29
Pump control
FP32U
FP32U
FP32
FP32U
FP32U
FP32U
FP32U
FP32U
FP32U
Current
Min. current
Latest
operating
time
Latest
capacity
Outlet flow
Inlet flow
Total
quantity
Quantity
today
Quantity
yesterday
Pump 1
26
44
64
58
116
144
172
Pump 2
28
48
66
60
118
146
174
Common
226
78
Description
Current
from energy
meter, coil
or CUE
(Amps with
1 decimal)
Low current
limit (Amps
with 1
decimal) “If
min. current is
not exceeded,
start failure
occurs after 60
sec”
Seconds
Calculated
capacity
(L/s with 2
decimals)
Calculated
flow (L/s
with 2
decimals)
Calculated
flow (L/s
with 2
decimals)
Calculated
quantity (m³
with 2
decimals)
Calculated
quantity
(m³ with 2
decimals)
Calculated
quantity (m³
with 2 decimals)
Pump control
Signal
FP32U
Setpoints
Start level 1
1. start
50
Start level 2.
2. start
52
Stop level 1.
1. stop
54
Stop level 2.
2. stop
56
External gauges
FP32U
FP32U
FP32U
Total
Today
Yesterday
Flow gauge
250
252
254
Description
Flow pulse (m³ with 2 decimals) If a
pulse input is used, it needs to be in
the same resolution as the pulse
Flow pulse (m³ with 2 decimals) If a pulse
input is used, it needs to be in the same
resolution as the pulse
Flow pulse (m³ with 2 decimals) If a
pulse input is used, it needs to be in the
same resolution as the pulse
Energy meter
238
240
242
Description
(kW with 1 decimal)
(kW with 1 decimal)
(kW with 1 decimal)
Rain gauge
256
258
260
Description
(0,2 mm per pulse with 1 decimal)
(0,2 mm per pulse with 1 decimal)
(0,2 mm per pulse with 1 decimal)
Converters
FP16U
FP16U
FP16U
FP16U
CUE Amp.
CUE Hz
CUE kW
CUE ref
1853
1852
1851
1850
1803
1802
1801
1800
Description
(Amps with 1 decimal)
(Hz with 1 decimal)
(kW with 2 decimal)
(Hz with 1 decimal)
Pump word: P1=Register 70 P2=Register 72
Warning
Alarm
Bit 0: Pump startet
Running
Running
Bit 1: Pump error - Therma
Thermal error
Bit 2: Pump error - Klixon
Klixon error
Bit 3: Pump - manual mode
Manual mode
Bit 4: Pump error - operation signal not recieved
Starting error
Bit 5: Pump warning - Low flow
Low flow