Installation & Operation Manual

STEP THREE:

TEST OPERATION

2. Supply water to fixture and flush air from 

system.

4. De-activate safety equipment. Alarm horn and 

strobe should now automatically de-activate.

1. Apply power to alarm circuit. Unit should not be 

operating if safety equipment is not activated.

3. Activate safety equipment. Alarm horn should 

be sounding and strobe light should be flashing.

ASW SILENCING SWITCH ONLY. Test 
silencing switch. Push silencing button, while 
alarm is active; the horn should stop sounding 
and the strobe should continue to flash.
To reset -ASW Silencing Switch: Pull button 
firmly, an audible “pop” should be heard and a 
yellow band should be visible near the end of 
the mushroom button. NOTE: If the yellow band 
is not visible, switch is NOT reset and the horn 
will not sound the next time alarm is activated. 

YELLOW

BAND

1

5
8

" (41)

1

5

16

" (35)

WHEN FULLY EXTENDED, A VISIBLE YELLOW

BAND WILL APPEAR ON THE PUSHBUTTON

SHAFT AT THE REAR OF THE MUSHROOM

PUSHBUTTON.

ALARM SILENCING SWITCH SHOWN
ACTIVATED. TO RESET AFTER SILENCING
ALARM, ASW PUSHBUTTON MUST BE PULLED

FIRMLY TO FULLY EXTENDED POSITION.

1
2

" NPT CONDUIT

CONNECTION

Revised: 12/10/18

Содержание S0000-AL3

Страница 1: ...cement of the defective materials shall constitute the sole remedy of the Buyer and the sole remedy of Acorn under this warranty Acorn shall not be liable under any circumstances for incidental conseq...

Страница 2: ...3 Flush water supply lines prior to installation This will remove unwanted debris from the lines and prevent unwanted blockages in the safety equipment Page 2 of 9 Acorn Safety a division of Acorn En...

Страница 3: ...50 6 MIN 150 125 250VAC 5A DPDT DOUBLE POLE DOUBLE THROW FLOW SWITCH GENERAL NOTES 1 ALL DIMENSIONS ARE IN INCHES MM 2 FLOW SWITCH SHALL BE INSTALLED VERTICALLY WITH HORIZONTAL FLOW 3 DIRECTION OF WAT...

Страница 4: ...ELECTRICAL WIRING S0000 AL3 WIRE AND CONNECTORS BY OTHERS WIRE AND CONNECTORS BY OTHERS EXISTING WIRES NOTES NC WHITE BLACK BLACK BLACK NO C GREEN WHITE BLACK TOP LIGHT SIGNAL LIGHT SIGNAL GREEN HORN...

Страница 5: ...LECTRICAL WIRING WIRE AND CONNECTORS BY OTHERS WIRE AND CONNECTORS BY OTHERS EXISTING WIRES NOTES NC WHITE BLACK BLACK BLACK NO C FLOW SWITCH GREEN WHITE BLACK TOP LIGHT SIGNAL LIGHT SIGNAL GREEN HORN...

Страница 6: ...3 and at least 6 from closest fitting l Flow Switch direction of flow is indicated on switch body SUPPLIES REQUIRED not provided by Acorn l Use hand tools and wrenches in a manner which will prevent...

Страница 7: ...locate the alarm near emergency equipment and in a manner that would allow it to be readily visible by employees and quick reaction or emergency personnel when activated 3 Connect wiring supplied by o...

Страница 8: ...h Push silencing button while alarm is active the horn should stop sounding and the strobe should continue to flash To reset ASW Silencing Switch Pull button firmly an audible pop should be heard and...

Страница 9: ...arm should the unit fail to operate Do not attempt repair MAINTENANCE Perform visual inspection and an operational test twice a year ITEM PART NUMBER DESCRIPTION 1 7103 115 000 ALARM AMBER STROBE WITH...

Отзывы: