Acorn Safety S0000-AL3 Скачать руководство пользователя страница 7

Page 7 of 9

  

Acorn Safety

 

a division of Acorn Engineering

Manual #7109-305-001

Installation & Operation Manual

4. Connect the ground wires and ground in 

accordance of local and NEC National Electrical 
Code requirements. A green ground screw is 
provided on the alarm box (or J-box).

STEP ONE:

FLOW SWITCH INSTALLATION

1. Determine location of flow switch in water 

supply line. The inlet and outlet ports of the flow 
switch must be a minimum of 6” from any tees 
or elbows (as shown on page 3) in the water 
supply line. Refer to page 6 and rough-in 
drawing.

2. Pipe the flow switch in-line of fixture supply 

inlet. The switch body must be in the vertical 
position with the water pipe horizontal. The 
water flow must be in the direction of the arrow 
that is marked on the flow switch body. Refer to 
page 6 and rough-in drawing.

STEP TWO:

ALARM INSTALLATION

2.Attach alarm hanger plate as shown with angled 

flange in an upward orientation.

1. Determine mounting method and location of 

alarm. As a recommendation, locate the alarm 
near emergency equipment and in a manner 
that would allow it to be readily visible by 
employees and quick reaction or emergency 
personnel when activated.

3. Connect wiring (supplied by others) to the 

terminals within the flow switch junction box as 
shown in the appropriate wiring diagram. Extra 
set of wiring terminals provided for remote 
monitoring, not shown.

3. Field wire flow switch to alarm box (or J-box). 

Provide electrical service wiring to alarm box (or 
J-box). Note: Circuit wiring should not be 
energized at this time. It is recommended that 
the alarm and other components be installed in 
accordance of national and local electrical 
codes.

5. Connect flow switch field wiring and electrical 

service wiring to alarm terminals as indicated in 
wiring diagram.

6. Hang the horn/strobe assembly over the hanger 

plate with the mounting screw at the bottom, 
then tighten mounting screw to secure..

7. Apply power to the circuit and test to verify 

operation.

SURFACE MOUNTING J-BOX

(NTS)

2" [51]

3"

[76]

1
2

" NPT REMOVABLE

BOX PLUGS

#10 x 1-1-4" LONG PHILLIPS

HEAD SCREWS PROVIDED

CAP PLUGS

PROVIDED

Ø

1
4

" [6.3] FIELD

DRILLING REQUIRED

2" [51]

1

1
2

"

[38]

HANGER PLATE

HORN / STROBE

ASSEMBLY

Revised: 12/10/18

Содержание S0000-AL3

Страница 1: ...cement of the defective materials shall constitute the sole remedy of the Buyer and the sole remedy of Acorn under this warranty Acorn shall not be liable under any circumstances for incidental conseq...

Страница 2: ...3 Flush water supply lines prior to installation This will remove unwanted debris from the lines and prevent unwanted blockages in the safety equipment Page 2 of 9 Acorn Safety a division of Acorn En...

Страница 3: ...50 6 MIN 150 125 250VAC 5A DPDT DOUBLE POLE DOUBLE THROW FLOW SWITCH GENERAL NOTES 1 ALL DIMENSIONS ARE IN INCHES MM 2 FLOW SWITCH SHALL BE INSTALLED VERTICALLY WITH HORIZONTAL FLOW 3 DIRECTION OF WAT...

Страница 4: ...ELECTRICAL WIRING S0000 AL3 WIRE AND CONNECTORS BY OTHERS WIRE AND CONNECTORS BY OTHERS EXISTING WIRES NOTES NC WHITE BLACK BLACK BLACK NO C GREEN WHITE BLACK TOP LIGHT SIGNAL LIGHT SIGNAL GREEN HORN...

Страница 5: ...LECTRICAL WIRING WIRE AND CONNECTORS BY OTHERS WIRE AND CONNECTORS BY OTHERS EXISTING WIRES NOTES NC WHITE BLACK BLACK BLACK NO C FLOW SWITCH GREEN WHITE BLACK TOP LIGHT SIGNAL LIGHT SIGNAL GREEN HORN...

Страница 6: ...3 and at least 6 from closest fitting l Flow Switch direction of flow is indicated on switch body SUPPLIES REQUIRED not provided by Acorn l Use hand tools and wrenches in a manner which will prevent...

Страница 7: ...locate the alarm near emergency equipment and in a manner that would allow it to be readily visible by employees and quick reaction or emergency personnel when activated 3 Connect wiring supplied by o...

Страница 8: ...h Push silencing button while alarm is active the horn should stop sounding and the strobe should continue to flash To reset ASW Silencing Switch Pull button firmly an audible pop should be heard and...

Страница 9: ...arm should the unit fail to operate Do not attempt repair MAINTENANCE Perform visual inspection and an operational test twice a year ITEM PART NUMBER DESCRIPTION 1 7103 115 000 ALARM AMBER STROBE WITH...

Отзывы: