Acorn Safety S0000-AL3 Скачать руководство пользователя страница 2

Installation & Operation Manual

1. Read the installation instructions prior to beginning the installation.

2. Separate parts from packaging and verify all necessary parts are accounted for and undamaged. Obtain missing or 

damaged parts from Acorn Safety prior to beginning installation.

4. In order to comply with ANSI Z358.1, the safety equipment must be inspected periodically. An inspection tag is provided for 

documentation purposes.

5. All employees at risk of contamination should be informed and trained in the use of this and any other safety equipment. 

The signage provided should be posted appropriately in close proximity to this equipment.

PRELIMINARY STEPS

3. Flush water supply lines prior to installation.  This will remove unwanted debris from the lines and prevent unwanted 

blockages in the safety equipment.

Page 2 of 9

  

Acorn Safety

 

a division of Acorn Engineering

Manual #7109-305-001

ROUGH-IN

S0000-AL3 FLUSH MOUNT

5

1
2

" SQ.

(140)

HANGER
PLATE

AMBER STROBE

1 FLASH PER SECOND

ALARM HORN

90 dB AT 10 FEET

2

1
2

" (65)

4

7
8

" (125)

5
8

" (15)

J-BOX & J-BOX EXTENSION

BY OTHERS

6" MIN

[150]

6" MIN

[150]

125 / 250VAC, 5A DPDT

DOUBLE POLE, DOUBLE

THROW FLOW SWITCH

GENERAL NOTES:

1. ALL DIMENSIONS ARE IN INCHES [MM].

2. FLOW SWITCH SHALL BE INSTALLED VERTICALLY WITH HORIZONTAL FLOW.
3. DIRECTION OF WATER FLOW MUST BE IN SAME DIRECTION AS SHOWN ON FLOW SWITCH.
4. J-BOX AND J-BOX EXTENSION BY OTHERS.

UNIONS & PIPE

SUPPLIED BY OTHERS

FLOW

12"

[305]

3
4

" NPTI CONDUIT

CONNECTION

FLUSH MOUNTING

KEEP SWITCH

BODY VERTICAL

HORN / STROBE

ASSEMBLY

Revised: 12/10/18

Содержание S0000-AL3

Страница 1: ...cement of the defective materials shall constitute the sole remedy of the Buyer and the sole remedy of Acorn under this warranty Acorn shall not be liable under any circumstances for incidental conseq...

Страница 2: ...3 Flush water supply lines prior to installation This will remove unwanted debris from the lines and prevent unwanted blockages in the safety equipment Page 2 of 9 Acorn Safety a division of Acorn En...

Страница 3: ...50 6 MIN 150 125 250VAC 5A DPDT DOUBLE POLE DOUBLE THROW FLOW SWITCH GENERAL NOTES 1 ALL DIMENSIONS ARE IN INCHES MM 2 FLOW SWITCH SHALL BE INSTALLED VERTICALLY WITH HORIZONTAL FLOW 3 DIRECTION OF WAT...

Страница 4: ...ELECTRICAL WIRING S0000 AL3 WIRE AND CONNECTORS BY OTHERS WIRE AND CONNECTORS BY OTHERS EXISTING WIRES NOTES NC WHITE BLACK BLACK BLACK NO C GREEN WHITE BLACK TOP LIGHT SIGNAL LIGHT SIGNAL GREEN HORN...

Страница 5: ...LECTRICAL WIRING WIRE AND CONNECTORS BY OTHERS WIRE AND CONNECTORS BY OTHERS EXISTING WIRES NOTES NC WHITE BLACK BLACK BLACK NO C FLOW SWITCH GREEN WHITE BLACK TOP LIGHT SIGNAL LIGHT SIGNAL GREEN HORN...

Страница 6: ...3 and at least 6 from closest fitting l Flow Switch direction of flow is indicated on switch body SUPPLIES REQUIRED not provided by Acorn l Use hand tools and wrenches in a manner which will prevent...

Страница 7: ...locate the alarm near emergency equipment and in a manner that would allow it to be readily visible by employees and quick reaction or emergency personnel when activated 3 Connect wiring supplied by o...

Страница 8: ...h Push silencing button while alarm is active the horn should stop sounding and the strobe should continue to flash To reset ASW Silencing Switch Pull button firmly an audible pop should be heard and...

Страница 9: ...arm should the unit fail to operate Do not attempt repair MAINTENANCE Perform visual inspection and an operational test twice a year ITEM PART NUMBER DESCRIPTION 1 7103 115 000 ALARM AMBER STROBE WITH...

Отзывы: