AMC-DTM-Sensor Transmitter
- 18 -
5.4.2 Type
Alarm can be of three types: Increasing, Decreasing and Disabled.
5.4.3 Name
Operator can specify the name of the alarm displayed on the Liquid Crystal Display (LCD). The
name may have up to 12 characters and can include any of the characters displayable by the
LCD.
5.4.4 Activation Delay (On Delay)
When gas concentration crosses given alarm threshold, alarm is not activated until the
concentration remains above the threshold for Activation Delay period of time. The Activation
Delay Timer is adjustable from 0 to 99 minutes in increments of 1 minute.
Silence
Timer
Activation
Delay
silence
button
relay output – silenced during Minimum Run Time
Silence
Timer
silence
button
relay output – silenced just before gas conc. dropped
Silence
Timer
0ppm
Threshold
Hysteresis
gas concentration
t
relay output – no intervention
relay output – silenced while gas concentration is high
Minimum Run
Time
silence
button
Figure 5-9: Alarm activation, silencing and deactivation