background image

10

condensate

Drain

Figure 6. condensate Drain location

line Voltage

•  A wiring diagram is located on the inside cover of the 

units electrical box. The installer should become familiar 

with the wiring diagram before making any electrical 

connections to the outdoor unit.

• 

an electrical disconnect must be located within sight 

of and readily accessible to the unit. 

This switch shall 

be capable of electrically de-energizing the unit.

•  Line  voltage  to  the  unit  should  be  supplied  from  a 

dedicated branch circuit containing the correct fuse 

or circuit breaker for the unit. Incoming field wiring 

and minimum size of electrical conductors and circuit 

protection must be in compliance with information listed 

on the outdoor unit data label. Any other wiring methods 

must be acceptable to authority having jurisdiction.

•  The outdoor unit requires both power and control circuit 

electrical connections. Refer to the wiring diagrams for 

identification and location of outdoor unit field wiring 
interfaces. See 

Figure 10 (page 18)

 & 

Figure 11 (page 

19)

. Make all electrical connections in accordance 

with all applicable codes and ordinances.

•  Overcurrent protection must be provided at the branch 

circuit distribution panel and sized as shown on the unit 

rating label and according to applicable local codes. See 

the unit rating plate for minimum circuit ampacity and 

maximum overcurrent protection limits.

•  Provide power supply for the unit in accordance with the 

unit wiring diagram, and the unit rating plate. Connect 

the line-voltage leads to the terminals on the contactor 

inside the control compartment.

•  Use only copper wire for the line voltage power supply 

to this unit as listed in 

Table 2

. Use proper code agency 

listed conduit and a conduit connector for connecting 

the supply wires to the unit. Use of rain tight conduit is 

recommended.

•  Units are shipped from the factory wired for 230 or 460 

volt operation. For 208 - 230V operation, remove the 

lead from the transformer terminal marked 240V and 

connect it to the terminal marked 208V.

•  Optional equipment requiring connection to the power 

or control circuits must be wired in strict accordance of 

the NEC (ANSI/NFPA 70), applicable local codes, and 

the instructions provided with the equipment.

ElEctrical Wiring

 Warning:

to avoid risk of electrical shock, personal injury, 

or death, disconnect all electrical power to the unit 

before performing any maintenance or service. 

the unit may have more than one electrical supply.
label all wires prior to disconnection when 

servicing the unit. Wiring errors can cause 

improper and dangerous operation

•  Electrical  connections  must  be  in  compliance  with 

all applicable local codes and ordinances, and with 

the current revision of the National Electric Code  

(ANSI/NFPA 70).

•  For  Canadian  installations  the  electrical  connections 

and grounding shall comply with the current Canadian 

Electrical Code (CSA C22.1 and/or local codes).

Pre-Electrical checklist:

 Verify that the voltage, frequency, and phase of the 

supply source match the specifications on the unit rating 

plate.

  Verify that the service provided by the utility is sufficient 

to handle the additional load imposed by this equipment. 

refer to the unit wiring label for proper high and low 

voltage wiring.

  Verify factory wiring is in accordance with the unit wiring 

diagram. See 

Figure 10 (page 18)

 & 

Figure 11 (page 

19)

. Inspect for loose connections.

  Phase balance on 3 phase units must always be checked. 

See Unbalanced 3-Phase Supply Voltage section on 

page 11

.

table 2. copper Wire Size

coPPEr WirE SizE — aWg

(1% VoltagE DroP)

SuPPlY WirE lEngtH-FEEt

SuPPlY circuit

amPacitY

200

150

100

50

6

8

10

14

15

4

6

8

12

20

4

6

8

10

25

4

4

6

10

30

3

4

6

8

35

3

4

6

8

40

2

3

4

6

45

2

3

4

6

50

2

3

4

6

55

1

2

3

4

60

Wire Size based on N.E.C. for 60° type copper conductors.

condensate Drain

Condensate is removed from the unit through the 3/4” 

female pipe fitting located on the front side of the unit. 
See 

Figure 6

. Install a 2 inch condensate trap in the 

drain line of the same size and prime with water. When 

connecting rigid drain line, hold the female fitting with a 

wrench to prevent twisting. 

Do not over tighten!

 Refer 

to local codes and restrictions for proper condensate 

disposal requirements.

Содержание Q6SE X36

Страница 1: ... plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedtoassistqualifiedindividualsexperiencedintheproper installation of this appliance Some local codes require li...

Страница 2: ...2 ...

