background image

4

imPortant SaFEtY inFormation

Please read all instructions before servicing this equipment. 

Pay attention to all safety warnings and any other special 

notes highlighted in the manual. Safety markings are 

used frequently throughout this manual to designate a 

degree or level of seriousness and should not be ignored. 

Warning

 indicates a potentially hazardous situation that 

if not avoided, could result in personal injury or death. 

caution

 indicates a potentially hazardous situation that 

if not avoided, may result in minor or moderate injury or 

property damage.

about tHE HEat PumP

Your heat pump is a unique, all weather comfort-control 

appliance that will heat and cool your home year round 

and provide energy saving comfort. It’s an unknown fact 

that heat is always in the air, even when the outside 

temperature is below freezing. The heat pump uses this 

basic law of physics to provide energy saving heat during 

the winter months. For example, If the outdoor temperature 

is 47° F (8° C), your heat pump can deliver approximately 

3.5 units of heat energy per each unit of electrical energy 

used, as compared to a maximum of only 1 unit of heat 

energy produced with conventional heating systems.
In colder temperatures, the heat pump performs like an air 

conditioner run in reverse. Available heat energy outside 

the home is absorbed by the refrigerant and exhausted 

inside the home. This efficient process means you only 

pay for “moving” the heat from the outdoors to the indoor 

area. You do not pay to generate the heat, as is the case 

with more traditional furnace designs.
During summer, the heat pump reverses the flow of the 

heat-absorbing refrigerant to become an energy-efficient, 

central air conditioner. Excess heat energy inside the 

home is absorbed by the refrigerant and exhausted 

outside the home.

oPErating inStructionS

Please refer to the thermostat manufacturer’s User manual 

for detailed programming instructions.

cooling operation

1. Set the thermostat’s system mode to COOL or AUTO 

and change the fan mode to AUTO. See 

Figure 1

.

2. Set the temperature selector to the desired temperature 

level. The outdoor fan, compressor, and blower motor will 

all cycle on and off to maintain the indoor temperature 

at the desired cooling level.

 notE: 

If the temperature level is re-adjusted, or the 

system mode is reset, the fan and compressor in the 

outdoor unit may not start immediately. A protective 

timer circuit holds the compressor and the outdoor fan 

off for approximately three minutes following a previous 

operation or the interruption of the main electrical power.

Heating operation

1. Set the thermostat’s system mode to HEAT or AUTO 

and change the fan mode to AUTO. See 

Figure 1

.

2. Set the temperature selector to the desired temperature 

level. The compressor, outdoor fan, and blower motor 

will cycle on and off to maintain the indoor temperature 

at the desired heating level.

 notE:

 If the temperature level is re-adjusted, or the 

system mode is reset, the fan and compressor in the 

outdoor unit may not start immediately. A protective 

timer circuit holds the compressor and the outdoor fan 

off for approximately three minutes following a previous 

operation or the interruption of the main electrical power.

Emergency Heat

Some thermostats may include a system mode called EM 

HT or AUX HT, etc. This is a back-up heating mode that 

should only be used if a problem is suspected. With the 

mode set to EM HT, etc., the compressor and outdoor fan 

will be locked off and supplemental heat (electric resistance 

heating) will be used as a source of heat. Sustained use 

of electric resistance heat in place of the heat pump will 

result in an increase in electric utility costs.

Defrost operation

During cold weather heating operation, the outdoor unit 

will develop a coating of snow and ice on the heat transfer 

coil. This is normal and the unit will defrost itself. This unit 

features Demand Defrost that monitors ambient and coil 

temperatures to regulate the defrost function accordingly.

notE:

 While the ice and snow is melting, some steam 

may rise from the outdoor unit as the warm coil causes 

the melting frost to evaporate.

Figure 1. Digital thermostat

Fan

mode

temperature

Selector

System

mode

uSEr inFormation

Содержание Q6SE X36

Страница 1: ... plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedtoassistqualifiedindividualsexperiencedintheproper installation of this appliance Some local codes require li...

Страница 2: ...2 ...

Страница 3: ... the Heat Pump for Automatic Cooling Heating 5 Operating the Indoor Blower Continuously 5 Shutting the Heat Pump Off 5 HEAT PUMP MAINTENANCE 5 Regular Cleaning 5 TROUBLESHOOTING 5 Warranty Information 5 START UP adjustments 13 Pre Start Check List 13 Start Up Procedure 13 Air Circulation 13 Short Cycle Protection 13 System Cooling 13 System Heating 13 Refrigerant Charging 13 Charging an R 410A Uni...

