6
Analog input
SPIDER is designed with one analog input
0 ... 20 mA / 4 … 20 mA.
Numbers of analog mA inputs
1
Electrically isolated
No
Measuring range
0 / 4
–
20mA
Input impedance
Approx
. 100 Ω
Measuring accuracy
+/- 1% af FS
Signal area
0-24mA / 0
–
30 V DC
Signal frequence
Max. 100 Hz
Kabel / signal lenght
Max. 100m
Digital input with the option of 0-10V analog
SPIDER has 6 digital inputs, all of which can be selected as 0-10V analog voltage inputs.
Numbers of digital inputs
6
Electrically inslated
No
Digital signal
Low < 5 V / < 1 mA
High> 12 V / > 4 mA
Analog measuring range
0
–
10 V DC
Analog signal impedance
Approx
. 20KΩ
Measuring accuracy
+/- 1% of FS
Signal range (min / max)
0
–
30 V DC
Signal f frequence
Max. 100 Hz
Kabel / signal lenght
Max. 100m
Digital output
SPIDER is equipped with 4 digital relay outputs.
Numbers of digital outputs
4
Electrically isolated
Yes
Insulation voltage
4 KV
Relay type
Relay output
Kabel / signal lenght
Max. 100m
Relay NO #11 og #21
Constant load
max. 10 A @ 230Vac - AC1
max. 500 W @ 230Vac - AC3
max. 1 A @ 48 VDC
max. 10 A @ 24 VDC
Minimum current
5 mA @ 10 V
Max. Start-up current
18A
Switch speed
Max. 1 Hz
Relay NO #31 og #41
Constant load
max. 2 A @ 230Vac - AC1
max. 100 W @ 230Vac - AC3
max. 1 A @ 30 VDC
Minimum current
5 mA @ 10 V
Max. Start-up current
6A or 10A @ 20 ms
Switch speed
Max. 10 Hz