Страница 3: ... the Heat Pump for Automatic Cooling Heating 5 Operating the Indoor Blower Continuously 5 Shutting the Heat Pump Off 5 HEAT PUMP MAINTENANCE 5 Regular Cleaning 5 TROUBLESHOOTING 5 Warranty Information 5 START UP adjustments 13 Pre Start Check List 13 Start Up Procedure 13 Air Circulation 13 Short Cycle Protection 13 System Cooling 13 System Heating 13 Refrigerant Charging 13 Charging an R 410A Uni...

Страница 4: ...hange the fan mode to AUTO See Figure 1 2 Setthetemperatureselectortothedesiredtemperature level Theoutdoorfan compressor andblowermotorwill all cycle on and off to maintain the indoor temperature at the desired cooling level NOTE If the temperature level is re adjusted or the system mode is reset the fan and compressor in the outdoor unit may not start immediately A protective timer circuit holds...

Страница 5: ... service on the system Failure to comply may result in personal injury or death Proper maintenance is most important to achieve the best performancefromtheapplianceandshouldbeperformed by a qualified service technician at least once a year Follow the maintenance schedule and the instructions below for years of safe trouble free operation Regular Cleaning Clean or replace the indoor air filter at t...

Страница 6: ...authorized parts or accessory kits may be used with this product Improper installation service adjustment ormaintenance may cause explosion fire electrical shock or other hazardous conditions which may result in personal injury or property damage WARNING The safety information listed below must be followed during the installation service and operation of this unit Unqualified individuals shouldnot...

Страница 7: ... calculatedandasystemofthepropercapacityselected It is recommended that the area to be conditioned be completely insulated and vapor sealed Check the electrical supply and verify the power supply is adequate for unit operation If there is any question concerning the power supply contact the local power company Allunitsaresecurelypackedatthetimeofshipmentand upon arrival should be carefully inspect...

Страница 8: ...ans are used to hoist the unit are safe and adequate The lifting equipment must be adequate for the load Refer to Table 5 page 15 for unit weights The unit must be lifted from the holes in the base rails using cables or chains Spreader bars are required to protect the unit and ensure even loading Keep the unit in an upright position at all times The rigging must be located outside the units center...

Страница 9: ...ccess panel was designed to fit underneath the top panel 2 Slide the first filter between both guide channels of filter rack and allow the filter to drop easily into place 3 Verify the bottom of the filter is within the channels of the rack 4 Slide the 2nd filter and 3rd filter on taller models between both guide channels of filter rack 5 Verify the top of the filter is within the channels of the ...

Страница 10: ...ct it to the terminal marked 208V Optional equipment requiring connection to the power or control circuits must be wired in strict accordance of the NEC ANSI NFPA 70 applicable local codes and the instructions provided with the equipment ELECTRICAL WIRING WARNING To avoid risk of electrical shock personal injury ordeath disconnectallelectricalpowertotheunit before performing any maintenance or ser...

Страница 11: ...ermostat connections are listed in Table 3 page 12 The thermostat should be mounted about 5 feet above theflooronaninsidewall DONOTinstallthethermostat on an outside wall or any other location where its operationmaybeadverselyaffectedbyradiantheatfrom fireplaces sunlight or lighting fixtures and convective heat from warm air registers or electrical appliances Refer to the thermostat s instruction ...

Страница 12: ...y 6 hours and 4 minutes unless the coil temperature is above the selected terminate temperature Thesystemcanbemanuallyforcedintodefrostmodeat any time by shorting the TEST terminals on the demand defrost board together for more than 9 seconds The coil temperature sensor does not need to be cold when the unit is forced into defrost After the TEST input is removed thedefrostmodewillterminatein13 7mi...

Страница 13: ...nit are free from obstructions and debris and all equipment access control panels are in place Verifythattheductworkissealedtopreventairleakage Verify that the line voltage power leads are securely connected and the unit is properly grounded Verify that the low voltage wires are securely connected to the correct leads on the low voltage terminal strip Verify that the outdoor fan turns freely Verif...

Страница 14: ...structed with sheet metal WARNING Do not place combustible material on or against the unit cabinet Do not place combustible materials including gasoline and any other flammable vapors and liquids in the vicinity of the unit CAUTION The unit should never be operated without a filterinthereturnairsystem Replacedisposable filters with the same type and size Proper maintenance is important to achieve ...

