Medical IT System Insulation Monitoring Devices 

(Four-Piece Set) 

 

Installation and Operation Manual V2.5 

 

 

 

 

 

 

 

 

Acrel Co., Ltd. 

Содержание AID120

Страница 1: ...163 Medical IT System Insulation Monitoring Devices Four Piece Set Installation and Operation Manual V2 5 Acrel Co Ltd...

Страница 2: ...by ignoring tips of this manual Transformers and related insulation monitors are professional electrical equipment and any relevant operation needs to be carried out by specialized electrical technici...

Страница 3: ...h sub product 02 2016 10 25 V2 1 Some errors have been fixed 03 2016 11 7 V2 2 The overview added products conform to Enterprise standards Q31 0114000129C013 2016 IT System Insulation Monitoring Instr...

Страница 4: ...lation monitor 5 4 3 Technical parameters of AID10 AID150 6 4 4Technical parameters of AKH 0 66P26 current transformer 6 5 Installation and wiring 7 5 1 Shape and mounting hole size 7 5 2 Wiring metho...

Страница 5: ...four piece set of medical IT system insulation monitoring products in operating room 26 9 Power on and debugging instructions 27 9 1 Wiring check 27 9 2 Common faults and eliminations 28 9 3 Settings...

Страница 6: ...et include AITR series medical isolation transformer AIM M10 medical intelligent insulation monitor AKH 0 66P26 current transformer and AID series AID10 AID150 external alarm and display instrument et...

Страница 7: ...ght alarm can be remote The AID150 can also monitor data from multiple AIM R100 residual current monitors 2 Function features 2 1 Function features of AITR series medical isolation transformer The tra...

Страница 8: ...on of AID Series Products Model Selection Description AID10 It can monitor one set of AIM M10 insulation monitor and be used for installation by embedding into wall AID150 It can monitor 16 sets of AI...

Страница 9: ...Table 3 Technical Parameters of AITR Series of Medical Isolation Transformer Type AITR10000 AITR8000 AITR6300 AITR5000 AITR3150 Insulation class H H H H H Protection class IP00 IP00 IP00 IP00 IP00 Pow...

Страница 10: ...40dB 40dB 40dB 40dB 40dB 4 2 Technical parameters of AIM M10 medical insulation monitor Refer to Table 4 Table 4 Technical parameters of AIM M10 insulation monitoring instrument Auxiliary power suppl...

Страница 11: ...AID120 150 Parameter Type AID10 AID150 Auxiliary power supply Voltage DC 24V Consumption 0 6W Insulation alarming range 14A 18A 22A 28A 35A 45A Temperature alarm setting range 0 200 Number of monitor...

Страница 12: ...mensions of AITR series medical isolation transformer unit mm Shape structure and size of AITR series medical isolation transformer are shown as below and in Table 7 unit mm External dimensions of AIT...

Страница 13: ...ternal dimensions of AID series unit mm On Overload Insulation Overtemp Test AID10 Mute AID10 front view AID10 hole size AID10 side view T e s t M u t e M e n u A c r e l On Comm AID150 AID150 front v...

Страница 14: ...nsulation monitoring instrument Figure 2 AITR series medical isolation transformer terminal blocks diagram Note The wirings of input and output terminals of the isolation transformer should select the...

Страница 15: ...rounding wires J1 J2 relay output are the dry nodes which need additional power supply during the control of external load For example J1 controls AC 220V cooling fan then the AC 220V power supply is...

Страница 16: ...o far from the AIM M10 insulation monitor When the AID10 150 external alarm and display instrument is used in the operating room it can be embedded in the wall and installed next to the information pa...

Страница 17: ...Overload Insulation OverTEMP Test AID10 Mute 86 boxes and walls 86 boxes and walls 86 boxes and walls Lower shell assembly 2 Connect the connecting wire to the AID10 rear cover assembly through the te...

Страница 18: ...close to the knockouts of the pipeline so that the wires two power cords a two core shielded twisted pair can be drawn to the front cover and then fix the cover on the shell with screws 2 If the AID1...

Страница 19: ...ith 6A fuse protection in series 3 The relay output control of the No 7 and 8 terminals of the AIM M10 insulation monitor is a dry node which needs an additional fan power supply when used for the fan...

Страница 20: ...the field space is too limited to apply the isolation power cabinet the isolation transformer can be installed separately but should not be too far away from the insulation monitor and the field load...

Страница 21: ...3 15kVA 20A If the circuit breaker selection is not in accordance with the above requirements the company shall not be liable for any medical malpractice caused by the closure difficulty of the circu...

Страница 22: ...ds the alarm value the indicator light flashes to alarm 6 2 3 AID150 Indicator status Instructions On When the device is in normal operation the indicator flashes and the flickering frequency is about...

Страница 23: ...nd Up button Down button In programming mode used to increase or decrease the value Test button In non programming mode used to start the self test function of instrument Menu Enter shared button In n...

Страница 24: ...to enter the programming mode 2 In programming mode the instrument parameters are set After entering the programming mode press Up or Down to view each parameter interface In the programming mode pre...

Страница 25: ...larm and display key operation 1 Description of the Operating Interface After the system is powered on if there is no fault alarm AID150 shows the normal operation interface as shown in the following...

Страница 26: ...07 02 12 30 45 Press up and down key Press Enter NO 03 Press Erasure to return System normal Slave addr 00 Type No record Time 00 00 00 00 00 Press up and down key 3 Programming Interface Operation a...

Страница 27: ...n to select the Comm and press Enter to confirm Press Up and Down to select Firmware and press Enter to confirm Press Erasure to return Press Up and Down to select the Clear and press Enter to confirm...

Страница 28: ...smitted in two opposite directions Firstly the signal from the main computer is addressed to a unique terminal device slave computer and then the answering signal emitted from the terminal device is t...

Страница 29: ...dress of 01 with an installation date and time of 12 00 Friday December 1 st 2009 in which the Monday to Sunday are replaced with number 1 to 7 The host computer sends Send message The slave computer...

Страница 30: ...Default 11 1 0004Hlow byte month R W 1 12 Unit month Default 4 6 0005Hhigh byte day R W 1 31 Unit day Default 20 1 0005low byte week R W 1 7 Unit week Default 3 7 0006Hhigh byte hour R W 1 24 Unit hou...

Страница 31: ...70 1 20 24 0013H 0017H Reserve 5 25 0018Hhigh byte SOE1 Reserve 1 0018Hlow byte STA1 R SOE1 type 0 6 0 No fault record 1 Insulation fault 2 Overload fault 3 Over temperature fault 4 Ll disconnection 5...

Страница 32: ...shadowless lamp MED IMD Note The grounding bat in the isolated power supply cabinet should be connected reliably with the equipotential terminals in the field 9 Power on and debugging instructions 9...

Страница 33: ...on the system Then check whether each meter is abnormal and whether there is a fault alarm in AIM M10 For common problems the causes can be determined and the faults can be eliminated according to the...

Страница 34: ...ication parameter setting In order to realize the centralized monitoring function of multiple sets of insulation monitors through the centralized alarm and display AID150 it is necessary to set the sl...