ACME 924738 Скачать руководство пользователя страница 8

Overview 

The FSC-1 is a digital EC motor control.  The control has a simple 

five

 bu

on interface with a four digit LED 

display.  All programmable parameters can be accessed through the user menu with the 

five

 bu

on interface.  

There are two ECM connectors with modula

ng outputs, one 0-10V output, and one 0-10V DC input.  The FSC-

1 is compa

ble with Telco Green, Genteq, Nidec, and U.S. Motors.  User parameters are stored in non-

vola�

le 

memory, and are retained 

ev

en during a power outage.  The FSC-1 is powered by 24V AC. 

Normal Opera

on 

Pulse Applica

on 

Eve

ry ten seconds the FSC-1 display will toggle between the current percent of run speed and the current 

RPMs.  The percent of run speed can be changed by using the 

 and 

 keys followed by the 

 key to 

save

 your changes.  You also h

av

e the 

op�

on of using the control locally or remotely through a poten

ometer, 

2 Speed Switch, or a 0-10V reference where 0V is 0% and 10V is 100%, unless 

ov

erridden by the low speed and 

high speed limits.  You can access programming mode by holding the enter key for three seconds.   

0-10 Applica

on

In the 0-10V applica

�on

 you are pr

ovi

ded a programmable 0-10V reference.  The

display shows the selected 

vo

ltage.  The 

vo

ltage is easily changed using the

 and 

 keys followed by the 

 key to 

sav

e your changes.  

Programming 

Please refer to the “FSC-1 Menu Map” on page 9  for 

edi�ng 

parameters within program mode.   To enter

program mode hold the 

 key for three seconds 

un�l

 “APPS” is displayed.  Use the 

 and

 keys to 

navigate

 to the desired menu parameter shown in column 1 of the menu map on page 9.  To edit a menu

parameter press the 

 key once on the desired parameter.  The current 

va

lue will be displayed in column 2 

 and 

 keys to change 

val

ues within a parameter.  The 

of the menu map on page 9.  Also use

parameter will blink 

un�l 

the user presses

to 

save

 the changes or the 

 key to cancel without 

saving. 

If a key is not pressed for 

fi�een

 seconds, the control will return to normal 

opera�ng

 mode.  

Different

parameters are as follows: 

1. “APPS”: Prompts the user to select which applica

�o

n to u

�l

ize.

2. “SP1”: Sets the speed of the motor for Setpoint 1.

3. “SP2”: Sets the speed of the motor for Setpoint 2.

4. “LSPD”: Sets the lowest possible speed the motor will operate at.  If the

 bu

on is pressed one 

more 

�me

 passed the “LSPD” limit, the control will turn 

off.

5. “hSPD”: Sets the highest possible speed the motor can operate at.

6. “tyP”: Sets the type of motor the control is 

configured

 for.  The FSC-1 is 

compa�ble

 with

Genteq, Nidec and US motors.

7. “re”: Allows the user to select local control or remote control type.

8.

“ver”:

 Allows the user to 

view

 the current 

so�ware

 

version

 number.

FSC-1 DIGITAL CONTROL SETUP 

Control is only used on ECM motors

Page 8

Содержание 924738

Страница 1: ...ill not be responsible for damage during storage These suggestions are provided solely as a convenience to the user who shall make his own decision as to whether to use any or all of them INDOOR The ideal storage environment for fans and accessories is indoors above grade in a low humidity atmosphere which is sealed to prevent the entry of blowing dust rain or snow Temperatures should be evenly ma...

Страница 2: ...ovide ignition to combustible or flammable materials unless the unit is specifically built for hazardous environments 3 WARNING If gases other than clean air are to be exhausted using the fan then the user bears the responsibility of determin ing that the fan is appropriate and safe for the application 4 Provide a square opening in the wall equal to the outside dimensions of the fan It is preferab...

Страница 3: ...ather resistant only they are not weatherproof NOTE Not all sizes in chart are available in all fan models WALL MOUNTED FACE MOUNT Exhaust or Supply R Fans Illustrated is a typical installation when mounting the fan directly to the wall Flashing over damper by others Propeller to damper distance M is important to reduce turbulence and damper flutter which may lead to premature damper failure See F...

Страница 4: ...ional support using hanging rods or support from underneath It is preferable to frame in the opening with 2 x 6 material or similar suitable materi al or metal channels adequate for support of the fan The installer provides suitable fasteners hex bolts or lag screws to secure the fan Dampers are designed to reduce drafts prevent entry of for eign material and limit the amount of rain that enters t...

Страница 5: ...ainte nance checks are preformed prior to restarting the unit 6 Inspect all moving parts for damage or rust and clean area SET SCREW TIGHTENING SCHEDULE 1 Before initial operation of the fan tighten set screws according to the procedure outlined below 2 After 500 operating hours or three months whichever comes first tighten set screws to the full recommended torque 3 At least once a year tighten s...