Страница 15: ... 24 9 13 5 16 12 13 3 13 5 16 12 CG A 47 5 75 NPT Female Drain Connector B DOWNFLOW SUPPLY DUCT OPENING DOWNFLOW RETURN DUCT OPENING 23 5 Back View 13 5 16 0 13 7 13 5 16 0 12 45 11 75 22 75 55 8 C HORIZONTAL SUPPLY DUCT OPENING HORIZONTAL RETURN DUCT OPENING 4 0 CONDENSING COIL 5 0 8 4 00 Side View 1 1 4 Ø Power Entry 1 3 4 Ø Power Entry Capped 22 25 Ø Control Wiring Entry 23 3 5 27 1 5 30 1 4 5 ...

Страница 16: ...FROST BOARD Typical Wiring for Two Stage Heat Pump Cool Operation Economizer HP Cool E R W1 O Y2 C G A1 Y1 UNIT LOW VOLTAGE TERMINAL BOARD Y2 E R W2 IN O Y C M 1 2 3 4 5 6 7 8 9 Brown ACCESSORY HEAT PLUG 1 2 3 4 5 6 7 8 9 ECONOMIZER PLUG IF APPLICABLE SEE ECONOMIZER INSTALLATION INSTRUCTIONS Blower Relay See Note L W2 OUT W2 FACTORY WIRING FIELD WIRING NOTE If installing an economizer using the ne...

Страница 17: ...DEFROST BOARD ACCESSORY HEAT PLUG E R W1 O Y2 C G A1 Y1 UNIT LOW VOLTAGE TERMINAL BOARD Y2 M E R W2 IN O Y C Typical Wiring for Two Stage Heat Pump Cool Operation Economizer HP Cool 1 2 3 4 5 6 7 8 9 ECONOMIZER PLUG IF APPLICABLE SEE ECONOMIZER INSTALLATION INSTRUCTIONS See Note Blower Relay See Note W2 OUT L W2 FACTORY WIRING FIELD WIRING NOTE If installing an economizer using the new Honeywell W...

Страница 18: ...TIME IS ACCUMLATED OPENING OF DFT DURING DEFROST OR INTERVAL PERIOD RESETS THE INTERVAL TO 0 NOTE See Installation Instructions for wiring application and Information concerning accessory Heat Kits and other options WIRING DIAGRAM 10160710 1 2 3 4 5 6 7 8 9 9 8 1 7 6 5 4 3 2 9 8 1 7 6 5 4 3 2 T2 T1 T3 R C S T2 T1 N G L C T3 T4 T5 TO 208 230 VAC POWER SUPPLY 9 8 1 7 6 5 4 3 2 9 8 1 7 6 5 4 3 2 3 PH...

Страница 19: ...CK YELLOW YELLOW BLACK GREEN RED BROWN WHITE BLUE BLACK WHITE YELLOW GREY ORANGE BROWN YELLOW BLACK RED RED BROWN BLACK RED RED YELLOW GREEN BLACK BLACK 460 Volt Convertible Packaged Heat Pump Three Phase 60Hz WIRING DIAGRAM NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 If any of the original wire as supplied with the furnace must be replaced i...

Страница 20: ...when above curve Add refrigerant when below curve Figure 12 Charging Chart for 3 Ton Units Q6SE X48 Charging Chart Cooling 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Liquid Temperature F Remove refrigerant when above curve Add refrigerant when below curve Figure 13 Charging Chart for 4 Ton ...

Страница 21: ...1 20 01 1358 20 94 1279 22 23 X48 Tap T1 952 29 87 901 31 56 864 32 91 728 39 06 672 42 31 583 48 77 508 55 97 Tap T2 1646 17 27 1593 17 85 1520 18 71 1476 19 26 1417 20 07 1349 21 08 1265 22 48 1198 23 73 Tap T3 1764 16 12 1705 16 68 1626 17 49 1570 18 11 1525 18 65 1451 19 60 1403 20 27 1304 21 81 Tap T4 1962 14 49 1916 14 84 1838 15 47 1787 15 91 1720 16 53 1670 17 03 1595 17 83 1537 18 50 Tap ...

Страница 22: ...22 ...

Страница 23: ...23 ...

Страница 24: ...uct Safety should always be the deciding factor when installing this product and using common sense plays an important role as well Pay attention to all safety warnings and anyotherspecialnoteshighlightedinthemanual Improperinstallationof the unit or failure to follow safety warnings could result in serious injury death or property damage These instructions are primarily intended to assist qualifi...

Отзывы: