FAULTS
SUPPLY FAULT
– This LED will be ON whenever the Main Supply has been removed or has dropped below 20 Volts.
BATTERY FAULT
– Indicates that there is low voltage level on the batteries or the battery charger circuit has failed.
AUX. SUPPLY FAULT
– Indicates that the Auxiliary Supply has a fault.
EARTH FAULT
– When this indicator is ON, there is leakage current flowing between the Earth connection/wiring and any
other wire connected to the panel.
SOUNDER FAULT
–
If there is a conventional sounder circuit fault, the general FAULT LED will be lit and the DISABLE
SOUNDERS LED in the DISABLEMENTS section will be flashing.
ZONES & INPUTS
Individual zone and monitored input indicators are provided for both FIRE/ALARM, EXTINGUISH and FAULT conditions. If
any of these inputs is disabled, then its Fault LED will also be used to indicate the disablement of that particular zone/ input.
The zone/ Input Disabled LED will be ON along with the associated disabled status LED. Flashing Fault LED along with
general Fault LED indicates fault on that zone.
CONTROLS
-
AUTHORISED USER CODE: 2244
Some keys will only be operational at the repeater after entering the authorised user code. If the operation of a switch is only
available after successfully entering the authorised user code, it will be clearly stated in this manual that these functions are
only active at Access Level 2.
NOTE:
If active please SILENCE INTERNAL BUZZER before entering code.
The four numbered keys are used to enter digits from 1 to 4 for authorised user code entry.
BUZZER SILENCE (1)
– At Access Level 1 this button is used to silence the panel's internal buzzer. Access Level 2 used to
confirm/accept changes in programming.
RESET (2)
– Press this button to reset the panel at Access Level 2.
LAMP TEST (3)
– Press this button at Access Level 1 or 2 to test all LED indicators and the panel's internal buzzer. Release
when test is finished.
SOUNDERS (4)
– Press once to activate/silence sounders. If sounders are active, for example, during a FIRE condition or in
the event of an Evacuation action, pressing this button will stop the sounders. Auxiliary Relays are not affected by this
action. When selected the disablements in Level 2, this button is used to choose the desired disablement.
6