AMC-DTM-Sensor Transmitter
- 11 -
When an Alarm is declared, LCD displays Concentration Display and Alarm Display in 2 two-
second flash periods. See Figure 5-3 and Figure 5-4.
ALARM 1
> 50.0%LEL
F
A1 A2 A3
Figure 5-4: Alarm Display
The first line shows the name of the active alarm. The second line shows the condition
triggering the alarm. “>” character is used for increasing alarms and the “<” for decreasing. The
concentration value (50.0%LEL in the example) is the value of the alarm threshold. Alarm LED
rapidly flashes when the corresponding alarm is active.
It is possible to change default alarm names (ALARM 1, ALARM 2 and ALARM 3) to an
operator defined value. See Figure 5-5.
fan is on
> 10.0%LEL
F
A1 A2 A3
Figure 5-5: Alarm display – renamed alarm
Active alarms are displayed in flash cycles together with the Default Display. Up to four displays
can be shown this way (three gas alarms and the default display). Gas alarms are mutually
exclusive. They can be active in any order or combination.
During the Minimum Run Time period, hourglass symbol is displayed in the second line. See
Figure 5-6. Alarm LED flashes slowly when the alarm is in this mode.
ALARM 1
> 50.0%LEL
F
A1 A2 A3
Figure 5-6: Alarm display during Minimum Run Time
When alarm is silenced, the character “s” is also displayed together with the hourglass symbol
during the silence period. See Figure 5-7. Alarm LED flashes slowly when the alarm is in this
mode.