5.2.3 Installation method of ACLP10-24 DC24V power supply
The ACLP10-24 DC24V power supply is used to install in the way of guide rail, which is fixed with snap-in
type. It can also be installed on the same guide rail side by side with the AIM-R100 insulation monitor.
5.3 Wiring method
5.3.1 Wiring method of AIM-R100 residual current monitor
Upper terminals: U1, U2 (1, 2) are AC220V auxiliary power supply. I
△
1~I
△
8 (3, 4, 5, 6, 8, 9, 10, 11) are
connected to one end of the residual current transformer, and COM1 (7) or COM2 (12) are connected to the other
end of the residual current transformer corresponding (wiring without polarity).
Lower terminal: Z1, Z2 (13, 14) access to external self-check reset button, DO1+, DO1- is alarm relay
output, A, B is centralized alarm and display instrument terminal, I
△
9-I
△
12 (24, 23, 22, 21) access to the end of
the residual current transformer, COM3 (20) access to the other end of the residual current transformer (wiring
without polarity).