6.2 Calibration Procedure
When operator enters “calibrate” menu, “calibrate the unit?” question is presented. If the
operator confirms that their intention is to calibrate the unit, the unit drives 4-20mA output to
2mA and de-asserts all gas alarms. This state is retained for 2 minutes after the calibration is
over to allow gas sensor to recover from the high gas concentration applied during calibration.
Calibration is deemed over after the operator leaves the “calibrate” menu, either by successfully
completing calibration or by canceling calibration.
6.2.1 Zero
Adjustment
ALARM 1
> 50.0%LEL
F
A1 A2 A3
Figure 6-2: Alarm 1 Menu
Operator chooses “calibrate”, “Zero” in the menu. Operator then applies Zero gas concentration
to the sensor. Sensor displays the current concentration of the gas in the upper line and a
moving block character in the lower line. Zero Buffer functionality is inhibited during calibration
to enable operator to see the exact measured gas concentration. The block character moves
from left to right if the concentration is rising and from right to left if it is falling. The unit
measures average concentration over an averaging period of about 10 seconds. When the
average concentration difference between the two successive 10 second periods is less than
1% of the average concentration, the block character slows down. The unit then tries to detect
that the concentration has stabilized. It does so by waiting for two rising slopes and two falling
slopes of the average 10 second concentration. Since this is a random process, it usually
takes longer than 40 seconds. When this is detected, the block character is replaced with a
question “ok. proceed?”.
Operator does not have to wait for the “ok. proceed?” question to calibrate. Operator can at any
moment during the calibration press “yes” button to accept the currently measured
concentration as the calibrating point.
If this process takes longer than 5 minutes, the unit displays the question “unstable. cancel?”. If
“yes” is pressed, the calibration is cancelled. If “no” is pressed, the calibration continues
unaffected.