Страница 4: ...hange the fan mode to AUTO See Figure 1 2 Setthetemperatureselectortothedesiredtemperature level Theoutdoorfan compressor andblowermotorwill all cycle on and off to maintain the indoor temperature at the desired cooling level NOTE If the temperature level is re adjusted or the system mode is reset the fan and compressor in the outdoor unit may not start immediately A protective timer circuit holds...

Страница 5: ... service on the system Failure to comply may result in personal injury or death Proper maintenance is most important to achieve the best performancefromtheapplianceandshouldbeperformed by a qualified service technician at least once a year Follow the maintenance schedule and the instructions below for years of safe trouble free operation Regular Cleaning Clean or replace the indoor air filter at t...

Страница 6: ...authorized parts or accessory kits may be used with this product Improper installation service adjustment ormaintenance may cause explosion fire electrical shock or other hazardous conditions which may result in personal injury or property damage WARNING The safety information listed below must be followed during the installation service and operation of this unit Unqualified individuals shouldnot...

Страница 7: ... calculatedandasystemofthepropercapacityselected It is recommended that the area to be conditioned be completely insulated and vapor sealed Check the electrical supply and verify the power supply is adequate for unit operation If there is any question concerning the power supply contact the local power company Allunitsaresecurelypackedatthetimeofshipmentand upon arrival should be carefully inspect...

Страница 8: ...ans are used to hoist the unit are safe and adequate The lifting equipment must be adequate for the load Refer to Table 5 page 15 for unit weights The unit must be lifted from the holes in the base rails using cables or chains Spreader bars are required to protect the unit and ensure even loading Keep the unit in an upright position at all times The rigging must be located outside the units center...

Страница 9: ...ccess panel was designed to fit underneath the top panel 2 Slide the first filter between both guide channels of filter rack and allow the filter to drop easily into place 3 Verify the bottom of the filter is within the channels of the rack 4 Slide the 2nd filter and 3rd filter on taller models between both guide channels of filter rack 5 Verify the top of the filter is within the channels of the ...

Страница 10: ...ct it to the terminal marked 208V Optional equipment requiring connection to the power or control circuits must be wired in strict accordance of the NEC ANSI NFPA 70 applicable local codes and the instructions provided with the equipment ELECTRICAL WIRING WARNING To avoid risk of electrical shock personal injury ordeath disconnectallelectricalpowertotheunit before performing any maintenance or ser...

Страница 11: ...ermostat connections are listed in Table 3 page 12 The thermostat should be mounted about 5 feet above theflooronaninsidewall DONOTinstallthethermostat on an outside wall or any other location where its operationmaybeadverselyaffectedbyradiantheatfrom fireplaces sunlight or lighting fixtures and convective heat from warm air registers or electrical appliances Refer to the thermostat s instruction ...

Страница 12: ...y 6 hours and 4 minutes unless the coil temperature is above the selected terminate temperature Thesystemcanbemanuallyforcedintodefrostmodeat any time by shorting the TEST terminals on the demand defrost board together for more than 9 seconds The coil temperature sensor does not need to be cold when the unit is forced into defrost After the TEST input is removed thedefrostmodewillterminatein13 7mi...

Страница 13: ...nit are free from obstructions and debris and all equipment access control panels are in place Verifythattheductworkissealedtopreventairleakage Verify that the line voltage power leads are securely connected and the unit is properly grounded Verify that the low voltage wires are securely connected to the correct leads on the low voltage terminal strip Verify that the outdoor fan turns freely Verif...

Страница 14: ...structed with sheet metal WARNING Do not place combustible material on or against the unit cabinet Do not place combustible materials including gasoline and any other flammable vapors and liquids in the vicinity of the unit CAUTION The unit should never be operated without a filterinthereturnairsystem Replacedisposable filters with the same type and size Proper maintenance is important to achieve ...

Страница 15: ... 24 9 13 5 16 12 13 3 13 5 16 12 CG A 47 5 75 NPT Female Drain Connector B DOWNFLOW SUPPLY DUCT OPENING DOWNFLOW RETURN DUCT OPENING 23 5 Back View 13 5 16 0 13 7 13 5 16 0 12 45 11 75 22 75 55 8 C HORIZONTAL SUPPLY DUCT OPENING HORIZONTAL RETURN DUCT OPENING 4 0 CONDENSING COIL 5 0 8 4 00 Side View 1 1 4 Ø Power Entry 1 3 4 Ø Power Entry Capped 22 25 Ø Control Wiring Entry 23 3 5 27 1 5 30 1 4 5 ...

Страница 16: ...FROST BOARD Typical Wiring for Two Stage Heat Pump Cool Operation Economizer HP Cool E R W1 O Y2 C G A1 Y1 UNIT LOW VOLTAGE TERMINAL BOARD Y2 E R W2 IN O Y C M 1 2 3 4 5 6 7 8 9 Brown ACCESSORY HEAT PLUG 1 2 3 4 5 6 7 8 9 ECONOMIZER PLUG IF APPLICABLE SEE ECONOMIZER INSTALLATION INSTRUCTIONS Blower Relay See Note L W2 OUT W2 FACTORY WIRING FIELD WIRING NOTE If installing an economizer using the ne...

Страница 17: ...DEFROST BOARD ACCESSORY HEAT PLUG E R W1 O Y2 C G A1 Y1 UNIT LOW VOLTAGE TERMINAL BOARD Y2 M E R W2 IN O Y C Typical Wiring for Two Stage Heat Pump Cool Operation Economizer HP Cool 1 2 3 4 5 6 7 8 9 ECONOMIZER PLUG IF APPLICABLE SEE ECONOMIZER INSTALLATION INSTRUCTIONS See Note Blower Relay See Note W2 OUT L W2 FACTORY WIRING FIELD WIRING NOTE If installing an economizer using the new Honeywell W...

Страница 18: ...TIME IS ACCUMLATED OPENING OF DFT DURING DEFROST OR INTERVAL PERIOD RESETS THE INTERVAL TO 0 NOTE See Installation Instructions for wiring application and Information concerning accessory Heat Kits and other options WIRING DIAGRAM 10160710 1 2 3 4 5 6 7 8 9 9 8 1 7 6 5 4 3 2 9 8 1 7 6 5 4 3 2 T2 T1 T3 R C S T2 T1 N G L C T3 T4 T5 TO 208 230 VAC POWER SUPPLY 9 8 1 7 6 5 4 3 2 9 8 1 7 6 5 4 3 2 3 PH...

Страница 19: ...CK YELLOW YELLOW BLACK GREEN RED BROWN WHITE BLUE BLACK WHITE YELLOW GREY ORANGE BROWN YELLOW BLACK RED RED BROWN BLACK RED RED YELLOW GREEN BLACK BLACK 460 Volt Convertible Packaged Heat Pump Three Phase 60Hz WIRING DIAGRAM NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 If any of the original wire as supplied with the furnace must be replaced i...

Страница 20: ...when above curve Add refrigerant when below curve Figure 12 Charging Chart for 3 Ton Units Q6SE X48 Charging Chart Cooling 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F Remove refrigerant when above curve Add refrigerant when below curve Figure 13 Charging Chart for 4 Ton ...

Страница 21: ...1 20 01 1358 20 94 1279 22 23 X48 Tap T1 952 29 87 901 31 56 864 32 91 728 39 06 672 42 31 583 48 77 508 55 97 Tap T2 1646 17 27 1593 17 85 1520 18 71 1476 19 26 1417 20 07 1349 21 08 1265 22 48 1198 23 73 Tap T3 1764 16 12 1705 16 68 1626 17 49 1570 18 11 1525 18 65 1451 19 60 1403 20 27 1304 21 81 Tap T4 1962 14 49 1916 14 84 1838 15 47 1787 15 91 1720 16 53 1670 17 03 1595 17 83 1537 18 50 Tap ...

Страница 22: ...22 ...

Страница 23: ...23 ...

Страница 24: ...uct Safety should always be the deciding factor when installing this product and using common sense plays an important role as well Pay attention to all safety warnings and anyotherspecialnoteshighlightedinthemanual Improperinstallationof the unit or failure to follow safety warnings could result in serious injury death or property damage These instructions are primarily intended to assist qualifi...

Отзывы: