction, RS-485 bus 

fault conditions, and power. 

 

    115VAC, 230VAC, and 24VAC models supported (no 

separate transformers are required for 24VAC models). 

 

OPERATION 

 

The Model 4683-TTM-xF network repeaters are used to isolate 
and boost RS485 signals and extend network distance.  Each 
repeater will permit the addition of up to another 32 devices to a 
network, and extend the communication distance another 4000 
feet. 

 

The repeater has two “sides” referred to as side A and side B.  
Side A typically connects to the network towards the host (input 
side).  Side B connects to the extended network (output side).  
Functionally, sides A and B are equivalent.  Transient signal 
protection is provided on both RS-485 sides.  When both RS-
485 lines are idle, each side is in the receive mode.  When a 
one to zero transition is detected (signifying a start bit) on either 
side, the opposite side’s transmitter is enabled (half-duplex).  
The transmitter stays enabled for one character’s time (based 
on the baud rate switch setting).  The character received is then 
passed through. 

 

The repeater receives AC power through a three-screw terminal 
strip.  Input power is fused and isolated.  Model 4683-TTM-1F 
units require 115VAC, 4683-TTM-2F units require 230VAC, and 
4683-TTM-3F units require 24VAC. 

COMMUNICATION SPECIFICATIONS 

 

Baud Rates:

  DIP switch settings on unit for 600, 1200, 2400, 

4800, 9600, 19.2K, 38.4K, & 76.8K baud rates.  Only one 
switch must be closed according to baud rate required for 
proper operation.  

 

RS-485 Bus Loading:

  One unit load equivalent. 

 

RS-485 Bus Drive:

  Complete RS-485 compliance for up to 32 

unit loads (31 unit loads if a repeater is used). 

 

End-of-Line Termination Network:

  Refer to Figure 1.  The 

EOL termination network is individually selected for both 
the A and B sides by a pair of shorting clips.  The A side 
(input) is controlled by jumpers J1 & J2.  The B side 
(output) is controlled by jumpers J3 & J4.  

 

The EOL network termination is enabled for the A side or 
the B side when the associated pair of jumpers are 
positioned over pins 1 and 2.  The EOL termination is 
disabled (removed from circuit) when the pair of jumpers 
are positioned over pins 2 and 3. 

 

Duplex:

  Half duplex only.  

 

Data Format:

  Ten bits typical (1 start bit, 8 data bits, and 1 

stop bit).  Other formats are supported. 

 

Status Indicators:  

Red power LED; red RS-485 bus fault 

LED’s, side A & B; green transmit LED’s, A-to-B & B-to-A. 

 

PHYSICAL SPECIFICATIONS 

 

Operating Temperature:

  -25°C to 70°C (-13°F to 158°F). 

 

Relative Humidity (RH):

  10 to 95% RH (non-condensing), up 

to 40° C (104° F). 

 

Power:

  115VAC ±10%, 50/60Hz, 0.05A (Model 4683-TTM-1F); 

230VAC ±10%, 50/60Hz, 0.03A (Model 4683-TTM-2F); 
24VAC ±10%, 50/60Hz, 0.18A (Model 4683-TTM-3F). 

 

Power Line Fuse:

  0.5A, 250V, 3AG type.  Refer to Figure 1 

for fuse location. 

 

Isolation:

  Unit includes galvanic and optical isolation between 

RS-485 side A, RS-485 side B, AC power, and chassis 
ground.  Common mode voltages of up to 250Vrms, or 
354V DC (withstands a 1500V AC dielectric strength test 
for 1 minute without breakdown), are permitted on a 
continuous basis.  This complies with test requirements 
outlined in ANSI C39.5-1974 for voltage ratings specified.  

 

RFI Resistance:

  Withstands RFI field strengths of up to 10V 

per meter at 27MHz, 151MHz, and 467MHz with no digital 
effect, per SAMA PMC 33.1 test procedures.  

 

Line Noise Effects:

  Field and power line terminals withstand 

ANSI/IEEE C37.90-1978 Surge Withstanding Capability 
(SWC) Test with no component failures.  Unit is tested to 
a standardized test waveform that is representative of 
surges (high-freq. transient electrical interference), 
observed in actual installations.  

 

Communication Connections:

  Network repeater – both RS-

485 connections use modular terminal blocks with screw 
clamps.  Wire range is 14 to 26 AWG.  

 

Power Wire Connections:

  Network repeater terminal block. 

See label on unit for power to be applied to unit.  

 

Approvals:

  UL/cUL Listed, US & Canada, Energy 

Management Equipment. 

 

Shipping Weight:

  3.0 pounds (1.4 kg) packed per unit. 

Содержание 4683-TTM-1F

Страница 1: ...sed through The repeater receives AC power through a three screw terminal strip Input power is fused and isolated Model 4683 TTM 1F units require 115VAC 4683 TTM 2F units require 230VAC and 4683 TTM 3F units require 24VAC COMMUNICATION SPECIFICATIONS Baud Rates DIP switch settings on unit for 600 1200 2400 4800 9600 19 2K 38 4K 76 8K baud rates Only one switch must be closed according to baud rate...

Страница 2: ...and attach 120Ω termination resistors externally between the RT terminals adjacent to the network connections but this can only be used if the trunk bias is applied somewhere else on the network Reference Section 4 4 1 Idle line Fail safe of the TIA Telecommunications systems bulletin application guideline for TIA EIA 485A Setting The Baud Rate The unit includes an 8 position DIP switch S1 along t...

Страница 3: ...N ST 1 RUN BAUD RATE COM DFT Acromag A N3 DFT Acromag A N5 BAUD RATE B N1 Acromag B N3 DFT Acromag B N5 DFT Acromag 1 300 5 4800 2 600 6 9600 3 600 7 19 2K 4 2400 8 38 4K AC INPUT TB 1 RS 232C 232 485 RS485 FAULT TB 2 RS 485 FAULT A TX B A RS 485 SIDE B FAULT B acromag POWER HOST PC A N1 RS 485 DFT Acromag A N4 DFT Acromag UP TO 4000 FEET SIGNAL REPEATER RS 485 OUTPUT SIDE B Acromag ANY RS 485 DEV...

Страница 4: ...TION RED POWER LED B N4 B N5 Ground 230VAC UP TO 32 NODES PER NETWORK SEGMENT B N32 COM SIGNALS AT CONVERTER HOST RED RS485 FAULT LED SIDE A TRANSMIT DIRECTION B TO A A TO B 2 OPTION 230VAC GROUND AC HI AC LO 1 OPTION SET BAUD RATE AT S1 TRANSMIT DIRECTION RS485 TO RS232 AND RS232 TO RS485 DE9 DB25 TO HOST RS232 CONNECTIONS TO HOST COMPUTER HOST PC RED RS485 FAULT LED SIDE B NOTE SIDE A AND SIDE B...