Страница 6: ...u use arrows to apply fan order speed Brown 0 10VDC to Motor Blue Common White Black Black Black Red Green Yellow Green Handi Box Disconnect Switch Motor Yellow White Yellow White 115 V Red 208 V Orange 230 V Brown 277 V Connect to wire of input voltage and insulate the rest 115 or 208 230 VAC 1 Ph 24 VAC Transformer POWER INPUT LINE ECM MOTOR WIRING FOR GENTEQ MOTORS ONLY USING THE FSC 1 CONTROLL...

Страница 7: ...ellow Yellow White Motor Handi Box Disconnect Switch BY OTHERS Green Green Yellow Red Black Black Black White Blue Brown W h i t e A B White Red Black not used Speed control may be mounted up to 100 ft away from fan Hold down center button to access menu Use arrows to navigate apply these settings APPS to 0 10 SP1 too Speed 1 SP2 to Speed 2 tYPE to tC42 rE to 2Spd Once out of menu use arrows to ap...

Страница 8: ...by the key to save your changes Programming Please refer to the FSC 1 Menu Map on page 9 for edi ng parameters within program mode To enter program mode hold the key for three seconds un l APPS is displayed Use the and keys to navigate to the desired menu parameter shown in column 1 of the menu map on page 9 To edit a menu parameter press the key once on the desired parameter The current value wil...

Страница 9: ...GENTEQ US Motor Page 9 ...

Страница 10: ...c fields in the vicinity of current carrying conductors and permanent magnet motors can result in a serious health hazard to persons with cardiac pacemakers metal implants and hearing aids To avoid risk stay away from the area surrounding a permanent magnet motor WARNING Do not remove cover for at least five 5 minutes after AC power is disconnected to allow capacitors to discharge Dangerous voltag...

Страница 11: ...s Rotation can be changed by swapping any of the Red Black and Blue wires connecting the control board to the motor at terminals T1 T2 and T3 INSTALLATION 1 Wire motor in accordance with local codes The motor can be mounted by the feet or face See Figure 14 for mounting hole locations Verify fasteners holding motor to fan are properly secured 2 Verify fan wheel is properly secured on motor shaft 3...

Страница 12: ...tch will select the Low LO or High HI speed on the speed controllers based on the dial settings Toggle switch and mounting plate fit in a standard gang box and wired to Dual Potentiometer Speed Dial The speed dial can be mounted up to 100 ft from fan using additional wire by others Building Control 0 10VDC Wire Kit See Figure 20 Factory mount ed Molex receptacle that allows a quick connection to s...

Страница 13: ...lding Supplied Controller Not Used with Building Supplied Controllers White Green Ground Black N L1 L2 Motor Control Box Line Voltage 208 230 VAC Single Phase 14 AWG Remote Potentiometer A Variable 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Speed B Potentiometers mounted up to 100 ft from fan FIGURE 17 FIGURE 18 Page 13 ...

Страница 14: ...in that they are secure Fault Indication A red LED on the control board provides fault indication During a fault this LED will blink a specific number of times to identify the fault that has occurred The table below describes these fault indications Maintenance EBSM motors use brushless technology with sealed bearings so no maintenance is required other than keeping any accumulated debris from col...

Страница 15: ... potentiometer box Speed B on box is not used for single speed selection and will not have a dial The motor will shut off between 0 1 9V Two Speed Dial See Figure 23 Motor will come with a prewired control cable and wired to a mounted dual speed potentiometer dial that is used to control the speed of the motor The supplied un mounted toggle switch will select the Low LO or High HI speed on the spe...

Страница 16: ...peed Potentiometer Speed Select Control A Black Red White Wired in Field B Red to Red White to White Black to Black Potentiometers and speed selector can be mounted up to 100 ft from fan A Variable 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Speed B Page 16 FIGURE 24 FIGURE 23 ...

Страница 17: ...View PARTS LIST LEGEND No Description Qty No Description Qty 1 Propeller 1 6 Motor Mounting Nuts 4 2 Orifice 1 7 Key 1 3 Frame Assembly 1 8 Frame Mounting Bolts 6 4 Motor 1 9 Frame Mounting Nuts 6 5 Motor Mounting Bolts 4 FIGURE 25 ...

Страница 18: ...ely claim the Company shall have the option either to inspect the product while in Purchaser s possession or to request Purchaser to return the product to the Company at Purchaser s expense for inspection by the Company The Company shall replace or at its option repair free of charge any product it determines to be defective and it shall ship the repaired or replacement product to Purchaser F O B ...

Отзывы: